0: Master

1 - 247: Slave

Holding 

register

0x11

17

Modbus duomenų perdavimo 

greitis

0: 1200

1: 2400

2: 4800

3: 9600

4: 19200

5: 38400

6: 57600

7: 115200

Holding 

register

0x12

18

Modbus parity

0: None

1: Even

2: Odd

Holding 

register

0x13

19

Valdomas įrenginys

0: None

1: Custom

2: ECO

3: PRV

Holding 

register

0x14

20

Valdomo įrenginio Modbus adresas 1 - 247

Holding 

register

0x15

21

SET Temperature address 00:00 - FF:FF

Holding 

register

0x16

22

SET Fan speed (%) address 00:00 - FF:FF

Holding 

register

0x17

23

SET Fan speed fixed address 00:00 - FF:FF

Holding 

register

0x18

24

SET Pressure address 00:00 - FF:FF

Holding 

register

0x19

25

SET CO2 address 00:00 - FF:FF

Holding 

register

0x1A

26

Temperature address 00:00 - FF:FF

Holding 

register

0x1B

27

Alarm 1 address 00:00 - FF:FF

Holding 

register

0x1E

28

Alarm 2 address 00:00 - FF:FF

Holding 

register

0x1F

29

Alarm 3 address 00:00 - FF:FF

Holding 

register

0x20

30

Alarm 4 address 00:00 - FF:FF

Holding 

register

0x21

31

Alarm 5 address 00:00 - FF:FF

Holding 

register

0x22

32

Alarm 6 address 00:00 - FF:FF

Holding 

register

0x23

33

Alarm 7 address 00:00 - FF:FF

Holding 

register

0x24

34

Alarm 8 address 00:00 - FF:FF

Holding 

register

0x25

35

Alarm 9 address 00:00 - FF:FF

Holding 

register

0x26

36

Alarm 10 address 00:00 - FF:FF

Holding 

register

0x27

37

Atkurti pultelio gamyklinius para-

metrus

0: Ne

1:Taip

Holding 

register

0x28

38

Miego režimas

0 - Išjungtas

1 - 99 užmigimo laikas 

sekundėmis

Holding 

register

0x29

39

Summary of Contents for Stouch

Page 1: ...x 370 41 540417 office salda lt www salda lt Art no GAUSTOUCH001 Sensorinis pultelis Sensor controller Sensorpult Bo tier de commande tactile lt Psl 2 ru C 17 en Pg 33 de S 49 fr P 64 Stouch Techninis...

Page 2: ...tinkiniam montavimui Vieno paspaudimo sensorinis valdymas Lengvai valomas Skai i atvaizdavimas ekran lyje Garsinis atsakas lietim Gali b ti prijungtas prie BMS tinklo Galima tiesiogiai prijungti prie...

Page 3: ...nis kabelio jungimas Montavimas 2 2 specialus jungimas i r ti 8 kontakt jungimas 3 U kabinkite pultel laikydami j pasukt 25O kampu kair pus 4 5 Sukite pultel de in kol pultelis prisispaus prie plok tu...

Page 4: ...imas 2 PASTABA Maitnimo altinis turi b ti parenkamas priklausomai nuo pultelio bei oro kokyb s keitiklio naudojamos srov s Maitinimo altinis su pulteliu nekomplektuojamas 1 Kai pultelis naudojamas su...

Page 5: ...IS 150P EKO M M RIS 150P EKO3 1 PE 2 N 3 L 4 GND 5 0 10VDC IN 6 10VDC OUT STouch CON1 F F Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S KCO2 DSC G A3 F L N PE G 230VAC_24VDC 1 24VDC AC 2 24VAC DC 3...

Page 6: ...ND 0 10V PWM F F F STouch CON1 1 24VDC AC 2 24VAC DC 3 GND 4 RS465 B 5 RS485 A 6 GND 7 0 10VDC IN 8 0 10VDC OUT Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S KCO2 DSC G A4 N L PE G 230VAC_24VDC PAST...

Page 7: ...jos Informacija vartotojui Pultelyje sukurtas paprastas vartotojo meniu garso temperat ros miego re imo bei CO2 lygio parametr nustatymui Spartusis maksimalaus grei io aktyvavimo mygtukas Nustatytos b...

Page 8: ...liavus gedimo prane im pultelis gr ta pradin b sen PASTABA grie tai draud iama anuliuoti gedim nepa alinus jo prie asties Tai turi atlikti serviso atstovai ar rengin aptarnau jantis personalas L2 L7 V...

Page 9: ...nius renginius F 20 meniu punkte reikia nurodyti CUSTOM bei rengini adresus meniu punktuose nuo Nr F 22 iki F 37 Jeigu renginiai toki adres neturi nurodytuose meniu punkt laukeliuose reikia vesti 00 0...

Page 10: ...kybes keitikliai ir nuotolinis valdymo pultelis kai valdomas ventiliatorius turi b ti maitinami nuo atskiro maitinimo altinio Su pulteliu jis nekomplektuojamas PULTELIS slave FAN 0 10 VDC MODBUS 4 Sl...

Page 11: ...nt patekti serviso meniu reikia 1 Perjungti b sen I jungta jei pultelis jungtas 3 sekundes palaikyti B1 element 2 3 sekundes palaikyti B1 ir B2 3 vesti apsaugos kod 022 su B4 B6 elementais ir patvirti...

Page 12: ...27 Temperature address 00 00 FF FF 00 00 F 28 Alarm 1 address 00 00 FF FF 00 00 F 29 Alarm 2 address 00 00 FF FF 00 00 F 30 Alarm 3 address 00 00 FF FF 00 00 F 31 Alarm 4 address 00 00 FF FF 00 00 F...

Page 13: ...lding register 0x01 1 I jungimo blokavimas 0 Neblokuojama 1 Ventiliatorius visada pu ia minimaliai 1 grei iu Holding register 0x02 2 1 greitis 0 100 Holding register 0x03 3 2 greitis 0 100 Holding reg...

Page 14: ...ster 0x19 25 SET CO2 address 00 00 FF FF Holding register 0x1A 26 Temperature address 00 00 FF FF Holding register 0x1B 27 Alarm 1 address 00 00 FF FF Holding register 0x1E 28 Alarm 2 address 00 00 FF...

Page 15: ...C ON OFF 0 ON 1 OFF Holding register 0x38 51 Current fan speed 0 100 Input register 0x01 1 Current fixed fan speed 0 4 Input register 0x02 2 Temperature Setpoint 150 350 C 10 Input register 0x03 3 Cur...

Page 16: ...s jutiklio gedimas Gedim prane imai Kai v dinimo renginys su ECO valdikliu Indikacija Reik m avarijos apra ym i r ti renginio techniniame vadove A 01 Aktyvuota ilumokai io prie u alimin apsauga A 02 S...

Page 17: ...RU 17 S touch www salda lt Stouch SALDA PRV ECO Modbus BMS 0 10VDC 0 10VDC CO2 4 boost StandBy CO2 Stouch 13 6 3 9x25 DIN 7981 2 5x25 2 12x30 2 84 mm 20 5 mm 1 5 mm 84 mm...

Page 18: ...RU 18 S touch www salda lt 1 1 2 2 1 2 2 8 3 25 4 5 1 4 1 2 3 4 PIN1 24V PIN2 B PIN3 A PIN4 COM PIN1 24V PIN2 B PIN3 A PIN4 COM...

Page 19: ...dbus 5 RS485 A Modbus 6 GND 7 0 10VDC CO2 8 0 10VDC 0 10 VDC 1 GND DC 2 1 Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S KCO2 DSC G A2 STouch CON1 F F AHU RS485_1 L N G 230VAC_24VDC 1 24VDC AC 2 24VA...

Page 20: ...M RIS 150P EKO3 1 PE 2 N 3 L 4 GND 5 0 10VDC IN 6 10VDC OUT STouch CON1 F F Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S KCO2 DSC G A3 F L N PE G 230VAC_24VDC 1 24VDC AC 2 24VAC DC 3 GND 4 RS465 B...

Page 21: ...1 2 5kW 4A 2970min 1 PE N L 10V Tacho GND 0 10V PWM F F F STouch CON1 1 24VDC AC 2 24VAC DC 3 GND 4 RS465 B 5 RS485 A 6 GND 7 0 10VDC IN 8 0 10VDC OUT Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S K...

Page 22: ...RU 22 S touch www salda lt B1 B2 B3 B4 B5 boost B6 S1 L4 L7 CO2 LED A 01 A 02 LED...

Page 23: ...1 B2 B4 B6 L2 2 L2 4 6 B3 B4 B6 L3 3 L3 4 6 B4 B6 L4 L7 4 6 L4 L5 L6 L7 B4 B5 B6 L2 boost 2 5 L2 600 4 6 BOOST 180m 3H B4 B6 L4 L7 3 2 3 L4 L5 L6 L7 A 01 A 02 B4 B6 L2 L7 2 L2 L3 L7 L4 L5 L6 B2 B3 B5...

