ENGLISH
9. ALARM MESSAGES
SCREEN
DESCRIPTION
If the sense of the cycle of the input voltages R, S, o, T is inverted, the display
will show the following message.
KLIXON
MOTOR 1
If the internal temperature of motors 1, 2 or exceeds the KLIXON thermal
3
threshold,
the display will show
the motherboard will turn off the motor and
the following message.
DATA
LOGGER
If the current absorbed by motors 1, 2 or 3 exceeds the one set in the setup,
the motherboard will turn off the motor and the display will show the following
message.
If the current absorbed by motors 1, 2 or 3 is lower than the one set in the
setup, the motherboard will turn off the motor and the display will show the
following message.
If the supply voltage drops below the minimum voltage and this condition
persists for 5 seconds the alarm is activated, the motor is no longer powered
and you will see the following message. If the voltage is within the set range
and stays there for 60 seconds, the motherboard will automatically reset the
alarm.
If the supply voltage exceeds the maximum voltage and this condition
persists for 0.5 seconds the alarm is activated, the motor is no longer
powered and you will see the following message. If the voltage is within the
set range and stays there for 60 seconds, the motherboard will
automatically reset the alarm.
If the motherboard detects the absence of one of the three phases R, S, or T,
the display will show the following message.
ALLARME LIVELLO
MASSIMO 1.50m
If the pressure in the system falls below the value set in the MINIMUM
PRESSURE parameter of the setup, the motherboard will turn off the motor
and the display will show the following message.
If the water level in the tank exceeds the level set in the ALARM LEVEL
parameter, the display will show the following screen.
button for 2 seconds.
In the motherboard, when any type of alarm is generated, three outputs are activated, two 12Vdc
outputs respectively for siren and flashing lamp and one with pure contact relay.
All alarms are automatically reset except for the maximum current which is reset by pressing the
By means of the button it is possible to silence the siren output which will remain deactivated
until a new alarm is generated.
37
MAX. 1 CURRENT
PREMI RESET
CORRENTE MIN. 1
PREMI RESET
ALLARME
TENSIONE MINIMA
ALLARME
TENSIONE MASSIMA
ALLARME
MANCANZA FASE
ALLARME
FASI RST INVERSE
PRESSIONE MINIMA
PREMI RESET