Safety-related functions

3  Safety-related functions

1.  Emergency venting over the i/p converter 

(Fig. 1 path 

)

In automatic operation, the PD controller (3) compares the actual value to the DC control 
signal from 4 to 20 mA coming from the microcontroller. In case of a system deviation, 
the activation of the i/p converter is changed so that the actuator (1) is either vented or 
filled with air. Fail-safe action is triggered when no signal (0 mA) is applied to terminals 
11/12 and, as a result, to the i/p converter.

2.  Emergency venting over the optional solenoid valve 

(Fig. 1 path 

)

The solenoid valve (12) is energized by a 24 V DC voltage signal. Fail-safe action is trig-
gered when no signal (0 mA) is applied to terminals 81/82. This causes the solenoid 
valve (12) to vent the output of the i/p converter to the atmosphere. The actuator is vent-

ed as well.

3.  Safety-related end position monitoring over the optional inductive limit contact 

(Fig. 1 path 

)

The inductive limit contact SJ2-SN (NAMUR NC contact) indicates the adjusted end posi-
tion in a safety-instrumented system at terminals 41/42. See 

u

 EB 8384-3 for adjusting 

the limit contacts.

Fail-safe action

Fail-safe action is triggered by the i/p converter or solenoid valve and upon supply air fail-

ure. The positioner fully discharges its pneumatic output to the atmosphere, causing the 

mounted actuator to be vented. As a result, the valve moves to the fail-safe position. The fail-
safe position depends on how the springs are arranged in the pneumatic actuator (air-to-
close or air-to-open).
When the air supply fails and the optional solenoid valve is de-energized, all positioner 
functions, except open/closed loop control, remain active (including diagnostics, HART

®

 

communication as well as position and status feedback).

The pneumatic output of the positioner can also be vented to the atmosphere over the 

software, e.g. by entering a suitable set point. This procedure is not a safety-instrumented 

function.

Protection against unauthorized changes to the configuration

A change to the configuration cannot affect the safety function nor cause it to be deactivated.

Note

Summary of Contents for TROVIS 3730-3

Page 1: ...Safety Manual SH 8384 3 EN Translation of original instructions Edition December 2016 Series 3730 Type 3730 3 Electropneumatic Positioner with HART communication...

Page 2: ...y Property damage message or malfunction Additional information Recommended action DANGER WARNING NOTICE Note Tip The mounting and operating instructions for all supplied devices are included in the d...

Page 3: ...ation The documents listed below contain descriptions of the start up functioning and operation of the positioner You can download these documents from the SAMSON website The documents marked with an...

Page 4: ...4 SH 8384 3 EN Contents 1 Scope 5 2 Technical data excerpt from EB 8384 3 6 3 Safety related functions 8 4 Mounting connection and start up 10 5 Required conditions 11 6 Proof testing 13 7 Repairs 15...

Page 5: ...in safety instrumented systems up to SIL 2 single device HFT 0 and SIL 3 redundant configuration HFT 1 The individual safety functions of the positioner are to be regarded as Type A elements in ac cor...

Page 6: ...rotary actuators according to VDI VDE 3845 fixing levels 1 and 2 2 Technical data excerpt from EB 8384 3 Type 3730 3 Positioner also observe the technical data in the test certificates for explosion...

Page 7: ...s is given Use is possible on observing the requirements of IEC 61511 and the required hard ware fault tolerance in safety instrumented systems up to SIL 2 single device HFT 0 and SIL 3 redundant conf...

Page 8: ...ctive limit contact SJ2 SN NAMUR NC contact indicates the adjusted end posi tion in a safety instrumented system at terminals 41 42 See u EB 8384 3 for adjusting the limit contacts Fail safe action Fa...

Page 9: ...valve 13 Analog position transmitter 2 Travel sensor 14 Software limit contact alarm 1 2 3 PD controller 15 Fault alarm output alarm 3 4 A D converter 16 Display 5 Microcontroller 17 Actuation of sole...

Page 10: ...ing parts and accessories G 81 82 11 12 83 84 51 52 A2 A3 A1 41 42 31 32 A 31 32 24 V DC Solenoid valve optional mA control signal Not Ex Binary input of a PLC acc to IEC 61131 2 Pmax 400 mW or switch...

Page 11: ...zed The positioner is suitable for the prevailing ambient temperature Versions Temperature range All 20 to 80 C With metal cable gland 45 to 80 C The limits in the test certificates additionally apply...

Page 12: ...bed The vent opening at the back of the positioner remains open when the positioner is in stalled on site Electrical installation The positioner is connected to the electric power supply properly as d...

Page 13: ...in a plant PFDavg Function testing Regularly check the safety function according to the test plan drawn up by the operator Record any faults in the positioner and inform SAMSON of them in writing Emer...

Page 14: ...ner in Code 0 5 Set the voltage to 0 V DC terminals 81 82 6 Check whether the actuator is fully vented within the demanded time Connect a pressure gauge to check that the actuator has completely vente...

Page 15: ...cal and physical processes Material fatigue Aging damage caused to organic materials e g plastics or elastomer by exposure to light and heat Chemical attack organic materials e g plastics or elastomer...

Page 16: ...16 SH 8384 3 EN...

Page 17: ...ces are classified as type A Die Konformit t des Entwicklungsprozesses der durchgef hrten FMEDA und der Aussa gen dieser Herstellererkl rung sind von der T V Rheinland Industrie Service durch das Zert...

Page 18: ...iggered as fol lows The electrical input of the positioner is de energized o Types 3730 0 1 2 3 0 mA at terminals 11 12 o Types 3730 4 5 0 V voltage level at terminals IEC 1158 2 The electrical input...

Page 19: ...4 Frankfurt am Main Germany Phone 49 69 4009 0 Fax 49 69 4009 1507 samson samson de SAMSON AG SAMSON AG Guido K nig Zentralabteilungsleiter Produktmanagement und marketing Mess und Regeltechnik SAMSON...

Page 20: ...SAMSON AG MESS UND REGELTECHNIK Weism llerstra e 3 60314 Frankfurt am Main Germany Phone 49 69 4009 0 Fax 49 69 4009 1507 samson samson de www samson de SH 8384 3 EN 2017 01 18 English...

Reviews: