EB 8355-2 EN
39
Operation
100%
0%
4
20 mA
12
4
20 mA
100%
0%
< >
< <
< >
< <
Reference variable
Input signal
Dead band
Open
Open
Travel
Travel
Closed
Closed
Valve 2
Valve 1
Fig. 13:
Normal or split-range operation
5.1.1 Adjusting the proportional
band Xp and air delivery
Q
1.
Close the volume restriction (11) as far
as the required positioning speed
permits.
Check the positioning speed by pushing
the diaphragm lever (3) as far it will go.
2.
Adjust the reference variable at the input
to approx. 50 % of its range.
3.
Turn the zero adjuster (6.2) until the
valve has reached approx. mid-travel.
4.
Use the adjuster (8) to set the proportion-
al band X
p
to a value half way (half
turn).
5.
Check the valve's tendency to hunt and
the positioning speed by briefly tapping
the diaphragm lever (3).
The X
p
value is to be adjusted to be as
small as possible, without considerable
overshooting occurring.
NOTICE
Always adjust the X
p
restriction be-
fore setting the starting point.
Changing it later will cause the zero
point to be shifted.
Summary of Contents for 3767
Page 13: ...EB 8355 2 EN 13 Design and principle of operation...
Page 20: ...20 EB 8355 2 EN Mounting on control valves...
Page 51: ......
Page 52: ...52 EB 8355 2 EN Ptb16 3767 doc Ptb16 3767 doc...
Page 53: ...EB 8355 2 EN 53 Ptb16 3767 doc Ptb16 3767 doc...
Page 54: ...54 EB 8355 2 EN Ptb16 3767 doc Ptb16 3767 doc...
Page 55: ...EB 8355 2 EN 55...
Page 56: ...56 EB 8355 2 EN...
Page 57: ...EB 8355 2 EN 57...
Page 58: ...58 EB 8355 2 EN...
Page 59: ...EB 8355 2 EN 59...
Page 60: ...60 EB 8355 2 EN...
Page 61: ...EB 8355 2 EN 61...
Page 62: ...62 EB 8355 2 EN...
Page 63: ...EB 8355 2 EN 63...
Page 64: ...64 EB 8355 2 EN...
Page 65: ...EB 8355 2 EN 65...
Page 66: ...66 EB 8355 2 EN...
Page 67: ...EB 8355 2 EN 67...