TRIO-UPS-2G/1AC/24DC/10
107432_en_02
PHOENIX CONTACT
11 / 30
–
Observe the national safety and accident prevention
regulations.
–
Assembly and electrical installation must correspond to
the state of the art.
–
The uninterruptible power supply is a built-in device.
The protection class IP20 of the device is meant to be
applied in a clean and dry environment.
–
The device must be installed in a control cabinet that
can be locked and only opened by specialist staff.
–
Horizontal mounting position (normal mounting
position)
–
Observe mechanical and thermal limits.
–
Ensure sufficient convection (minimum gap above/
below: 50 mm). Housing can become hot.
–
Ensure that the primary-side wiring and secondary-side
wiring are the correct size and have sufficient fuse
protection.
–
Refer to the associated table for the connection
parameters, such
as the necessary stripping length for
the wiring with and without ferrule (see section Wire
cross sections).
–
Protect the device against foreign bodies penetrating it,
e.g., paper clips or metal parts.
–
To reduce the risk of fire, replace only with same type
and rating of fuse.
–
To reduce the risk of fire, connect only to a circuit
provided with the following maximum branch circuit
overcurrent protection in accordance with the National
Electrical Code, ANSI/NFPA 70.
–
The uninterruptible power supply is maintenance-free.
Repairs may only be carried out by the manufacturer.
The warranty no longer applies if the housing is opened.
–
The uninterruptible power supply may only be used for
its intended use.
–
Improper use invalidates the device protection.
–
Use current-limited source or suitable fuse.
–
The switching outputs are active outputs according to
SELV. These may only be operated on permitted SELV
circuits.
–
Keep these instructions in a safe place – this data sheet
contains important safety notes which must be
observed during installation and maintenance of the
UPS devices and batteries.
NOTE
More follows