12 | SAMLEX AMERICA INC.
SAMLEX AMERICA INC. | 13
SECTION 5 |
Installation & Charger Operation
be disabled to prevent overcharging of the battery (see details under
!
CAUTION!
at Section 4.1.3). A DIP Switch (4 in Figs 2.1 to 2.3) is provided on top of the output
terminals for selecting the battery type and for disabling the Boost Stage when charging
loaded batteries. The following selections can be made with the help of the DIP Switch.
!
CAUTION!
Do not change the DIP Switch setting when the charger is operating. Always
change the DIP Switch setting when the charger is off , i.e. after disconnecting
the charger from the AC input power.
NOTE: The voltages are for a temperature of 80°F.
!
CAUTION!
Please ensure that the position No. 4 of the DIP switch (S1-ON & S2-ON) is
NEVER selected.
TABLE 5.1 DIP SWITCH SETTINGS: SEC-1215UL/SEC-1230UL
S1
S2
Float
Boost
Battery
Type
Charging
Stages
OFF *
ON *
13.5 V *
14.4 V *
Flooded /
AGM *
3 Stages
(Stages 1, 2, 3)
ON
OFF
13.5 V
14.0 V
Gel Cell
3 Stages
(Stages 1, 2, 3)
OFF
OFF
13.5 V
Disabled
Battery with
Load
2 Stages
(Stages 1, 3)
ON
ON
Caution! Do NOT use this setting
* Factory pre-set in this position
TABLE 5.2 DIP SWITCH SETTINGS - SEC-2415UL
S1
S2
Float
Boost
Battery
Type
Charging
Stages
OFF *
ON *
27 V *
28.8 V *
Flooded /
AGM *
3 Stages
(Stages 1, 2, 3)
ON
OFF
27 V
28.0 V
Gel Cell
3 Stages
(Stages 1, 2, 3)
OFF
OFF
27 V
Disabled
Battery with
load
2 Stages
(Stages 1, 3)
ON
ON
Caution! Do NOT use this setting
* Factory pre-set in this position