7. Description of the controller functions
The TROVIS 5432 Heating and District Heating Controller is designed to control the flow tem-
perature in heating systems. The control is either weather-compensated using an outdoor or
flow sensor, or based on a fixed set point for the flow temperature just using one flow sen-
sor. The flow temperature is controlled so that the required room temperature is achieved.
When used as a district heating controller, the controller can limit the return flow tempera-
ture.
The connected sensors allow the controller to measure the respective temperatures which are
transmitted to the central signal processing system.
Subsequently, the system issues a control signal corresponding to the preset set points to
operate the control valve and a binary signal for the heating circulation pump.
If a sensor for the drinking water temperature TS is connected, the drinking water priority is
automatically activated.
Fig. 3
⋅
Heating system diagram
VL
RL
AS Outdoor temperature sensor
RüS Return flow temperature sensor
VS Flow temperature sensor
UP Circulation pump
WT Heat exchanger
VL Flow
RL Return flow
22
EB 5432-1 EN
Description of the controller functions