background image

15

To install the battery module and the transformer, follow the 

steps described above for the UPS until obtaining the assembly 

shown in Fig. 11.

Fig. 11. 

Mounting the set in a 19” rack cabinet.

5.1.5.4.  Preliminary considerations before connection.

 

In the description of this manual, reference is made to the 

connection of terminals and switch operations that are 

only available in some versions or devices with extended 

backup. Ignore the related operations if your unit does not 

feature them.

 

Thermal control of these devices is carried out with the 

passage of forced air from the front to the rear.

The front surface and about 15cm on the rear side should 

be left free of obstructions to facilitate the free circulation 

of air for ventilation.

 

Follow and respect the instructions described in this sec-

tion referring to the installation of a single device or a 

system in parallel.

 

Protection or external manual bypass board:

 

ˆ

The system will have at least one short-circuit protec-

tion on the UPS’s power supply line.

 

ˆ

It is advisable to have an external manual bypass board 

fitted with input, output and manual bypass protections 

in single systems.

 

ˆ

For parallel systems, 

it is essential

 to have a distri-

bution or manual bypass board. The board’s circuit 

breakers must be able to isolate a UPS from the system 

in the event of a fault and power the loads with the 

others, either during periods of preventative mainte-

nance or during breakdown and repair.

 

Upon request, we can supply an external manual bypass 

board for a single device or parallel system.

You can also choose to manufacture it, taking into account 

the version and configuration of the device or system avail-

able and the documentation contained in the CD-ROM or 

pen drive relating to ‘Recommended installation’.

 

In the documentation supplied with this user manual 

and/or on the CD-ROM or pen drive, information is 

available on ‘Recommended installation’ for each input and 

output configuration. This documentation includes wiring 

diagrams and information about the sizes of the protections 

and the minimum cross sections of cables connected to the 

device according to their rated working voltage. All values 

Fig. 9. 

Vertically mounted tower-type model.

5.1.5.3.  Mounting a rack in a 19” cabinet.

 

To mount a device in a 19” rack cabinet, proceed as follows 

(see Fig. 10 and Fig. 11):

 

ˆ

Using the supplied screws, fix the two adapter angles 

for use as handles on each side of the UPS, respecting 

your hand.

 

ˆ

To install the device in a rack cabinet, it is necessary 

to have internal lateral guides for use as supports. Al-

ternatively, and upon request, we can supply universal 

slides for use as guides, for installation by the user.

Mount the guides at the required height, ensuring 

correct tightening of the fixing screws and appropriate 

fitting in the machining, according to each case.

 

ˆ

Place the device onto the guides and insert it all the 

way to the back.

Depending on the device model and weight, and/or 

whether it is installed in the upper or lower part of the 

cabinet, it is recommended that two people carry out 

the installation operations.

 

ˆ

Fix the UPS to the frame of the cabinet using screws.

Fig. 10. 

Mounting a UPS in a 19” cabinet.

SLC TWIN RT2 T

 UNINTERRUPTIBLE POWER SUPPLIES (UPS)

USER MANUAL        

Summary of Contents for SLC TWIN RT2 T UL

Page 1: ...UNINTERRUPTIBLE POWER SUPPLIES UPS USER MANUAL SLC TWIN RT2 T UL 6 and 10kVA...

Page 2: ...put of a single device 5 2 1 1 Connection of the UPS output to the isolation transformer s input 5 2 2 Configuration of the output 5 2 2 1 Connecting the loads 5 2 3 Connection to external batteries b...

Page 3: ...7 2 8 Warning or alert indicators 8 MAINTENANCE WARRANTY AND SERVICE 8 1 BATTERY MAINTENANCE 8 1 1 Notes for the installation and replacement of the battery 8 2 UPS TROUBLESHOOTING GUIDE 8 2 1 Trouble...

Page 4: ...ed personnel Although no effort has been spared to ensure that the in formation in this user manual is complete and accurate we accept no liability for any errors or omissions that may exist The image...

Page 5: ...manner without any doubts whatsoever Finally once the equipment is installed and operating it is rec ommended to save the documentation downloaded from the website CD ROM or pen drive in a safe and e...

Page 6: ...erial damage The EC declaration of conformity of the product is available to the customer upon express request to our offices And UL CSA and FCC markings in accordance with the speci fications of stan...

Page 7: ...ducts recovered at the end of their useful life contact your distributor Packaging For the recycling of the packaging there must be compliance with the legal requirements in force in accordance with t...

Page 8: ...ies or slight contradictions may arise If in any doubt the labelling on the device itself will always prevail The nameplate of the device shows all of the values re lating to its main properties and c...

Page 9: ...or parallel systems Communication bus for parallel systems Fans Fig 4 Rear view of 6 and 10kVA models Battery module output circuit breaker Connector for external battery module Fig 5 Rear view of the...

Page 10: ...n size 003 Last three digits of the battery code AB Initials of the battery family 6 Number of batteries in one branch 2x Number of branches in parallel Disregard for one TWIN RT2 Battery module serie...

Page 11: ...c bypass of the device provided that it has AC input power Frequency converter CF mode Operating mode of the UPS as a frequency converter In this mode the static bypass is disabled by the condition of...

Page 12: ...computer systems based on LANs and WANs often re quire that communication with any element that is integrated into the computer network be made through a standard indus trial protocol One of the most...

Page 13: ...y module 1 battery module Information for warranty registration 2 metal pieces for use as handles and screws for installing the unit in a rack cabinet 2 plastic extensions of 2U to extend the base of...

Page 14: ...they have a battery module or whether the available backup is standard or extended Follow the instructions indicated in the sections relating to either of the two possibilities according to the parti...

Page 15: ...ngle device or parallel system You can also choose to manufacture it taking into account the version and configuration of the device or system avail able and the documentation contained in the CD ROM...

Page 16: ...inals for the instal lation of an external emergency power off button EPO or failing that a single device must be installed to cut the power supply to the loads in any operating mode 5 1 5 5 Prelimina...

Page 17: ...k wiring diagram Output earth Input earth Input neutral Input line Output line Output neutral Fig 13 Detail of the UPS connection terminals Output neutral Output neutral Line 2 input Line 1 input 11 2...

Page 18: ...input UPS Isolation transformer Fig 15 UPS isolation transformer connection according to the input voltage In the case of a 208V input Isolation transformer UPS Output line Input line Input neutral Ou...

Page 19: ...e in the isolation transformer 1 Option 1 There are 2 sets of outputs at 120V Connecting a load in X1 N and another in X3 N Output 1 Output 2 Fig 17 Connection of 2 independent 120V windings 2 Option...

Page 20: ...the neutral indicated on the labelling of the device and in this manual see Fig 14 Where there are discrepancies between the labelling and the instructions in this manual labelling shall always prevai...

Page 21: ...ustration Fig 21 Connection to battery modules 5 2 4 Connection of the input earth terminal and the earth connection terminal As the device has Class I protection against electric shock it is essentia...

Page 22: ...e system This is also applicable for systems in parallel Fig 23 Terminal block for connection to the inverter shutdown auxiliary contact of the manual bypass board 5 2 7 Terminals for digital input an...

Page 23: ...fully configure UPS shutdown Communication bus Current signal bus Fig 25 Communication and current signal connections for system in parallel 5 2 8 3 Connection of the power cables The following diagra...

Page 24: ...oni toring software and updating the firmware It is not possible to use both the RS 232 and USB ports at the same time In connector DB9 the signals of the RS 232 are supplied The maximum voltage and c...

Page 25: ...will also be necessary to set the fuse or circuit breaker of the batteries arranged between each one to On Although the device can operate correctly without charging the batteries for the specified 1...

Page 26: ...f it has a distribution board set the input and output pro tections to On Set the battery switch to On extended backup models Set the device s input circuit breaker to On Press the ON button for more...

