13. Boiler control output
14. CO terminal (input)
15. Dew point sensor input (humidistat)
16. Serial connector for the KL04RF extension
Identification of the wiring centre
Factory reset
17. External antenna connector
INSTALLATION
MOUNTING
12. Pump control output
Pump output - this is a volt free output (COM / NO) that controls the circulation pump
in the heating / cooling system. The output closes (pump starts) always after 3 minutes
after receiving the heating / cooling signal from any of thermostats paired with wiring
centre. The output opens (pump stops) after 3 minutes, when the last thermostat stops
sending heat / cold demand.
Connect the wiring centre to the 230 V AC power supply. The Network Status LED will blink.
Remove the top cover of the wiring centre.
To start identification
To start identification
When wall mounting, unscrew the main part of
the housing (see picture). When mounting on
the DIN rail tilt the hooks on the back of the housing.
To stop identification
To stop identification
Attach the back of the wiring centre to the wall.
Screw the main part of the wiring centre
to the back of the housing.
Remove the appropriate section of insulation
from the wires.
Wiring centre
power supply
110 mm
50 mm
10 mm
10 mm
Additional devices
(e.g. pump, boiler)
Connect the power cord.
Connect the rest of the wires.
Remove the CO10RF coordinator if you use
the UGE600 internet gateway..
Make sure that all the wires are properly connected
then connect the power cord to the 230 V AC power
supply - red LED diode will light up.
After finishing installation mount the top cover
of wiring centre.
To restore the factory settings, press and hold the Pair button for 15 seconds. G1 and G2 diodes will turn red
and go out.
To identify the wiring centre in the ZigBee network, follow the steps below:
In Online mode (using the SALUS Smart Home app):
In Offline mode:
Wiring centre will connect to the network automatically. The Network Status LED will turn solid green.
Opened CO input contacts (Changeover) means that whole system works in the
heating mode. Short circuit at the input CO will automatically switch the whole system
to cooling mode (wiring centre and paired thermostats).
Shorting the contacts at the dew point sensor input (too high humidity) causes
switching off all zones in the wiring centre and Pump control outputs.
It is used for communication between the KL08RF wiring centre and the KL04RF extension module. KL04RF
extension module increases functionality and expands support up to 12 zones.
The external antenna connector 08RFA is located underneath the wiring centre under
zones 7 and 8. After connecting an additional antenna, place the jumper in the EXT
position.
Boiler output - this is a volt free output (COM / NO) that controls the boiler in the
heating system. The output closes and the boiler turns on but always after 3 minutes
after receiving the heating signal from any of thermostats paired with wiring centre.
The output opens and the boiler switches off when the last thermostat stops sending
heat demand (after the time set on the Delay jumper).
L
230 V AC
max
1 A
N
Dew point sensor input is active only in cooling mode (with closed CO
contacts).
1
1
3
5
7
9
2
4
6
8
10
3
2
L
N
230 V AC
Scan for equipment
Open the ZigBee network
Close the ZigBee network
Online
Online
Offline
Offline
OR
OR
OR
OR
SALUS
Smart
Home
5 sec
5 sec
1 sec
5 sec
Note:
Do not use CO10RF coordinator
with UGE600 simultaneously.
5 sec
Connect equipment
15 sec
Note:
If you restore the factory settings of the wiring centre, all paired devices will be removed from
the ZigBee network - you will have to synchronize them again.
10. ZigBee network coordinator
11. Terminals for actuators
Wires of the thermoelectric actuators should be plugged into the self-locking connectors in the appropriate
zones. You can connect 3 actuators directly to one zone. The current load of one zone is adapted to operate with
up to 6 thermoelectric actuators with a power of 2 Watts. If there is a need to connect more than 6 actuators
please use an additional relay to relieve the output of the zone.
The ZigBee network coordination unit CO10RF is used
for Offline mode and it’s included with the wiring
centre. CO10RF enables wireless control of all devices
installed in one network. Within one network can be
connected max 9 wiring centres. It means that if in the
network there are more than one wiring centre, you
can use one coordinator and put the remaining ones
in a safe place.
Note:
Do not use CO10RF coordinator with
UGE600 simultaneously.
Note:
On the actuator contacts, there
is voltage 230 V AC during their work.
The operation was explained on the example of T30NC actuators.
Boiler output is inactive in the cooling mode.