1
Description
Uninterruptible power supply
TRIO-UPS-2G/1AC/24DC/10
© PHOENIX CONTACT
Data sheet
The TRIO-UPS-2G uninterruptible power supply (UPS) with
integrated power supply unit is used to ensure that secure
DC power for critical electrical loads continues to be
supplied in the event of disturbances in the power supply
network, e.g. due to mains breakdown or failure. In the event
of such a disturbance, the UPS switches to battery
operation without interruption so that connected loads
continue to be continuously supplied. In this operating
mode, the output voltage is directly dependent on the
battery voltage. When mains power is restored, the UPS
automatically returns to normal operation. The connected
loads are again supplied via the power supply network and
the battery is charged at the same time. The TRIO-UPS-2G
uninterruptible power supply (UPS) is designed specifically
for supplying industrial PCs (IPCs).
Features
–
Power supply, loading unit and electronic switchover
unit in a device
–
Wide-range input AC
–
Adjustable output voltage in mains operation
–
USB interface for configuration and diagnostics
–
Adjustable charging parameters for the use of different
types of energy storage
–
Comprehensive signaling
Technical data (short form)
Input voltage range
100 V AC ... 240 V AC
110 V DC ... 250 V DC
Nominal output voltage (U
N
)
24 V DC
Nominal output current (I
N
)
10 A
Buffer period
to 3 h
Residual ripple
< 20 mV
MTBF (IEC 61709, SN 29500)
> 2007013 h (230 V AC, at 25 °C)
> 1210518 h (230 V AC, at 40 °C)
> 575978 h (230 V AC, at 60 °C)
Maximum power dissipation in no-
load condition
< 3 W (for 230 V AC)
Power loss nominal load max.
< 32 W (for 230 V AC)
Ambient temperature (operation)
-25 °C ... 70 °C ( > 60 °C Derating:
2.5 %/K )
Ambient temperature (start-up type
tested)
-40 °C
Dimensions W/H/D
68 mm / 130 mm / 160 mm
Weight
1.34 kg
Make sure you always use the latest documentation.
It can be downloaded from the product at
phoenixcontact.net/products
.
107432_en_02