background image

38

SALICRU

7.3.4.2.  operating mode / description of state.

Operating mode / state

UpS start-up

description.

when the UpS is started, the display screen of this mode is displayed for a few seconds to initialise the CpU and system.

LCd display.

no output mode

description.

If the bypass voltage / frequency is out of range or the bypass is disabled (or prohibited), the UpS will enter no output mode with the inverter 

running or shut down. The UpS does not supply output voltage. The audible alarm modulated every two minutes is audible.

LCd display.

AC mode

description.

If the input voltage is within the range of the device, the UpS will supply stable AC sine-wave voltage to the load or loads, and charge the 

batteries.

LCd display.

eCo mode

description.

If the input voltage is within the regulation ranges and eCo mode is activated, the UpS supplies the output voltage from the bypass in eCo 

mode (energy saving).

LCd display.

ECO

CF mode

description.

when the output frequency is selected as CF in parameter 3 of the settings menu code 02, the inverter supplies a constant output frequency 

(50 or 60 hz). In this way, the UpS will not supply bypass output voltage, but will charge the batteries.

LCd display.

battery mode

description.

when the input / frequency voltage is not within the predefined range of the device or there is an AC mains failure, the UpS powers the loads 

from the batteries for a limited time due to their own capacity and activates the audible alarm modulated every 4 seconds.

LCd display.

bypass mode

description.

when the input voltage is within the predefined range of the device and the bypass is enabled, when the UpS is switched off, the device 

enters bypass mode. The audible alarm modulated every two minutes is activated.

LCd display.

Summary of Contents for 698CC000002

Page 1: ...SLC TWIN RT2 0 7 10 kVA UNINTERRUPTIBLE POWER SUPPLY SYSTEMS UPS USER MANUAL...

Page 2: ...on battery module 5 1 5 6 Vertical tower type mounting with PDU 5 1 5 7 Rack mounting in 19 cabinet with PDU 5 1 5 8 Preliminary considerations before connection 5 1 5 9 Preliminary considerations bef...

Page 3: ...7 2 4 2 Operating mode Description of state 7 2 4 3 Warning or alert codes 7 2 4 4 Error or fault codes 7 2 4 5 Warning or alert indicators 7 3 Control panel for 4 kVA to 10 kVA models 7 3 1 Audible...

Page 4: ...ed personnel Although no effort has been spared to ensure that the information in this user manual is complete and accurate we are not responsible for any errors or omissions that may exist The images...

Page 5: ...ssioning to be performed in a simple and orderly manner without having any doubts whatsoever Finally once the equipment is installed and operating it is recommended to save the documentation downloade...

Page 6: ...duct may cause radio interference in which case the user must take additional measures SLC TWIN RT2 4 10 kVA This is a category C3 UPS This is a product for commercial and industrial application in th...

Page 7: ...self will always prevail The nameplate of the device shows all of the values relating to its main properties and characteristics Act accordingly for its installation 0 7 to 3 kVA models 4 to 10 kVA mo...

Page 8: ...grammable at disconnection for non critical loads Connector for connection to external battery module Standard and B1 3 kVA models COM port USB RS232 COM port AC power IEC connector Smart slot protect...

Page 9: ...ery module connector Fig 3 Rear view of battery modules for extended backups PDU for 4 to 6 kVA devices Output circuit breaker Output IEC connectors Output circuit breaker Output IEC connectors PDU fo...

Page 10: ...without batteries but with a space reserved for installation in the same box for models whose standard version specifies this For other models the battery pack will be installed in the manner conside...

Page 11: ...ains contact T S S With the inverter shut down the output supplies mains power directly through the static bypass of the device provided that it has AC input power Frequency converter CF mode Operatin...

Page 12: ...hout interruptions to the power supply of the protected system while preventing unnecessary hazards for the technical personnel 4 5 3 Communication card The UPS features a slot at the rear for inserti...

Page 13: ...UPS 1 battery module Information for warranty registration 2 metal pieces for use as handles and screws for installing the unit in a rack cabinet 2 plastic pieces to extend the base of the UPS and ena...

Page 14: ...distance is considerable it is recommended to transport the device in its packaging to the installation site and then unpack it 5 1 5 Siting immobilising and considerations All TWIN RT2 series UPSs ar...

Page 15: ...t the guides at the required height ensuring correct tightening of the fixing screws and appropriate fitting in the machining according to each case Place the device onto the guides and insert it all...

Page 16: ...he upper or lower part of the cabinet it is recommended that two people carry out the installation operations Fix the UPS and the battery module to the cabinet frame by means of the screws supplied wi...

Page 17: ...n of the cables must always be considered in relation to the size of the terminals of the switches so that they are correctly fastened across their entire cross section for optimum contact between the...

Page 18: ...g systems in parallel only in models 3 kVA To access the signal block it is necessary to remove its protective cover Slot for the integration of one of the optional electronic communication units Remo...

Page 19: ...ig 2 as critical loads will be reserved Take into account that they are set by default as critical loads The 3 kVA models also have a 16A IEC connector that enables the connection of a load of the tot...

Page 20: ...through the mesh available in the cable bundle of them being compulsory to fix the con nectors of both ends to the connectors fitted in the battery case by means of the supplied screws and duly tight...

