Samson 3710 series Mounting And Operating Instructions Download Page 8

 8  

EB 8392 EN

Attachment to positioners and limit switches

Attachment to positioners 

and limit switches

The description in section 4.1 and 4.2 ap

-

plies to the following devices:

 

Type 3730 Positioner

 

Type 3731 Positioner

 

Type 3766 Positioner

 

Type 3767 Positioner

 

Type 3768 Limit Switch

 

Î

Check device index before attachment.

Note:

See the last two figures of the config

-

uration ID written on the nameplate 
for the device index.

4.1 

Attachment to positioners 

and limit switches (device 

index .05 and higher)

1.  Fasten the reversing amplifier directly to 

the positioner/limit switch using two M5 
screws.

 

Î

On mounting the device, make sure that 
the two O-rings (1.2 in Fig. 2 left) are in

-

serted properly into their groove.

Tip:

If you lose any O-rings for the revers-

ing amplifier, you can order more 
(order number 8421-9064).

4.2 

Attachment to positioners 

and limit switches (below 

device index .05)

Required accessories:

Connecting plate (1400-9621) (2 in Fig. 2)
1.  Screw the special nuts (1) included in the 

accessories for the connecting plate (2) 
into the holes of the positioner.

2.  Insert the O-rings (1.2) into the grooves 

of the connecting plate (2). Slide the hol

-

low bolts (1.3) into the threaded ports 
and fasten tight.

3.  Fit O-rings (1.2) on the reversing amplifi

-

er. Place it on the connecting plate (2) 
and fasten tight.

4.3 

Attachment to Type 3725 

Positioner

Required accessories:

Connecting plate (1402-0512) (1 in Fig. 3)
1.  Fasten the connecting plate (1) between 

the positioner and the reversing amplifier 
using two M5 x 50 screws (2).

Note:

The screws supplied with the connect-
ing plate have a TORX PLUS

®

 profile 

and must be tightened using a suit-
able tool.

Summary of Contents for 3710 series

Page 1: ...Mounting and Operating Instructions EB 8392 EN Edition December 2012 Type 3710 Reversing Amplifier in standard version with pressure gauges for Y1 and Y2 Series 3710 Type 3710 Reversing Amplifier...

Page 2: ...safely The instructions are binding for handling SAMSON devices For the safe and proper use of these instructions read them carefully and keep them for later reference If you have any questions about...

Page 3: ...d limit switches device index 05 and higher 8 4 2 Attachment to positioners and limit switches below device index 05 8 4 3 Attachment to Type 3725 Positioner 8 4 4 Note on attachment to rotary actuato...

Page 4: ...experienced personnel familiar with the product According to these mounting and operating instruc tions trained personnel refers to individuals who are able to judge the work they are as signed to an...

Page 5: ...3 Connecting thread ISO 228 1 G 1 18 NPT 2 Ambient temperature range 25 to 80 C 0 50 to 80 C 1 3 60 to 80 C 2 3 Degree of protection IP 65 filter check valve made of polyamide 2 IP 65 filter check val...

Page 6: ...power The following rule applies Y1 Y2 Z Example Y1 of the positioner 1 bar Supply pressure Z 6 bar Resulting Y2 5 bar Z Y2 Y1 Z Y1 Output 38 Supply 9 Positioner Pressure is added to Y1 to create 6 ba...

Page 7: ...and Y2 6 bar Connections 18 NPT ISO 228 1 G Degree of protection IP 65 Compliance Permissible ambient temperature 25 to 80 C 13 to 176 F Low temperature version 50 to 80 C 58 to 176 F 60 to 80 C 67 t...

Page 8: ...p If you lose any O rings for the revers ing amplifier you can order more order number 8421 9064 4 2 Attachment to positioners and limit switches below device index 05 Required accessories Connecting...

Page 9: ...2 Connecting plate Attachment to Types 3730 3731 3766 and 3767 as well as Type 3768 Limit Switch below device index 05 Fig 2 Attachment to Types 3730 3731 3767 and 3766 Positioners as well as Type 376...

Page 10: ...w plug 1 2 Screw the screw plug 1 into the vent opening of the intermediate piece 5 3 Thread the threaded bushing 2 and re taining washer 4 into the free cable gland of the positioner 4 Screw vent plu...

Page 11: ...lifier 2 Insert gasket 3 into the recess of the supply pressure regulator and slide the special hollow bolts 2 into the holes for Output and Supply 3 Position reversing amplifier and fasten using the...

Page 12: ...eumatic connections The air connections are designed either with 18 NPT or G threads Customary fit tings for metal or copper tubing or plastic hoses can be used Signal pressure connections See dimensi...

Page 13: ...the corre sponding connections 4 Tighten the lock nuts of the pressure gauges leaving a 2 to 3 mm gap be tween the lock nut and pressure gauge s square end Always use screw plugs G 1 8 to seal any un...

Page 14: ...luding pressure compensation element 1402 1337 Pressure gauge 0 to 6 bar psi kPa stainless steel nickel plated brass connection including pressure compensation element 1402 1338 Seal with spacer 1099...

Page 15: ...15 80 90 164 52 Output Y2 Output Y1 Supply 9 Output Y1 Output Y2 56 86 130 80 166 30 86 101 Mounted using a connecting plate order no 1400 9621 onto Type 3766 3767 or Type 3780 Positioners below devi...

Page 16: ...SAMSON AG MESS UND REGELTECHNIK Weism llerstra e 3 60314 Frankfurt am Main Germany Phone 49 69 4009 0 Fax 49 69 4009 1507 samson samson de www samson de EB 8392 EN 2017 12 21 English...

Reviews: