6.2 Setting the function blocks and parameters
Note:
When you set certain function blocks, the associated parameter needs to be set, too.
The function blocks (F) and parameters (P) are listed in sequence. Further details about the
functions are described in chapter 7.
F
P
Function
S
FS
Comment / range
F= Function block P= Parameter S = Setting FS = Factory (default) settings
F 1
Operating mode
1
0
1
Weather-compensated control
Fixed set point control
(Chap. 7.1)
P1
Gradient
Heat. characteristic
1.6
0.2...3.2
P2
Level
Heating characteristic
0.0
-30.0...30.0 °C
F 2
Manual operation
1
0
0
Active
Not active
(Chap. 7.10)
F 3
Delayed outdoor
temperature adaptation
1
0
0
Active with outdoor sensor AS
(Chap. 7.2)
P7
5
1....6 °C/hr
F 4
Control signal
3-step
1
1
Three-step control
(Chap. 7.3.1)
P10
Kp Gain
2.0
0.1...50.0
P11
Tn Reset time
120
0...999 s
P12
Ty Valve transit time
45
10...240 s
Control signal on/off
0
On/off control
(Chap. 7.3.2)
P13
Differential gap
5
2...10 °C
P14
Minimum activation time
120
0...600 s
P15
Minimum deactivation time
120
0...600
s
F 5
Automatic clock reset
summer time/winter time
1
0
1
Active
Not active
F 6
Subfloor drying
1
Active
(Chap. 7.7)
0
0
Not active
20
EB 5432-1 EN
Configuration and parameterization