EB 3969 EN
Mounting and start-up
5.3.4
Compressed air quality
Risk of malfunction due to failure to comply
with required air quality.
Only use supply air that is dry and free of oil
and dust.
Read the maintenance instructions for up-
stream pressure reducing stations.
Blow through all air pipes and hoses thor-
oughly before connecting them.
With internal pilot supply over port
1
:
Instrument air (free from corrosive sub-
stances), 1.4 to 10 bar operating pres
-
sure
With external pilot supply over port
9
Instrument air (free from corrosive sub-
stances) or non-corrosive gases with 0 to
10 bar operating pressure
Compressed air quality according to ISO 8573-1
Particle size and
quantity
Oil content
Pressure dew point
Class 4
Class 3
Class 3
≤5 µm and
1000/m³
≤1 mg/m³
–20 °C/10 K
below the lowest
ambient
temperature to be
expected
5.3.5
Pilot supply
K
VS
0.3
In the delivered state, the pilot supply is fed
internally over port
1
, if not configured oth
-
erwise.
Fig. 4:
Internal pilot supply
On mounting the solenoid valve to rotary or
linear actuators fitted with positioners,
change the pilot supply to an external pilot
supply over port
9
.
NOTICE
!