48
SALMSON 12/2013
English
DANGER! Danger to life!
Hazardous contact voltage due to discharging converter
capacitors.
- Before any intervention on the converter, wait for 5 min-
utes after disconnecting from the supply voltage.
- Ensure that all electrical connections and contacts are
voltage-free.
- Verify the correct assignment of the connection terminals.
- Verify that pump and installation are properly earthed.
Control curves
IN1: Input signal in modes „Constant pressure“, „Variable pressure“ and „P.I.D. control“
100%
Sensor signal 4 – 20 mA
0
2
4
20
Input current (mA)
Value
in % of the sensor
measurement
range
In case of values between 0 and
2 mA, a cable is considered
as broken.
Safety
range
100%
Sensor signal 0 – 10 V
0
10
Input voltage (V)
Value
in % of the sensor
measurement range
100%
Sensor signal 0 – 20 mA
0
2
20
Input current (mA)
Value
in % of the sensor
measurement range
100%
Sensor signal 2 – 10 V
0
10
Input voltage (V)
Value
in % of the sensor
measurement range