Page 24: ...B5 B4 B6 B5 P 04 P 05 10 20 20 x 10 200 6 5 5 c y B1 MODBUS F 17 F 18 F 19 F 20 F 21 F 20 CUSTOM F 22 F 37 00 00 ECO PRV master MODBUS slave 1 Modbus master P 01 0 1 99 0 P 02 0 1 1 9 2 P 03 0 1 0 P 0...

Page 25: ...nagement System MODBUS slave slave BMS slave slave MODBUS RS485 2 Modbus slave 3 Modbus CO2 0 10VDC F 01 F 03 F 04 F 05 F 06 slave 0 10 VDC MODBUS 4 Modbus 0 10VDC 0 10VDC Modbus slave 1 5 6 1 2 ir 3...

Page 26: ...P 05 1 B1 3 2 B1 B2 3 3 022 B4 B6 B5 F 01 F 02 B4 B6 B5 B4 B6 B5 3 1 F 01 0 0 100 1 2 1 F 02 0 1 1 1 F 03 1 0 100 20 F 04 2 0 100 40 F 05 3 0 100 70 F 06 4 boost 0 100 100 F 07 1 0 999 5 F 08 2 0 999...

Page 27: ...F 25 00 00 FF FF 00 00 F 26 CO2 00 00 FF FF 00 00 F 27 00 00 FF FF 00 00 F 28 1 00 00 FF FF 00 00 F 29 2 00 00 FF FF 00 00 F 30 3 00 00 FF FF 00 00 F 31 4 00 00 FF FF 00 00 F 32 5 00 00 FF FF 00 00 F...

Page 28: ...0 100 0x05 5 4 boost 0 100 0x06 6 1 0 999 0x07 7 2 0 999 0x08 8 3 0 999 0x09 9 4 boost 0 999 0x0A 10 PID P 0 999 0x0B 11 PID I 0 999 0x0C 12 PID D 0 999 0x0D 13 0 1 2 2 0x0E 14 0 250 x10 0x0F 15 Modbu...

Page 29: ...00 00 FF FF 0x16 22 00 00 FF FF 0x17 23 00 00 FF FF 0x18 24 00 00 FF FF 0x19 25 2 00 00 FF FF 0x1A 26 00 00 FF FF 0x1B 27 1 00 00 FF FF 0x1E 28 2 00 00 FF FF 0x1F 29 3 00 00 FF FF 0x20 30 4 00 00 FF F...

Page 30: ...4 0x02 2 Temperature Setpoint 150 350 C 10 0x03 3 Current Temperature 500 1000 10 0x04 4 Pressure Setpoint 0 999Pa 0x05 5 Current pressure 0 999Pa 0x06 6 CO2 Setpoint 0 999ppm 0x07 7 Current CO2 0 99...

Page 31: ...RU 31 S touch www salda lt A 01 A 02 A 03 A 04 P mA A 05 A 06 A 07 A 08 A 09 ECO A 01 A 02 A 03 A 04 A 05 A 06 DTJ 100 A 07 A 08 A 09 DTJ 100 A 10 A 11 PRV...

Page 32: ...RU 32 S touch www salda lt A 01 A 02 A 03 A 04 A 05 A 06 A 07 A 08 A 09 A 10 CUSTOM modbus CUSTOM...

Page 33: ...ceptional and ergonomic design Easy operation Surface mounted One touch control Easily controlled Numbers displayed at screen Acoustic response to touch Can be connected to BMS network Can be directly...

Page 34: ...ection Installation 2 2 spec connection see 8 pin connection 3 Attach the special controller by positioning it rotated to the left at the angle of 25 4 5 Turn the controller to the right until the con...

Page 35: ...air quality converter the power supply and analog output GND of witch are not electrically separate then constant voltage DC has to be used for their power supply 2 NOTICE The power source must be sel...

Page 36: ...with RIS 150P EKO M M RIS 150P EKO3 1 PE 2 N 3 L 4 GND 5 0 10VDC IN 6 10VDC OUT STouch CON1 F F Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S KCO2 DSC G A3 F L N PE G 230VAC_24VDC 1 24VDC AC 2 24VA...

Page 37: ...elements and other components necessary for installation are not supplied M1 2 5kW 4A 2970min 1 PE N L 10V Tacho GND 0 10V PWM F F F STouch CON1 1 24VDC AC 2 24VAC DC 3 GND 4 RS465 B 5 RS485 A 6 GND...

Page 38: ...Controller allows easy setting of sound temperature sleep mode and CO2 level parameters from the user menu Fast button for setting maximum speed Numerical display of set and supply air temperature Sel...

