9
Appendix
9.1
Wiring for Type 5757-7
(refer to EB 5757-7 EN)
Note!
The pump output L´ is non-floating (230 V~).
Note:
Terminals at point of installation, not included in scope of delivery
blk black · bl blue · br brown · gr green · or orange · rd red · ye yellow
Diagram abbreviations:
VS Flow sensor · RüS Return flow sensor · AS Outdoor sensor
18
EB 5766 EN
Appendix
or
ye
rd
br
blk
gr
br
bl
blk
3
4
6
5
2
1
L
L´
N
230 V, 50 Hz
VS
Pt 1000
Pt 1000
Pt 1000
AS
RüS
Application with flow, return flow, and outdoor
sensors as well as binary input to switch between
operating modes = Default setting (WE)
Functions
WE
Configuration
Control w. reference variable 1
F01 - 1
Outdoor sensor
0
F02 - 0
Potentiometer/binary input
0
F05 - 0
BA as pump control output
0
F09 - 0
Return flow sensor
1
F11 - 1
or
ye
rd
br
blk
gr
br
bl
blk
3
4
6
5
2
1
L
L´
N
230 V, 50 Hz
VS
Pt 1000
Pt 1000
AS
Application with flow sensor and outdoor sensor
Functions
WE
Configuration
Control w. reference variable
1
F01 - 1
Outdoor sensor
0
F02 - 0
BA as pump control output
0
F09 - 0