EB 8394 EN
53
Code list
P15
Start initialization
Press
button to cancel the initialization process. As a result, the
valve moves to the fail-safe position. After a power supply failure
during initialization, the positioner starts with the values of the last
initialization (if available).
P16
Start zero calibration
The zero calibration process can be interrupted by touching
.
The control valve returns to closed-loop operation.
Note:
A zero calibration cannot be started when
E1
error code ex
-
ists.
After a power supply failure during zero calibration, the positioner
starts with the settings from the last zero calibration.
P17
Manual mode
Press
or
to enter the set point.
P18
Reset
Parameters are reset to their default setting.
The positioner can only return to closed-loop operation after it has
been re-initialized.
P19
Enable configuration
[LOCK]/OPEN
Enable configuration to change parameter settings.
This function is automatically canceled when none of the keys are
touched within three minutes.
P20
Firmware version
Installed firmware version is displayed. Touch
to display the last
four digits of the serial number.