Installation and operating instructions Salmson-IF-Modules Siriux
27
English
5.2
Technical data
General data
Terminal cross-section
1.5 mm² finely stranded
Safety in accordance with
EN 60950
Up to mains voltage 230 V, configuration TN or TT
Contact input
Version
SELV, isolated
Earth reference
Shared with control input 0-10 V
Off-load voltage
Max. 10 V
Loop current
Approx. 10 mA
Contact output
Version
Potential-free
Load rating
30 V AC/60 V DC: 1 A AC1/DC1
Min. load
12 V DC, 10 mA
Control input 0-10 V
Version
SELV, isolated
Earth reference
Shared with contact input
Voltage range
0-10 V
Input resistance
> 100 k
Accuracy
5 % absolute
Dielectric strength
24 V DC
Summary of Contents for Siriux DP
Page 2: ...Fig 1 10 U V 1 2 3 Off Aus H min n min H max n max H n...
Page 5: ...2 Pompes Salmson 12 2009...
Page 78: ......