Page 27: ...he new device into the system cable with DB15 connectors it will be necessary to switch the pow ering of the loads to the manual bypass Proceed as follows Press the OFF button on all of the UPSs for m...

Page 28: ...finally leave the system in parallel operation in Normal mode The load or loads are again protected by the parallel system 6 5 HOW TO REPLACE A FAULTY UPS IN AN OPERATIONAL PARALLEL SYSTEM The steps...

Page 29: ...displaying four equivalent segments respectively in the following proportion 0 25 26 50 51 75 and 76 100 Information about programmable outputs P1 Indicates that the programmable outputs are activate...

Page 30: ...SC ESC Escape HLS HLS Upper voltage limit for transfer to battery mode LLS LLS Lower voltage limit for transfer to battery mode AO AO EPO normally open AC AC EPO normally closed EAT EAt Estimated back...

Page 31: ...ed ON Starting up the UPS Press the button for at least 2 seconds Confirmation of selection Press this button to confirmselection in the device ssettings mode TEST MUTE Press and hold the two buttons...

Page 32: ...ttery mode Battery test 01 Output voltage YES 02 Output frequency YES 03 Reserved 04 Reserved 05 ECO enable disable mode YES 06 Reserved 07 Reserved 08 Bypass mode setting YES YES 09 Maximum battery d...

Page 33: ...de powering loads when the frequency is not respectively between 46 and 54Hz or 56 and 64Hz If ATO is selected in parameter 2 parameter 3 will display the current frequency Fig 34 Code 03 Reserved Fig...

Page 34: ...ass Code 09 Maximum battery discharge time setting Fig 41 Parameter 3 setting 000 999 Sets maximum backup time The UPS will turn off automatically once it has elapsed to protect the batteries The defa...

Page 35: ...o the value of the total capacity entered up to the maximum of the current that is possible This results in faster charging and therefore greater availability and more immediate backup in the event of...

Page 36: ...anges and ECO mode is activated the UPS supplies the output voltage from the bypass in ECO mode energy saving LCD ECO CF mode Description When the output frequency is selected as CF in parameter 3 of...

Page 37: ...ance switch cover open 3D Bypass not available 3E Startup fault 41 Bypass not available 42 Overtemperature in UPS output power transformer Applicable to models with transformer with two secondaries 11...

Page 38: ...nd Overload Modulated twice every seconds Battery disconnected BATT FAULT Modulated every second Battery overcharge Modulated every second EPO activated Modulated every second Fan fault Overtemperatur...

Page 39: ...d out by our T S S except for the replacement of batteries which can be performed by qualified personnel familiar with them No other person should handle them Depending on the configuration of the UPS...

Page 40: ...35 36 41 42 43 6E 6D are displayed on the LCD display and the audible alarm sounds continuously An internal fault has occurred in the UPS This is due to one of two possibilities 1 The load is still p...

Page 41: ...erformance at full load in line mode with battery 100 charged 89 Efficiency at full load in ECO mode 93 5 Overload in line mode 100 110 10 min 110 130 1 min 130 1 sec Overload in battery mode 100 110...

Page 42: ...tor between two points with different potential Unlike AC in DC electrical loads always circulate in the same direction from the point of greatest potential to the lowest Although DC is commonly ident...

Page 43: ...erter An inverter is a circuit used to convert DC into AC The function of an inverter is to change a DC input voltage to a symmetrical AC output voltage with the magnitude and frequency desired by the...

Page 44: ...44 SALICRU...

Page 45: ...45 SLC TWIN RT2 T UNINTERRUPTIBLE POWER SUPPLIES UPS USER MANUAL...

Page 46: ...alicru salicru_SA Product Range Uninterruptible Power Supplies UPS Stabilisers Step Down Light Dimmers Power Supplies Static Inverters Photovoltaic Inverters Voltage Stabilisers Information about our...

Reviews: