DIP Switch Setting for SEC-2425E, SEC-2440E
S1
S2
Float
Boost
Battery Type
Charging Stages
/ Application
Stand-alone charging
OFF * ON *
27.6 V *
29.6 V * Fleece / AGM * 3 Stages (Stages 1, 2, 3)
ON
OFF
27.6 V
28.8 V
Wet / Gel
3 Stages (Stages 1, 2, 3)
Charging loaded battery
or
Charging two banks and the batteries in the two banks are in dissimilar discharged condition
OFF
OFF
27.6 V
27.6 V
Loaded Battery 2 Stages (Stages 1, 3)
(can be Fleece/
AGM / Wet / Gel)
*Factory preset in this position
CAUTION!
Please ensure that position S1- ON and
S2 – ON is never selected
SELECTING THE TIME FOR STAGE 2 - CONSTANT OVERCHARGE VOLTAGE,
TIMED ABSORPTION / BOOST CHARGE MODE (“Uo” PHASE)
Stage 2 - Constant Overcharge Voltage, Timed Absorption / Boost Charge Mode (“Uo”
Phase) is controlled by an internal timer circuit. Time of 4 hours or 8 hours can be selected
with the help of a pair of switches S3 & S4 of the set of 4 DIP Switches (5). Select the times
as follows:
Time
DIP Switch S3
DIP Switch ST
Type of Battery
4 hours*
Off*
On*
Fleece / wet gel
8 hours
On
Off Gel
Gel & AGM
Disable
Off
Off
*Factory preset in this position
CAUTION!
Please ensure that position S3- ON and
S4 – ON is never selected
Page 20