Range:
Default (coldstart) value:
0.0 % to 120 %
2.0 %
Limit switch
Software GW2
Limit value alarm referring to travel/angle range, determined by the software from the
signal of the travel (displacement) pick-up. (Switching hysteresis 1%).
Range:
Default (coldstart) value:
0.0 % to 120 %
98 %
Limit switch
Software GW1 set when
Defines the contact circuit state as
≤
1 or
≥
3 mA
States:
Default (coldstart) value:
≥
3 mA values under range for travel/angle, values over range for travel/angle
values under range
Limit switch
Software GW2 set when
Defines the contact circuit state as
≤
1 or
≥
3 mA
States:
Default (coldstart) value:
≥
3 mA values under range for travel/angle, values over range for travel/angle
values over range
Limit value for total valve
travel
An alarm message is issued as soon as the limit for the total valve travel is exceeded.
Range:
Default (coldstart) value:
0 to 16 500 000
1 000 000
Loop/tag number
Loop/tag number - text that is associated with the field device installation. This text can be
used by the user in any way. Each field device is recommended to be assigned a unique
loop/tag number.
Length: 32 characters
For non-IBIS devices
→
message
Manufacturer
Manufacturers id code - Clearly identifies the manufacturer of the field device.
Message
Unassigned text stored in the field device.
Length: 32 characters.
For IBIS devices
→
loop/tag number.
Minimum control pulses
Shortest pulse supplied to the supply air or exhaust air valve. The pulses for the travel
ranges 0 to 20 %, 20 to 80 % and 80 to 100 % are determined separately!
States:
None..................................no pulses determined yet
Exhaust air .........................pulse for exhaust air determined
Supply air ...........................pulse for supply air determined
Valid...................................pulse for exhaust and supply air determined
Minimum transit time
(filling/venting)
The minimum transit time, in seconds, for filling or venting air from the actuator during
initialization is measured separately for supply and vented air. The transit time is defined as
the time required by the system comprising positioner, actuator, and valve to pass through
the rated travel /nominal angle.
46
EB 8380-1 EN
List of parameters
All manuals and user guides at all-guides.com
all-guides.com
Summary of Contents for 3780 series
Page 63: ...EB 8380 1 EN 63 All manuals and user guides at all guides com ...
Page 64: ...64 EB 8380 1 EN All manuals and user guides at all guides com ...
Page 65: ...EB 8380 1 EN 65 All manuals and user guides at all guides com ...
Page 66: ...66 EB 8380 1 EN All manuals and user guides at all guides com a l l g u i d e s c o m ...
Page 67: ...EB 8380 1 EN 67 All manuals and user guides at all guides com ...
Page 68: ...68 EB 8380 1 EN All manuals and user guides at all guides com ...
Page 69: ...EB 8380 1 EN 69 All manuals and user guides at all guides com ...
Page 70: ...70 EB 8380 1 EN All manuals and user guides at all guides com ...
Page 71: ...EB 8380 1 EN 71 All manuals and user guides at all guides com a l l g u i d e s c o m ...
Page 72: ...72 EB 8380 1 EN All manuals and user guides at all guides com ...
Page 73: ...EB 8380 1 EN 73 All manuals and user guides at all guides com ...
Page 74: ...74 EB 8380 1 EN All manuals and user guides at all guides com ...
Page 75: ...EB 8380 1 EN 75 All manuals and user guides at all guides com ...
Page 76: ... 2017 07 All manuals and user guides at all guides com a l l g u i d e s c o m ...