Manual operation
Switch to manual mode to configure all outputs (see wiring diagram in section 11).
Proceed as follows:
Position all selector mode switches to
+
,
0
or
–
.
Select
PU
pump manual level.
Open pump manual level.
Select pump PU1 to PU5:
PU1: BA11
PU2: BA12
PU3: BA13
PU4: BA14
PU5: BA15
Confirm pump selection.
The display blinks.
Activate output:
Deactivate output:
Confirm setting.
The modified values remain active as long as the controller is in manual mode.
Move slide switch from
0
,
+
or
–
.
Exit manual level.
Note!
In manual mode,
frost protection
is not guaranteed.
EB 5179 EN
27
Manual operation