System Overview - Configuration Options

06

VS10W and VS10B Installer Manual

Programmable Room Thermostat (PRT)

When configured for PRT (see page 31)  it mainly works by itself and allows the user to have separate Time and
Temperature control of each zone on the wiring centre. Features like Vacation , Party frost mode have to set on
each individual thermostat. The PRT can be configured for global Heat/Cool system changeover if your system
supports this. This is achieved  from a switched input from the  wiring centre (see note 6 from the wiring center
installation guide). Communication Connection (see page 13) is required to use heat/cool changeover function

Group Control Thermostat

When configured for a group control thermostat (see page 33) this allows central control of up to 7 group
thermostats see below, there can be a maximum of 2 groups per 8 zone wiring centre. Permanent temperature
override, Holiday, Party, Frost modes, can be selected centrally from the Group  Control Thermostat. Holiday will
also be applied to a timer if applicable. Communication connections (see page 13) are required for grouping
the group thermostats. Thermostats can  be also  globally changed from heating to cooling thermostats if you
system supports this by using the switched input connection on the WC (see note 6 from the wiring center
installation guide) along with the communications connections mentioned above

Group Thermostat

When configured for Group thermostat (see page 36) and in group mode the group thermostat will follow the
time schedule and any override modes of the group thermostat. The Group thermostat can have its own
programd temperatures, manual override and also be removed from the group temporarily or permanently.
Communication connections required (see page 13). 

Timer

When configured to timer (see pages 32 & 34) the unit will operate as a timer with no temp control. This can be
used for example hot water control. The timer will also follow Holiday mode from the group control thermostat
if applicable, communication connections required for this group function.

iT600 VS10W - VS10B Installer - User Manual 022.qxd_Layout 1  07.07.2014  0

Summary of Contents for VS10W

Page 1: ...4 in 1 Digital Thermostat Control Models VS10W and VS10B INSTALLER USER MANUAL iT600 VS10W VS10B Installer User Manual 022 qxd_Layout 1 07 07 2014 0...

Page 2: ...duct Compliance System options overview Installation Parameter Settings Error Codes User Guide Installers notes Warranty Box Contents Icons used in this manual Safety Important info Your benefit For l...

Page 3: ...onnected to the wiring centre and using the communication connections More information can be found on pages 9 and 10 Product Compliance This product is CE compliant and meets the following EC Directi...

Page 4: ...in the installernotessection pages72 74 230V AC 04 VS10W andVS10B Installer Manual These instructions are applicable to the SALUS model statedonthefrontcoverofthismanualonly Warning This product must...

Page 5: ...mmable Room Thermostat PRT The unit can be configured to either one of the following 1 UFH Manifold Wiring Centre Radiator Boiler HotWater Group Control Thermostat 2 Group Thermostat 3 Timer 4 SYSTEM...

Page 6: ...ermostat Holidaywill also be applied to a timer if applicable Communication connections see page 13 are required for grouping thegroupthermostats Thermostatscan bealso globallychangedfromheatingtocool...

Page 7: ...s Installing this Optional inexpensive CommunicationCableallowsthethermostatstocommunicate with each other This allows the thermostat to assume convenient remote control of groups of thermostats Bring...

Page 8: ...iants can be configured from VS10 Groups must have a group control thermostat 1 or 2 Groups can be usedperwiringcentre HWTimer can be stand alone or part of a group IfusingHWTimeraspart of a group it...

Page 9: ...6 6 Group Party 6 6 Group Heating Program 6 6 Group Permanent Override 6 6 GroupTemporary Override 6 6 Heat Cool changeover 6 4 Note Thecommunicationconnectionisonlyusedforheat coolchangeoverwhenusing...

Page 10: ...Group Party 6 4 Group Heating Program 6 4 Group Permanent Override 6 4 GroupTemporary Override 6 4 Heat Cool changeover 6 4 Note HW timer will only use HOLIDAY function when the communication connecti...

Page 11: ...ng the cylinder thermostat Unit configured to HotWaterTimer Cylinder thermostat options 1 Connected direct toWC Default 2 Connected direct toVS10 requires additional parameter change See page 40 VS10W...

Page 12: ...ge see page 40 Forconveniencethereisauniquebuiltinoptionallowingthecylinder thermostat to be connected to either the HWTimer orWiring Centre Please refer to note 1 onWiring Centre guide and page 18 fo...

Page 13: ...ermostat GroupThermostat and HWTimer PowerTerminals 230Vac Used for supplying power to the unit and switched output SensorTerminals Can be used for external AIR Floor sensor when configured as thermos...

Page 14: ...Carefully remove the front housing Installation Thermostat Mounting 1 3 2 60mm 14 VS10W andVS10B Installer Manual iT600 VS10W VS10B Installer User Manual 022 qxd_Layout 1 07 07 2014 0...

Page 15: ...e operation and efficient control the unit is best positioned in a draft free area and at 130cm from the floor Do not position the thermostat nearanyheatsource behindcurtains directsunlightoranareaofh...

Page 16: ...emote control of groups of thermostats Bringing central control of features such asTime control Holiday Partyfunctionsaswellasfrostcontrol The individual group members can leave or re enter group cont...

Page 17: ...the unit has to be configured for External Air Sensor or Floor Protection Sensor please see device parameter setting page 40 VS10W andVS10B Installer Manual 17 INSTALLATION SALUS External sensor Sold...

Page 18: ...s 230Vac Optional Communication Connections 12VDC If hot water is part of a group then the communication connection must be connected to group 1 18 VS10W andVS10B Installer Manual iT600 VS10W VS10B In...

Page 19: ...arameters page 40 For additional Wiring Centre information refer to note 1 onWiring Centre guide HWTimerconnectedcylinderthermostat IN OUT Link must be fitted WC connected cylinder thermostat Default...

Page 20: ...d Ensuretheorientationarrow is pointing upwards PowerTerminals SensorTerminals if applicable Communicationconnections optionalbutrecommended You are ready to secure the rear housing to the wall box 20...

Page 21: ...e rear housing Align the front housing at the bottom edge 2 Lightly press until you hear a positive click Ensure the pin connections are aligned VS10W andVS10B Installer Manual 21 INSTALLATION iT600 V...

Page 22: ...re Programmable thermostat Program mode indicator Indicatesprogramisrunning AutoOnorAutoOff Forgroupthermostatthis indicatesthatitisamemberofagroup Party indicator WhenPartymodeisactive Vacation indic...

Page 23: ...show the other information Temporary manual override indicator If the set temperature is changed when in program mode the hand will appear until the next program start time Programs number indicator I...

Page 24: ...am mode indicator Indicates program is running HW Mode indicator Mode for 1 period of HW a day from Program 1 ON to Program 3 OFF HW Mode indicator Indicates continuously On HW Mode indicator Indicate...

Page 25: ...w battery indicator Batteries need to be replaced Setting indicator Indicate the unit is in setting mode when program setting Indicate the manual mode Keylock indicator Shows that keys are inactive VS...

Page 26: ...returntohomedisplaywithoutsaving 3 Shortpresstoreturntothepreviousscreenwhenitisinuser installersettingmode 1 OKkey Shortpresstoconfirmselection 2 Longpresstosaveandexit 3 Longpresstoentertheusersetti...

Page 27: ...Installation First Power Up VS10W andVS10B Installer Manual 27 INSTALLATION iT600 VS10W VS10B Installer User Manual 022 qxd_Layout 1 07 07 2014 0...

Page 28: ...ebelow S03 setting 1 is used for Control Group options 2 3 see pages 33 36 communication connectionmustbeused globalheat coolchangeoverisalsoincludedifapplicabletoyoursystem S03setting0isusedforoption...

Page 29: ...GroupControlThermostatusedtocontrolagroup s ofDigitalStat s configuredasgroupthermostats Option 3 Page 35 Group 1 Group 2 Group 1 Group 2 An additional HotWaterTimer can be used with any of the above...

Page 30: ...dVS10B Installer Manual Press once Press x amount of times Hold for five seconds Flashing xx Short press to save and long press to save and exit Short press to back up iT600 VS10W VS10B Installer User...

Page 31: ...ttings Refer to page 33 Short press on to back up Use to change to 2 PRT with no communication Select S03 setting 0 if communication is required for global heat cool changeover Your system must suppor...

Page 32: ...s to exit to home screen or continue to change device settings Refer to page 40 Hot water with no communication 32 VS10W andVS10B Installer Manual Use to change to 2 Use to change to 2 iT600 VS10W VS1...

Page 33: ...S10W andVS10B Installer Manual 33 Long press to exit to home screen or continue to change device settings Refer to page 40 Communication connection required for this setting SYSTEM OPTION 2 iT600 VS10...