Page 39: ...Temperature is adjusted by touching elements B4 and B6 B4 B6 L4 L7 Change value of se lected setting Increase by touching B4 decrease by touching B6 Numbers change in the segment display L4 L5 L6 L7 s...

Page 40: ...devices select CUSTOM in menu item F 20 and device addresses in menu items from F 22 up to F 37 If devices have no such addresses in fields of given menu items enter 00 00 Normally this controller is...

Page 41: ...The air quality converters and remote controller when fan is controlled must be powered from a separate power source It is not supplied with the remote CONTROLLER slave FAN 0 10 VDC MODBUS 4 Pressure...

Page 42: ...roller Service menu To enter service menu 1 Go to Off state if controller is on press down element B1 for 3 seconds 2 Press down B1 and B2 for 3 seconds 3 Using elements B4 and B6 enter security code...

Page 43: ...ss 00 00 FF FF 00 00 F 27 Temperature address 00 00 FF FF 00 00 F 28 Alarm 1 address 00 00 FF FF 00 00 F 29 Alarm 2 address 00 00 FF FF 00 00 F 30 Alarm 3 address 00 00 FF FF 00 00 F 31 Alarm 4 addres...

Page 44: ...register and return to the service menu Name Possible values Type Address HEX Address DEC Fan control 0 0 100 1 Fixed speeds 2 Based on fixed pressures Holding register 0x01 1 Switch of locking 0 Not...

Page 45: ...CO2 address 00 00 FF FF Holding register 0x1A 26 Temperature address 00 00 FF FF Holding register 0x1B 27 Alarm 1 address 00 00 FF FF Holding register 0x1E 28 Alarm 2 address 00 00 FF FF Holding regis...

Page 46: ...nt fan speed 0 100 Input register 0x01 1 Current fixed fan speed 0 4 Input register 0x02 2 Temperature Setpoint 150 350 C 10 Input register 0x03 3 Current Temperature 500 1000 10 Input register 0x04 4...

Page 47: ...r A 09 Ambient air temperature sensor fault Alarms ECO automation alarms Indication Meaning see device technical manual for alarm description A 01 Heat exchanger antifreeze protection activated A 02 F...

Page 48: ...enung durch einen Druck Leichte Reinigung Zahlenabbildung auf dem Bildschirm Akustische Antwort auf die Ber hrung Kann an BMS Netz angeschlossen werden Kann direkt an Ventilator der durch 0 10VDC Sign...

Page 49: ...rtanschluss des Kabels Montage 2 2 spezieller Anschluss s 8 Kontakten Anschluss 3 Das Pult der um 25 nach links gedreht ist anh ngen 4 5 Das Pult nach rechts drehen bis er sich an die Oberfl che dr ck...

Page 50: ...G Wenn Bedienteil am Bedienteil Luftqualit tssensor angeschlossen ist bei dem Speisung und Analog Ausgang GND elektrisch nicht getrennt sind f r die Speisung muss perma nente Spannung DC angeschlossen...

Page 51: ...GND 5 0 10VDC IN 6 10VDC OUT STouch CON1 F F Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S KCO2 DSC G A3 F L N PE G 230VAC_24VDC 1 24VDC AC 2 24VAC DC 3 GND 4 RS465 B 5 RS485 A 6 GND 7 0 10VDC IN 8...

Page 52: ...PWM F F F STouch CON1 1 24VDC AC 2 24VAC DC 3 GND 4 RS465 B 5 RS485 A 6 GND 7 0 10VDC IN 8 0 10VDC OUT Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S KCO2 DSC G A4 N L PE G 230VAC_24VDC ANMERKUNG Net...

Page 53: ...er aktiven St rungen in Symbolen A 01 A 02 usw sowie LED Anzeige Ruhezustand des Pults f r das Energiesparen Ist eine Blockierung der Ausschaltung vom L ftungssystem m glich Absicherung gegen Kinder v...

Page 54: ...n mit Hilfe von B4 und B6 Elementen ausgef hrt werden nach Annullierung der St rung kehrt der Pult in den Anfangszu stand ANMERKUNG Die St rung ohne Beheben von Fehler zu anulieren ist strengstens ver...

Page 55: ...Mit diesem Pult k nnen andere Ger te die durch MODBUS Protokoll bedient werden gesteuert werden Das wird im Servicemen durch Angabe von n tigen Parametern in Punkten F 17 F 18 F 19 F 20 F 21 des Serv...