Page 21: ...of each UPS In the event of acquiring a manual bypass board through another conduit check that it has this auxiliary contact and connect it to the terminal block of the UPS or each device in parallel...

Page 22: ...ngth between the input and output cables of the device must be less than 20 When the distance between the UPSs in parallel and the circuit breaker board is more than 20 metres the difference in length...

Page 23: ...from each other Fig 20 View of ViewPower s main screen Installation procedure Go to the web page http support salicru com Select the required operating system and follow the instructions described on...

Page 24: ...ns depending on the model will start to function Then the main start screen will be displayed after a test of the device On the 4 to 10 kVA models it is necessary to press the ON button for a second t...

Page 25: ...nd The devices that make up the current parallel system will switch to Bypass mode Switch the devices to manual bypass 1 Remove the mechanical lock on the distribution board s manual bypass switch or...

Page 26: ...a faulty UPS in an operational parallel system The steps to follow to replace a UPS in a system consisting of two or three units are the same as those for incorporating a device except for the differ...

Page 27: ...cted to the output as a by displaying four equivalent segments respectively in the following proportion 0 25 26 50 51 75 and 76 100 Information about programmable outputs P1 Indicates that the program...

Page 28: ...ESC ESC Escape HLS HLS Upper voltage limit for transfer to battery mode LLS LLS Lower voltage limit for transfer to battery mode AO AO EPO normally open AC AC EPO normally closed EAT EAt Estimated bac...

Page 29: ...ble with each press OFF ENTER UPS shutdown Press this button for at least 2 seconds Confirmation of selection Press this button to confirmselection in the device ssettings mode Tab 6 Functionality of...

Page 30: ...ctly related to the capacity of the battery pack The charger will adapt the charging factor automatically according to the value of the total capacity entered up to the maximum of the current that is...

Page 31: ...ameter 02 ENA the CF 50 or CF 60 variables are displayed instead of BAT 50 or BAT 60 DIS ECO mode disabled ENA ECO mode enabled ENA Bypass enabled with the inverter of the UPS Off DIS Bypass disabled...

Page 32: ...the output voltage from the bypass in ECO mode energy saving LCD display CF mode Description When the input frequency is between 46 and 64 Hz the UPS can be set to a constant output frequency of 50 o...

Page 33: ...too low 2A Battery charger short circuited at its output 41 Overtemperature 43 Output overload 45 Charger fault 49 Input overcurrent Tab 13 Error or fault code 7 2 4 5 Warning or alert indicators Code...

Page 34: ...in relation to the point where it is located ON Starting up the UPS Press the button for at least 2 seconds Confirmation of selection Press this button to confirmselection in the device ssettings mod...

Page 35: ...codes list Description and settings Code 01 Output voltage Fig 27 Parameter 3 setting Output voltage It is possible to choose one of the following values for the output voltage between phase and neutr...

Page 36: ...Bypass enabled When selected bypass mode is enabled DIS Bypass disabled If selected automatic bypass is permitted but not manual switch to bypass At this point manual switch to bypass is understood as...

Page 37: ...external battery pack of 45 Ah belonging to it 45 Ah 7 Ah 6 4 When rounding down value 6 must be entered in parameter 3 The basic reason for adjusting the setting is as follows without it affecting t...

Page 38: ...n the regulation ranges and ECO mode is activated the UPS supplies the output voltage from the bypass in ECO mode energy saving LCD display ECO CF mode Description When the output frequency is selecte...

Page 39: ...switch cover open 3D Bypass not available 3E Start up fault Tab 20 Warning or alert code 7 3 4 4 Error or fault codes Code Error or fault description 01 DC bus start up fault 02 DC bus overvoltage 03...

Page 40: ...nal which is in turn connected to earth any metal part of the device Repair and or maintenance work must be carried out by our T S S except for the replacement of batteries which can be performed by q...

Page 41: ...After repeated overloads the UPS is locked in Bypass mode The connected loads are powered directly from the mains Disconnect the excess loads from the output sockets shut down the device and restart i...

Page 42: ...of the following fault codes 01 02 03 04 11 12 13 14 1A 21 24 35 36 41 42 or 43 are displayed on the LCD display and the audible alarm sounds continuously An internal fault has occurred in the UPS Thi...

Page 43: ...ged 89 90 91 93 Performance at full load in ECO mode 95 96 97 99 Overload in line mode 110 130 5 min 100 110 10 min 130 140 30 sec 110 130 1 min 140 150 1 5 sec 130 1 sec 150 100 ms Overload in batter...

Page 44: ...rallel devices 5 As a frequency converter the power supplied will be 78 of the rated 6 As a frequency converter the power supplied will be 60 of the rated Tab 25 General technical specifications 9 2 G...

Page 45: ...g through the visible light spectrum to infrared the latter called IRED infra red emitting diode Circuit breaker A circuit breaker is a device capable of interrupting the electrical current of a circu...

Page 46: ...46 SALICRU...

Page 47: ...47 SLC TWIN RT2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS UPS USER MANUAL...

Page 48: ...any salicru salicru_SA Product Range Uninterruptible Power Supplies UPS Lighting Flow Dimmer Stabilisers DC Power Systems Static Inverters Photovoltaic Inverters Voltage stabilisers The Technical Serv...

Reviews: