8. TECHNICAL SPECIFICATIONS.
MODEL
SLC ENERGY MANAGER
Single Phase Lite
Single Phase
Three Phase
INPUT CHARACTERISTICS
Nominal Voltage
110 - 240 Vac
Mains Supply Voltage
fluctuation
±
10%
Frecuency
50/60 Hz
Nominal Current
0,05 A
VOLTAGE
MEASUREMENTS
Voltage range
110 - 265 Vac
Frcuency range
50/60 Hz
Accuracy
1%
CURRENT
MEASUREMENTS
Output current
…/ 100 mA or …/ 5A
Overcurrent
120% In
Accuracy
1%
COMMUNICATIONS
USER
User Interface
Embedded web
INVERTER
Physical layer
RS-485
Protocol
Modbus
Speed
9600
Data bits
8
Stop bit
1
Parity
No
RELAYS
Quantity
-
2
Rated Voltage
-
250 Vac
Rated Current
-
6 A
DIGITAL INPUT
Quantity
-
1
Type
-
5 Vdc
Connexion
-
Dry Contact
MECHANICAL
CHARACTERISTICS
Size
a: 103,5 mm
l: 66 mm
p: 70,45 mm
Weight
0,225 kg
Case
PC+ABS UL94V-0
Mounting
DIN rail
Torque
0,5 - 0,6 Nm
ENVIRONMENTAL
CHARACTERISTICS
Protection
IP 20
Pollution degree
2
Use
Indoor
Temperature
0 - 50 ºC
Altitude
3000 m
Relative humidity
(without condensation)
95 %
Installation category
CAT II
Tab. 3. Technical specifications.
SLC ENERGY MANAGER
ENERGY METER
USER'S MANUAL
Summary of Contents for Equinox SLC
Page 1: ...SLC ENERGY MANAGER ES EN MANUAL DE USUARIO ENERGY MANAGER...
Page 2: ...2 SALICRU...
Page 14: ...14 SALICRU...
Page 15: ...15 ES SLC ENERGY MANAGER ENERGY METER USER S MANUAL...
Page 17: ...SLC ENERGY MANAGER EN USER S MANUAL ENERGY MANAGER...
Page 18: ...18 SALICRU...
Page 30: ...30 SALICRU...
Page 31: ...EN 31 SLC ENERGY MANAGER ENERGY METER USER S MANUAL...