TROUBLESHOOTING
The symptoms of abnormal operation and the possible cause(s) and remedies are
given in the succeeding paragraphs
There is no output. The AC power on / off switch (9) does not illuminate when
switched on. The charging indicator LED (4) is off (On the Remote Panel (15),
the Green LED under “Power” is off).
a) There is no AC input voltage in the outlet: Check that AC power is available in
the AC outlet receptacle and that it is switched on.
b) The AC input side fuse is blown due to:
• High input voltage - Check that the input voltage is 230 VAC nominal (normal
range is 207 to 253 VAC).
• High voltage transients / surges in the AC input line – Ensure that the AC input
voltage is clean and does not have high voltage transients / surges. Input voltage
surges / transients > 340 VAC (for 230 VAC input) will blow the AC side fuse.
Use a suitable AC line conditioner / surgesuppressor, if necessary.
• The unit has become defective – If fuse is not blowing due to the above two causes,
the unit has become defective.
There is no output voltage and the Charging Indicator LED (4) is red (On the Remote
Panel (15), the Red LED under “I Phase” is lighted, the Green LED under “Power”
is lighted).
a) The DC side output fuse is blown. The DC side fuse will blow if the battery is connected
in wrong polarity. Ensure that the Positive battery post is connected to the Positive
connector of the charger (either Bank 1 or Bank 2) and the Negative battery
post is connected to the Negative connector (common) of the charger. Replace the fuse
with the fuse with the properrating.
b) The battery / DC load is shorted. Check and remove the short circuit. The charger will
latch in the off condition if it was shut down due to short circuit and will
NOT re-set
automatically
. To re-set, switch off the AC power input on / off switch (9) and switch
on again.
c) Shut down due to high temperature. Check that the cooling fan is working, the air vents
are not clogged and the ambient temperature is not very high. The charger will be latched
in this shut down condition and will
NOT reset automatically
even after the unit has
cooled down. To reset, the AC input power on / off (9) switch has to be switched off and
on again.
Page 27