Page 34: ...andVS10B Installer Manual Long press to exit to home screen or continue to change device settings Refer to page 40 Communication connection required for this setting Use to change to 2 iT600 VS10W VS1...

Page 35: ...anual 35 SYSTEM OPTION 3 Group Control Thermostat Long press to exit to home screen or continue to change device settings Refer to page 40 Communication connection required for this setting iT600 VS10...

Page 36: ...ller Manual Group Thermostat Long press to exit to home screen or continue to change device settings Refer to page 40 Communication connection required for this setting Use to change to 1 iT600 VS10W...

Page 37: ...staller Manual 37 SYSTEM OPTION 3 Long press to exit to home screen or continue to change device settings Refer to page 40 Communication connection required for this setting Use to change to 2 iT600 V...

Page 38: ...Parameters If you have made an error or need to change your system parameters please follow steps below This should only be done by your installer Press all three buttons simultaneously iT600 VS10W VS...

Page 39: ...will follow power up sequence on page 27 You are now ready to enter or change your system parameters Refer to page 28 VS10W andVS10B Installer Manual 39 INSTALLATION iT600 VS10W VS10B Installer User M...

Page 40: ...ers follow the steps below Please note your system parameters will be shown first but cannot be edited in this section To change the system parameters please refer to the previous two pages 40 VS10W a...

Page 41: ...at Connected 0 connection D04 Sensor probe 0 D03 must be set to 1 then used as air sensor external sensor be used as or floor sensor Air sensor There will be no internal temp measurement 0 1 D03 must...

Page 42: ...ng Set point 5 40 Deg C Maximum temp that can 5 Deg C Limit be set for Cooling D14 Floor sensor High Output relay will be switched off LimitTemperature 6 45 Deg C when temp is reached for 27 Deg C flo...

Page 43: ...nsoropen 04 Floorsensorshort Floorsensorshort Ifthereismorethan1error thenonErrorpage pressUPtoshowothererrorcodes e g Err0305 3errorsErrorcode05 1stone PressUptoshowErr0308 3errorsErrorcode08 2ndone...

Page 44: ...emporary Frost Protection 5 CAdjustable Power Source 230VAC50Hz Rating 3Amp Communication Bus 12VDC Temperature Scale 5to35 C tolerance0 5 C Heat Cool Globalchangeoverusingcommunicationbusandexternali...

Page 45: ...User Guide Setting time and date VS10W andVS10B Installer Manual 45 USER GUIDE PRT and Group ControlThermostat iT600 VS10W VS10B Installer User Manual 022 qxd_Layout 1 07 07 2014 0...

Page 46: ...to select 12 hour and right to select 24 hour Adjust the time using the up or down arrow key 46 VS10W andVS10B Installer Manual PRT and Group ControlThermostat Hour Minutes iT600 VS10W VS10B Installer...

Page 47: ...d date Adjust the year month day using the up or down arrow key VS10W andVS10B Installer Manual 47 USER GUIDE PRT and Group ControlThermostat Month Year Day iT600 VS10W VS10B Installer User Manual 022...

Page 48: ...the home Typically 19 Deg C LowerTemperature typically used for unoccupied or sleep times Typically 17 Deg C for UFH or 15 Deg C for radiators Frost Temperature typically used for Periods of long abs...

Page 49: ...mperatureTypically 24 C VS10W andVS10B Installer Manual 49 Your thermostat comes preset for the above temperatures These can be adjusted please see page 53 Coolingisonlyavailableifyoursystemsupportsth...

Page 50: ...9 00 17 00 23 00 Monday to Friday 21 19 17 12 00 8 00 9 00 17 00 23 00 Saturday to Sunday PRT and Group ControlThermostat If using grouping the schedule from the group control thermostat will be appl...

Page 51: ...24 12 00 8 00 9 00 17 00 23 00 Saturday to Sunday VS10W andVS10B Installer Manual 51 USER GUIDE PRT and Group ControlThermostat If using grouping the schedule from the group control thermostat will be...

Page 52: ...VS10B Installer Manual Press once Press x amount of times Hold for five seconds Flashing xx Short press to save and long press to save and exit Short press to back up iT600 VS10W VS10B Installer User...

Page 53: ...e will use this as the low setting The temperature set are applicable to the individual thermostat PRT Group ControlThermostat and GroupThermostat Setting the low temperature VS10W andVS10B Installer...

Page 54: ...hosen By setting the low temperature the programs will use this as the low setting 54 VS10W andVS10B Installer Manual The temperature set are applicable to the individual thermostat PRT Group ControlT...

