19 

 

 

Temperature sensor checking 

Temperature  sensors  CT10,  CT6-P  can  be 
checked  by  measuring  their  resistance  in 
given temperature. In case of big differences 
between  measured  resistance  value  and 
values  in  table  below,  the  sensor  should  be 
replaced with a new one. 

CT10 

Weather temp. 

[°C] 

Value  

[Ω] 

32 554 

10 

19 872 

20 

12 488 

25 

10000 

30 

8059 

40 

5330 

50 

3605 

60 

2490 

70 

1753 

80 

1256 

90 

915 

100 

677 

 

CT6-P (weather) 

Weather temp. 

[°C] 

Value  

[Ω] 

-25 

901,9 

-20 

921,6 

-10 

960,9 

1000,0 

25 

1097,3 

50 

1194,0 

100 

1385,0 

125 

1479,4 

150 

1573,1 

 

Connecting a room thermostat 

Room  thermostat  (NO-NC)  connected  to  the 
control affects the heating circuit. 
The thermostat after contact opening reduces 
the preset temperature heating circuit about 
the  service  value  Decrease  of  thermostat  or 
can turn off the pump in the parameter Off by 
thermostat
.  The  values  of  the  parameters 
must be chosen so that when of working the 
room  thermostat  (contact  opening)  the 
temperature in the room dropped. 

 

Connecting a heat source 

COM-NO  terminals  are  used  to  connect  the 
contact heat source (no voltage) that turns on 
and off the heat source. The heat source can 
be  automatic  boiler  gas  or  oil,  which  has  a 
contact ON-OFF. Terminals COM-NO does not 
have  galvanic  isolation  of  230V  ~  and  can 

therefore  only  serve  to  disconnect  circuit 
voltage of 230V ~. Use separate relay in the 
event of having to disconnect circuits at low 
voltage. 

 

Risk  of  electric  shock  caused  by 
current  from  a  heat  source. 
Disconnect  the  controller  and 
heat source electrical supply and 
make sure there is no dangerous 
voltage on terminals.  
Protect yourself against incidental 
generation of supply voltage! 

Connection to  heat source (gas or oil  boiler) 
should  be  done  by  a  qualified  installer, 
according to technical data of this boiler.   
 
 

 

Summary of Contents for WT100

Page 1: ...WEATHER CONTROLLER WT100 FOR CONTROL TEMPERATURE HEATING CIRCUIT OPERATIONS AND INSTALLATION MANUAL VERSION 1 4 SOFTWARE VERSION v01 XX XX 03 2018...

Page 2: ...2...

Page 3: ...THE CONTROLLER 15 ENVIRONMENTAL CONDITIONS 15 INSTALLATION REQUIREMENTS 15 EXTERNAL CIRCUITS CONNECTION 16 CONNECTING ELECTRICAL SYSTEM 17 FIXING THE EXTERNAL WIRES 17 CONNECTION OF TEMPERATURE SENSO...

Page 4: ...t in case of failure it can be a source of sparks or high temperature which surrounded by ashes or flammable gases can cause fire or explosion Modification of the programmed parameters should be made...

Page 5: ...to observe these instructions Documentation storage Please keep this operation and assembly manual and other valid documentation in a safe place for future reference In case of moving or selling the d...

Page 6: ......

Page 7: ...REGULATOR INSTRUCTION MANUAL WT100...

Page 8: ...ixer actuator position ON open OFF closed STOP off 5 working heat source boiler switched on 6 information from the room thermostat No icon the thermostat is off Heating room temperature below the pres...

Page 9: ...mperature In periods of night heating circuit is completely turns off The frost protection function remains active as long as it is enabled in the Service menu Schedule The time intervals allow the in...

Page 10: ...turned on automatically using the Auto parameter including temperature settings for the Summer mode ON temp and Summer mode OFF temp General settings In general settings can change the settings date t...

Page 11: ...INSTALLATION MANUAL AND SERVICE SETTINGS WT100...

Page 12: ...vice settings Room thermostat Start pump temp 55 C 20 C Service settings Heating circuit Return sensor ON Service settings Protection In order to improve water flow in gravitational circuit of the boi...

Page 13: ...source with S ON OFF contact gas or oil boiler 2 relief valve different pressure 3 hydraulic coupling RECOMMENDED SETTINGS Parameter Setting MENU Kind of the system Radiators system Service settings...

Page 14: ...y valve actuator 1 heat source with S ON OFF contact gas or oil boiler 2 relief valve different pressure 3 hydraulic coupling RECOMMENDED SETTINGS Parameter Setting MENU Kind of the system Underfloor...

Page 15: ...unit casing disconnect power supply The unit installation must be done at disconnected voltage Controller must be installed by qualified and authorized technician in accordance with EN 60335 1 standa...

Page 16: ...50Hz P CH pump SM mixer actuator S contact to operate the heating source type ON OFF FU time delay subminiature fuse The terminals for hazardous voltage COM NO ZLo ZN ZLc PN PL L N The terminals safe...

Page 17: ...supply 230V to terminals for sensors will damage the regulator and creates risk of an electric shock Tips of the connected wires especially power leads must be secured against splitting by means of in...

Page 18: ...e may be shown Minimum length between those wires should be 100mm It is not acceptable to allow for contact betweens wires of the sensors and hot parts of the boiler and heating installation Wires of...

Page 19: ...pump in the parameter Off by thermostat The values of the parameters must be chosen so that when of working the room thermostat contact opening the temperature in the room dropped Connecting a heat so...

Page 20: ...ease of work mode 0 15K 10 Decrease of thermostat 0 30K 10 OFF by thermostat Yes No Yes Start pump temp 10 70 C 35 Min temperature 5 40 C 20 Max temperature 20 50 C 40 Valve full opening time 60 200s...

Page 21: ...ning the thermostat Preset temperature of water inside the heating circuit is not changed if Decrease of thermostat 0 Parameter disappears when Room thermostat OFF OFF by thermostat Stopping the flow...

Page 22: ...an accuracy of 1 Frost protection ON or OFF frost protection function Frost protection delay Time delay for enable frost protection function Description later in this manual Frost protection temp The...

Page 23: ...move In this setup it is possible to connect a room thermostat which will equalize the inaccuracy of selecting heating curve if the selected heating curve value is too high In such case it is necessa...

Page 24: ...vices settings Protection Frost protection Description of frost protection against the external temperature sensor readings When the external temperature drops below 3 C an Frost protection delay e g...

Page 25: ...5 C Technical data Power 230V 50Hz Maximum current consumption with loaded outputs 3 3 A Maximum current consumption without loaded outputs 0 02A Output current Pump Mixer actuator ON Mixer actuator O...

Page 26: ......

Page 27: ......

Page 28: ...SALUS Controls ul Rolna 4 43 262 Kobielice Poland www salus controls pl...

Reviews: