EB 9510 EN
9-3
Malfunctions
Table 9-2:
Troubleshooting
Error ID
Message
Possible causes and recommended action
101
AMR magnet lost
The Media 7 device has an internal device error.
Î
Contact SAMSON's After-sales Service.
102
AMR sensor not recognized
103
Memory error (calibration)
104
Memory error (data)
105
No factory calibration
106
Pressure sensor error
107
Internal data processing error
201
AMR signal outside range
Î
Reset the Media 7 device. Contact
SAMSON's After-sales Service department
when this error reoccurs.
202
Measuring span error
Î
Check the settings for the tank and media
data. Correct them, if necessary.
203
Characteristic error
An invalid tank geometry has been entered:
Î
Re-enter tank data (only possible in TROVIS-
VIEW).
204
AMR temperature sensor
The temperature sensor has failed.
Î
Reset error message. Contact SAMSON's
After-sales Service when this error reoccurs.
205
Temperature inside device below min.
limit
The temperature limit inside the device has fallen
below the adjusted min. limit.
Î
Check whether the heating functions properly
and the heating control is switched on.
Î
Select lower temperature limit.
206
Temperature inside device above max.
limit
The temperature limit inside the device has
exceeded the adjusted max. limit.
Î
Check whether the heating functions properly
and the heating control is switched on.
Î
Select a better location to mount the Media 7
device, if necessary.
207
Large differential pressure drop
The bypass valve has been opened. A
diaphragm rupture in the dp cell exists. The dp
cell leaks.
Î
Check all screw fittings.
Summary of Contents for Media 7 5007-1
Page 6: ...6 EB 9510 EN...
Page 14: ...1 8 EB 9510 EN...
Page 20: ...2 6 EB 9510 EN...
Page 68: ...7 12 EB 9510 EN...
Page 76: ...8 8 EB 9510 EN...
Page 90: ...13 2 EB 9510 EN...
Page 92: ...14 2 EB 9510 EN...
Page 97: ...EB 9510 EN 15 5...
Page 98: ...15 6 EB 9510 EN...
Page 99: ...EB 9510 EN 15 7...
Page 100: ...15 8 EB 9510 EN...
Page 101: ...EB 9510 EN 15 9...
Page 102: ...15 10 EB 9510 EN...
Page 123: ......