Page 55: ...elect the day of the programs VS10W andVS10B Installer Manual 55 5 2 7 Days Individual If using grouping the schedule from the group control thermostat will be applied to group members USER GUIDE iT60...

Page 56: ...emperature Schedule Adjust the time using the up or down arrow key Use right and left to select the Hi Mid or low temp 56 VS10W andVS10B Installer Manual iT600 VS10W VS10B Installer User Manual 022 qx...

Page 57: ...e temperatures see page 53 on how to change Repeat through to program 4 If you require a 5th or 6th program enter a time and select your temperature To remove a program out set the time to VS10W andVS...

Page 58: ...the up or down arrow key to adjust the temperature to the setting you desire Temporary override allows you to increase the temperature or decrease it to the desired setting until it reverts back on t...

Page 59: ...temporary override press or See below VS10W andVS10B Installer Manual 59 PRT Group ControlThermostat and GroupThermostat Confirm the temporary set temperature USER GUIDE iT600 VS10W VS10B Installer Us...

Page 60: ...oved from the group See page 64 Move from to Use the up or down arrow key to view your set temperature See page 58 To adjust your permanent override temperature follow the steps on page 58 Repeat for...

Page 61: ...se the up arrow to select the hr min Press tick to confirm and it will start to count down Party Mode set in a Control Group Thermostat will also affect group thermostats unless they are removed from...

Page 62: ...to be off for Press tick to confirm and it will start the holiday count down 62 VS10W andVS10B Installer Manual Holiday set in a Control Group Thermostat will also affect group thermostats unless the...

Page 63: ...een set to VS10W andVS10B Installer Manual 63 Frost protection set in a Control Group Thermostat will also affect group thermostats unless they are removed from the group See page 64 Frost protection...

Page 64: ...the group thermostat will follow this mode or will be displayed The group thermostat has now left the group and is in permanent To adjust the set temperature please refer to page 58 The group thermos...

Page 65: ...page 58 The group thermostat has now left the group and is in permanent To adjust the set temperature please refer to page 58 The group thermostat has been returned to it will follow the mode status o...

Page 66: ...Holiday mode from the group control thermostat will be displayed When is selected the hot water timer will follow the program schedule See page 68 Hot water will be on once per day Hot water will be c...

Page 67: ...User Guide HotWater Boost VS10W andVS10B Installer Manual 67 USER GUIDE iT600 VS10W VS10B Installer User Manual 022 qxd_Layout 1 07 07 2014 0...

Page 68: ...F 12 00 6 00 8 00 18 00 22 00 Saturday and Sunday Monday to Friday ON ON OFF OFF OFF Your hot water timer comes preset with the times below These can be adjusted See next page 68 VS10W andVS10B Instal...

Page 69: ...User Guide Setting HotWaterTimes VS10W andVS10B Installer Manual 69 USER GUIDE 5 2 7 Days Individual iT600 VS10W VS10B Installer User Manual 022 qxd_Layout 1 07 07 2014 0...

Page 70: ...User Guide Setting HotWaterTimes 70 VS10W andVS10B Installer Manual Repeat these steps for programs iT600 VS10W VS10B Installer User Manual 022 qxd_Layout 1 07 07 2014 0...

Page 71: ...User Guide Setting HotWaterTimes VS10W andVS10B Installer Manual 71 USER GUIDE Repeat these steps for programs iT600 VS10W VS10B Installer User Manual 022 qxd_Layout 1 07 07 2014 0...

Page 72: ...Installer Notes 72 VS10W andVS10B Installer Manual iT600 VS10W VS10B Installer User Manual 022 qxd_Layout 1 07 07 2014 0...

Page 73: ...Installer Notes VS10W andVS10B Installer Manual 73 iT600 VS10W VS10B Installer User Manual 022 qxd_Layout 1 07 07 2014 0...

Page 74: ...Installer Notes 74 VS10W andVS10B Installer Manual iT600 VS10W VS10B Installer User Manual 022 qxd_Layout 1 07 07 2014 0...

Page 75: ...he date of installation SALUS Controlssoleliabilityforbreachofthiswarrantywillbe atitsoption torepairorreplacethedefectiveproduct CustomerName CustomerAddress PostCode TelNo Email EngineersCompany Tel...

Page 76: ...ech com Issue Date April 2014 For PDF Installation guide please go to www salus controls com Maintaining a policy of continuous product development SALUS Controls plc reserve the right to change speci...

Reviews: