9.3
Wiring for Type 5724/5725
(refer to EB 5724 EN)
1)
Water flowmeter
2)
Flow switch
3)
Pump control output or fault alarm output
4)
Electromagnet, Type 5725
Domestic hot water heating in instantaneous heating system
Appendix
22
EB 5766 EN
1)
L
L1
N
5V IN
S1
S2
230V, 50Hz
3)
4)
Pt 1000
S1
Operation with Pt 1000 sensor und water flowmeter
= Default setting (WE)
Functions
WE
Configuration
Hot water tapping recognition
1
F01 - 1
Water flowmeter
1
F02 - 1
Current input
0
F05 - 0
Pt 1000
L
L1
N
5V IN
S1
S2
230V, 50Hz
3)
4)
S1
Operation with Pt 1000 sensor
Functions
WE
Configuration
Hot water tapping recognition
1
F01 - 0
Current input
0
F05 - 0
Pt 1000
BE1
L
L1
N
5V IN
S1
S2
230V, 50Hz
3)
4)
S1
Operation with Pt 1000 sensor and binary contact for
switching between set points
Functions
WE
Configuration
Hot water tapping recognition
1
F01 - 0
Current input
0
F05 - 0
Binary input function
0
F08 - 1