PST_TEST_STATUS_1 (219) to PST_TEST_STATUS_3 (221)
Storage class: – · Read capability (r)
Status of partial stroke tests (PST)
• PST_TEST_STAT1...3_TEST_START (test start)
• PST_TEST_STAT1...3_no_test_avail (no test available)
• PST_TEST_STAT1...3_X_CANCEL (x cancellation)
• PST_TEST_STAT1...3_Y_CANCEL (y cancellation)
• PST_TEST_STAT1...3_TOL_BAND_EXCEED (tolerance band exceeded)
• PST_TEST_STAT1...3_MAX_TIME_EXCEED (max. time exceeded)
• PST_TEST_STAT1...3_TEST_MAN_CANCEL (test manually cancelled)
• PST_TEST_STAT1...3_OUT_OF_MEMORY (measured data storage out of memory)
• PST_TEST_STAT1...3_ABO_INT_SOL_VAL (aborted by internal solenoid valve/forced venting)
• PST_TEST_STAT1...3_PRESSURE_FRIC (supply pressure/friction)
• PST_TEST_STAT1...3_W_STEP_TOO_HIGH (difference w - step start too high)
• PST_TEST_STAT1...3_ABORT_REF_CHANG (test aborted - reference variable was changed)
• PST_TEST_STAT1...3_MAX_BREAKTIME_EX (max. breakaway time exceeded)
• PST_TEST_STAT1...3_TIME_EXCEEDED (allowed time to reach PST target exceeded)
RESET_DIAG_FKT (206)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Reset functions
• 0
No function
• 1
Reset diagnosis
• 17
Reset 'Logger'
• 21
Reset 'Travel histogram x'
• 23
Reset 'Setpoint deviation histogram e'
• 22
Reset 'Cycle counter histogram'
• 24
Reset 'Drive signal diagram steady-state'
• 25
Reset 'Drive signal diagram steady-state - short-term monitoring
• 26
Reset 'Drive signal diagram hysteresis'
• 27
Reset 'Lower end position'
• 28
Reset 'Lower end position - reference values'
KH 8384-4 EN
87
AO Transducer Block, Slot 1
· Manufacturer-specific parameters