background image

 

      Powersine Combi

 

21 

 

 

Connected AC output load  
causes a too large inrush 
current. 

Try to power-up connected 
equipment successively, and 
not simultaneously. 
Otherwise stop using the 
connected load, it's not 
suitable to power it with this 
inverter. 

Mode indicator LEDs 
‘inverter on’ and ‘charger on’ 
are blinking red three times 
per second. 

The Powersine Combi has 
shut down due to a too high 
temperature. 

Reduce the AC output load in 
inverter mode. 
Try to reduce the ambient 
temperature around the 
Powersine Combi. Make sure 
that there is a clearance of at 
least 10cm around the unit. 
Do not obstruct the airflow, 
place no items on or over the 
unit. 
Keep the Powersine Combi 
away from direct sunlight or 
heat producing equipment. 

Mode indicator LED ‘AC in’ 
blinks red once per second. 

AC input signal is present but 
not within required voltage 
and frequency borders. 

Make sure that the AC input 
voltage falls within 185V- 
270V and 45Hz-65Hz. 

All mode indicator LEDs 
‘inverter on’, ‘charger on’ 
and ‘AC in’ are blinking red 
twice per second (manual 
restart needed) 

Maximum AC transfer switch 
current has been exceeded. 

Reduce the AC output load 

Mode indicator LED ‘inverter 
on’ or ‘charger on’ or ‘AC in’ 
is red continuously. 

Either the inverter mode, or 
the charger mode or the AC 
transfer switch has been 
disabled using Dashboard. 

Enable again using 
Dashboard if required. 

 

If only ‘inverter on’ is red 
continuously. 

Powersine Combi main 
switch is put into ‘charger 
only’ mode, meaning that 
the inverter is disabled. 

Output power bar is red 
(inverter mode). 

The inverter is overloaded 
and will shut down after a 
certain time (depending on 
the amount of overload)  

Reduce the AC output load 

All mode indicator LEDs 
‘inverter on’, ‘charger on’ 
and ‘AC in’ are blinking red 
four times. 
 

Device or connection fault. 

Powersine Combi is 
defective, return for service. 
External AC source is 
connected to the AC output 
instead of the AC input. 

Summary of Contents for PSC1600-12-60

Page 1: ...800 24 35 PSC2500 24 50 PSC3500 24 70 Model No SINEWAVE INVERTER CHARGER Manual Gebruiksaanwijzing Benutzerhandbuch Manuel Utilisateur Manual Para Utilizador Please read this manual before operating y...

Page 2: ...SSES DAMAGES COSTS OR EXPENSES WHETHER SPECIAL DIRECT INDIRECT CONSEQUENTIAL OR INCIDENTAL WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE...

Page 3: ...12 4 1 Operating the Powersine Combi 12 4 2 Powersine Combi LED indicators and error modes 12 4 2 1 Error indications 14 4 3 Programmable Alarm relay 14 4 4 Trigger input 15 4 5 Load requirements in i...

Page 4: ...of this owner s manual is to provide explanations and procedures for operating and configuring the Powersine Combi For installing the Powersine Combi a separate installation guide is included The inst...

Page 5: ...ting the inverter The connected loads are now supplied again by the grid generator without any interruption Additionally the Powersine Combi offers features like AC Input Power Boost which temporarily...

Page 6: ...gured in SAMLEX Dashboard When DIP switch 1 is set to OFF Local again DIP switch 2 up to 7 or 9 are overriding the corresponding parameter settings previously made in SAMLEX Dashboard The parameters t...

Page 7: ...Parameter AC input voltage range transfer switch Value 180V 270V Description Input voltage range which is accepted by the Powersine Combi for feeding through to the connected load Two AC undervoltage...

Page 8: ...nd Dashboard Parameter AC input fail sensitivity Value Normal Description This parameter can be set to Very Low Low Normal High and Very High The value of this Parameter decides how fast the Powersine...

Page 9: ...w During step 3 of the installation guide you can alter the factory settings of the DIP switches to change the functionality of the Powersine Combi on a few points For additional information about the...

Page 10: ...age 13 3V 26 6V programmable Factory setting OFF AC Input Power Boost ON AC Input Power Boost on OFF AC Input Power Boost o Factory setting ON Models PSC1600 1800 Bypass remote switch Bypasses the rem...

Page 11: ...e serious damage to your batteries and or connected battery loads Always consult your battery s documentation for the correct charge voltage settings 2 When charging and discharging lithium batteries...

Page 12: ...lease the AC transfer switch and activate the inverter again All this happens so fast that the connected load will not be disturbed When switched to Off the Powersine Combi is completely shut down and...

Page 13: ...as well as the status of each different mode see explanation below charger on LED Off not charging On green charging On blinking red error see chapter 4 2 1 On red charger disabled inverter on LED Off...

Page 14: ...s in a row Device error an error has occurred inside the Powersine Combi Please return for service Five flashes in a row Charge program error only for charger on indicator LED Charge program selection...

Page 15: ...ce the Powersine Combi to switch to inverter mode All this can be configured in SAMLEX Dashboard The PSC1600 1800 models are equipped with one trigger input while the PSC2000 3500 models are equipped...

Page 16: ...80 full indicator will be lit This stage will return the final 20 of charge to the battery The output voltage is kept at a constant level and the charge current decreases as a function of the battery...

Page 17: ...ements must be read carefully When the battery temperature sensor is installed the charger automatically compensates the charge voltages against battery temperature except when set to Lithium This mea...

Page 18: ...button on the bottom side of the unit see images below for 3 seconds until all charge status indicators start flashing Models PSC1600 1800 Models PSC2000 3500 The Powersine Combi will allow a maximum...

Page 19: ...r mode is not working AC transfer switch does not activate either The AC input voltage or frequency are out of range or too unstable Make sure that the AC input voltage is between 185V 270V and the fr...

Page 20: ...eck the DC system for an external source that pushes the battery voltage too high Too high ripple voltage on DC input manual restart needed Check battery wire connections Decrease battery cable length...

Page 21: ...cy borders Make sure that the AC input voltage falls within 185V 270V and 45Hz 65Hz All mode indicator LEDs inverter on charger on and AC in are blinking red twice per second manual restart needed Max...

Page 22: ...rogram contains go to error condition for example when a charge stage takes too much time If none of the above remedies will help solving the problem you encounter it s best to contact your local SAML...

Page 23: ...bled Yes Protections high low battery voltage high temperature overload short circuit high ripple voltage and low AC input voltage DC connections Two wires length 1 5 meters 35mm2 AC connections Screw...

Page 24: ...led Yes Protections high low battery voltage high temperature overload short circuit high ripple voltage and low AC input voltage DC connections M10 bolt terminals AC connections Screw terminals Enclo...

Page 25: ...bled Yes Protections high low battery voltage high temperature overload short circuit high ripple voltage and low AC input voltage DC connections M10 bolt terminals AC connections Screw terminals Encl...

Page 26: ...of the product and product malfunctioning Since SAMLEX cannot control the use and installation according to local regulations of their products the customer is always responsible for the actual use of...

Page 27: ...2500 24 50 PSC3000 12 120 PSC3500 24 70 Conforms to the requirements of the following Directives of the European Union EMC Directive 2004 108 EC The above product is in conformity with the following h...

Page 28: ...www samlex com www samlex solar com...

Reviews: