background image

- 14 -

Examples to the LCD display:

If the mains supply exist:

If the mains supply do not exist:

Summary of Contents for ADVANCE 1000-HV

Page 1: ...EK459B01 User s manual installation and start up UNINTERRUPTIBLE POWER SUPPLY ADVANCE series...

Page 2: ...2...

Page 3: ...Back panel 5 INSTALLATION 5 1 Inspecting the Equipment 5 2 Placement 5 3 Charging 5 3 1 Load connection 5 4 Modem Phoneline Connection 5 5 DC Start function 5 6 Turn On Off 5 7 UPS Setup 5 7 1 Tower...

Page 4: ...dures for the installation commissioning maintenance and troubleshooting of UPS from ADVANCE series This manual has to be read carefully before installing and operating it Keep this manual for future...

Page 5: ...ges to the environment separate this product from other residuals and recycle it suitably The users can contact with their provider or with the pertinent local authorities to be informed on how and wh...

Page 6: ...ty and Environment depart ment who with independence of other responsibilities has the responsibility and authority to assure that the processes of the quality and environmental management system are...

Page 7: ...ot regulated by these standards it is necessary to correct them in some installations Depending on the installation conditionsof UPS ADVANCE series the corrections described in the Electromagnetic Com...

Page 8: ...has been designed to respect the environment and has been manufactured in accordance with the standard ISO 14001 Recycling the UPS ADVANCE series at the end of its useful life SALICRU commits to use t...

Page 9: ...e Site Wiring Fault Battery Fault Self Test Failure A push button from the front panel allows silencing of the AC fail alarm and the initiation of the UPS self test sequence as well The UPS case for 7...

Page 10: ...The total view of the LCD in front panel The primary introduction to above figure 1 Power Switch To turn on the UPS press the ON OFF button more than three seconds To turn off the UPS press and hold t...

Page 11: ...allows you to select the Rated voltage one by one Step 3 After selecting the mode press the ENTER button more than three seconds the Rated voltage is configured Step 4 UPS will automatically transfer...

Page 12: ...y is empty the symbol will flicker every second 9 Output paremeters voltage frequency This part gives the information of the output including output voltage and output frequency The figure indicates t...

Page 13: ...e LCD will display FAULT CODE 5 constantly Output short circuit The LCD will display FAULT CODE 6 constantly Other fault type The LCD will display FAULT CODE 8 constantly 13 Input type Operation mode...

Page 14: ...14 Examples to the LCD display If the mains supply exist If the mains supply do not exist...

Page 15: ...15 4 2 Introducing the LCD display 4 3 Audible alarm introduction polarity...

Page 16: ...50 1000VA Models 1000 LV 750 LV 1000 HV 750 HV Rear panel description for LV and HV models table 1500 2000VA Models UPS module The host rear panel pictures for HV and LV models are shown as below Rear...

Page 17: ...17 Rear panel for LV model Rear panel description for LV and HV models table Battery module Rear panel for HV model or AS400...

Page 18: ...18 Rear panel for LV model Rear panel description for LV and HV models table 3000VA model Rear panel for HV model...

Page 19: ...19 Rear panel for LV model Rear panel description for LV and HV models table SNMPSlot orAS400 SNMPSlot orAS400...

Page 20: ...to avoid interference 5 3 Charging This UPS is shipped from the factory with its internal battery fully charged however some charge may be lost during shipping The battery should be recharged prior to...

Page 21: ...nt Setup 5 7 1 Tower Setup This series can be placed in horizontally and vertically 3000VA model is designed in a rack itself As a tower it is provided with the optional UPS stand to stabilize the UPS...

Page 22: ...22 c Tower form 3 3000VA model Tower form setup 1 Slide down the UPS vertically and put two UPS stands at the end of the tower 2 Place the UPS into two stands carefully...

Page 23: ...need 2U of valuable rack space Use the following procedure to install UPS in a rack 750 1000VA models optional 1 Align the mounting ears with screw holes on the side of the UPS 2 Install rack mountin...

Page 24: ...and Battery integrate into a rack form 1 Place the UPS on a flat and in a clean place that the front side of the UPS is facing to you 2 Disconnect the cable from the UPS and Battery modules UPS and B...

Page 25: ...Align the mounting bracket with the screwholes onthe each side of UPS and Battery modulesand secure withthe supplied screws 6 Reinstall the UPS and Battery modules cover 7 Tighten all screws up to fr...

Page 26: ...the rear panel of the UPS 9 Setup rack mount is completed and to connect the UPS Battery and Battery modules integrate a rack form The rackmount kit for connecting the UPS to Battery Battery to Batter...

Page 27: ...er management software Follow the procedure to install the E P O switch as below 1 Check the UPS is turned off 2 Remove the E P O connector from the E P O port on the rear panel of UPS 3 Connect isola...

Page 28: ...ional battery Follow the procedure to install additional battery as below 1500 2000VA models There are two external battery ports for each side of UPS itself and battery pack 1 Connect the battery cab...

Page 29: ...external battery port for the UPS itself 1 Connect the supplied battery module cable from extended battery module to the external battery port of the rear of UPS 2 If continuing to add up extended bat...

Page 30: ...ries in a fire The batteries may explode Ifyou are notqualified service personnel to replace the battery do not attemptto open the battery door Please call local dealer or distributor immediately Recy...

Page 31: ...le and screw up the battery retaining battery bracket 6 Close and reinstall the front panel 1500 2000VA models 1 Remove the battery case front panel by pulling on both ends 2 Disconnect the battery ca...

Page 32: ...area 5 Slide the new battery into Battery module 6 Reconnect the battery cable and screw up the battery retaining bracket 7 Close and reinstall the front panel back to Battery module 3000VA model 1 Re...

Page 33: ...y pulling on both ends 5 Pull the battery out from right side onto flat area 6 Pull the left side of battery out onto flat area 7 Slide the new batteries into Battery module 8 Reconnect the battery ca...

Page 34: ...r which allows to communicate with other equipments like the standard RS232 optocouplers simultaneously but the AS400 provides dry contacts from relays instead of optocouplers and it has a higher quan...

Page 35: ...cription I O 1 UPS failure Output 2 General alarm Output 5 Common Input 7 Low battery Output 8 UPS On Output 9 Mains failure Output 5 1 9 6 The following table and diagram shows the pin out of female...

Page 36: ...36 9 TROUBLE SHOOTING 9 1 Audible Alarm Trouble Shooting 9 2 General Trouble Shooting...

Page 37: ...37 10 SPECIFICATION Optocouplers 10 5 21 5 N A N A...

Page 38: ...while power failure With this software users can monitor and control any UPS on the same LAN no matter how far from the UPSs Installation procedure 1 Insert CD The installation assistant runs up autom...

Page 39: ...39...

Page 40: ...salicru com 08460Palautordera Tel 3493 8482400 sat salicru com...

Reviews: