- 26 -
After 3 minutes of no operation, the LCD panel will display the menu 1 STATUS AND ALARMS DISPLAY.
3.7.- Menu 6: Data logger display.
In this menu the end-user can check the last 1.024 events / alarms in chronological order.
By selecting 6.EVENTS DATA LOGGER in the main menu and after that selecting DATA LOGGER, the data logger is displayed.
The screen will show the date and time of the last event.
The log list can be checked using the keys <BACK or NEXT>.
At any position of the log list, by pressing MENU, the LCD panel will come back to the MAIN MENU.
To delete all the events and alarms, the submenu DELETE DATA LOGGER must be selected and after that press
<ENTER>.
After 3 minutes of no operation, the LCD panel will display the menu 1 STATUS AND ALARMS DISPLAY.
3.8.- Menu 7: Service.
The control PCB can be connected to a notebook computer through optical fiber. This way, the Service and Technical Support can
diagnose or set the parameters of the UPS. To make this procedure or to check the software version of the signalling, we must
enter into the menu 7. SERVICE MODE. This menu is protected, by a password that denies the access to not authorised personal.