![Samson 3710 series Mounting And Operating Instructions Download Page 10](http://html1.mh-extra.com/html/samson/3710-series/3710-series_mounting-and-operating-instructions_3753007010.webp)
10
EB 8392 EN
Attachment to positioners and limit switches
4.4
Note on attachment to
rotary actuators according
to VDI/VDE 3845
The description applies to the following de
-
vices:
−
Type 3730 Positioner (angle of rotation
>90°)
−
Type 3766 Positioner
−
Type 3767 Positioner
−
Type 3768 Limit Switch
Î
For the attachment of the reversing am
-
plifier to the above listed devices with
mounting kit 1400-8815, remove the
vent plug (6) from the intermediate piece
(5) and insert into the positioner (see
Fig. 4):
1. Place the O-ring (3) onto the screw plug
(1).
2. Screw the screw plug (1) into the vent
opening of the intermediate piece (5).
3. Thread the threaded bushing (2) and re
-
taining washer (4) into the free cable
gland of the positioner.
4. Screw vent plug (6) into the threaded
bushing (2).
5. Fasten the reversing amplifier directly to
the positioner/limit switch using two M5
screws.
Note:
The vent plug included in the mount-
ing kit (1400-8815) has IP 54 de
-
gree of protection. For a higher de-
gree of protection, select a suitable
vent plug from the accessories listed
in section 7.
3 1
5
6
2 4
1
Screw plug
2
Threaded bushing
3
O-ring
4
Retaining washer
5
Intermediate piece
6
Vent plug
Fig. 4:
Relocating the vent plug on attachment to rotary actuators according to VDI/VDE 3845