Page 56: ...hlen falls die Bedienung laut eingestellten Geschwindigkeitswerten gew hlt ist diese angeben Men punkte F 03 F 04 F 05 F 06 PULT slave VENTILATOR 0 10 VDC MODBUS 4 Druckbehalten das mit dem Pult und...

Page 57: ...cemen Zum Aufruf des Servicemen s 1 in den Zustand Ausgeschaltet umschalten wenn das Pult eingeschaltet ist Element B1 f r 3 Sekunden gedr ckt halten 2 B1 und B2 f r 3 Sekunden gedr ckt halten 3 Siche...

Page 58: ...0 00 FF FF 00 00 F 25 SET Pressure address 00 00 FF FF 00 00 F 26 SET CO2 address 00 00 FF FF 00 00 F 27 Temperature address 00 00 FF FF 00 00 F 28 Alarm 1 address 00 00 FF FF 00 00 F 29 Alarm 2 addre...

Page 59: ...register 0x07 7 2 Geschwindigkeit Pa 0 999 Holding register 0x08 8 3 Geschwindigkeit Pa 0 999 Holding register 0x09 9 4 Geschwindigkeit boost Pa 0 999 Holding register 0x0A 10 PID P des Drucks 0 999...

Page 60: ...egister 0x17 23 SET Fan speed fixed address 00 00 FF FF Holding register 0x18 24 SET Pressure address 00 00 FF FF Holding register 0x19 25 SET CO2 address 00 00 FF FF Holding register 0x1A 26 Temperat...

Page 61: ...ungen speichern 0 Nein 22 Ja Holding register 0x36 49 Current fan speed 0 100 Input register 0x01 1 Current fixed fan speed 0 4 Input register 0x02 2 Temperature Setpoint 150 350 C 10 Input register 0...

Page 62: ...emperaturf hlers f r R ckwasser A 09 Au enttemperaturf hler defekt St rungen St rungen der ECO Automatik Anzeigen Bedeutung Beschreibung der St rung s im technischen Handbuch des Ger ts A 01 Frostschu...

Page 63: ...DE 63 S touch www salda lt Anzeigen Bedeutung A 01 A 02 A 03 A 04 A 05 A 06 A 07 A 08 A 09 A 10 St rung der CUSTOM Automatik nach Einstellung der Adressen vom CUSTOM Modbus beif gen...

Page 64: ...Facile utiliser Destin pour montage en applique Commande tactile par un seul appui Nettoyage facile R ponse sonore un appui Possibilit de brancher sur le r seau GTB Possibilit du branchement direct a...

Page 65: ...Installation 2 2 fiche sp cifique Cf Fiche 8 contacts 3 Accrocher le bo tier en le tenant tourn 25 vers la gauche 4 5 Tourner le bo tier droite jusqu ce qu il se colle contre le mur Retirer le mod le...

Page 66: ...fectu que par un lectricien qualifi conform ment aux exigences internationales et nationales en vigueur en mati re de s curit en milieu lectrique et de montage des installa tions et des quipements lec...

Page 67: ...0 10V PWM F F F STouch CON1 1 24VDC AC 2 24VAC DC 3 GND 4 RS465 B 5 RS485 A 6 GND 7 0 10VDC IN 8 0 10VDC OUT Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S KCO2 DSC G A4 N L PE G 230VAC_24VDC 2 Lors...

Page 68: ...2 transsmiter S KCO2 DSC G A3 F L N PE G 230VAC_24VDC 1 24VDC AC 2 24VAC DC 3 GND 4 RS465 B 5 RS485 A 6 GND 7 0 10VDC IN 8 0 10VDC OUT 3 Lorsque le bo tier est utilis avec les ventilateurs de la gamme...

Page 69: ...isateur du bo tier est con u pour le r glage facile des param tres de la temp rature du r gime de veille et du niveau de CO2 Touche rapide d activation de la vitesse maximale Affichage des valeurs en...

Page 70: ...n seg mentaire La liste des pannes peut tre contr l e l aide des l ments B4 et B6 Apr s annulation de la panne le bo tier revient en position initiale NOTE Il est formellement interdit d annuler la pa...

Page 71: ...olume 0 coup 1 1 9 timbre du son 2 P 03 Affichage temp rature de l air souffl 0 Non affich e 1 Affichage alternatif avec celle de con signe 0 P 04 CO2 requise 0 99 x10ppm 20 x10 P 05 D passement CO2 t...

Page 72: ...des vitesses pr d finies indiquer ces vitesses dans les points du menu F 03 F 04 F05 F 06 BO TIER slave VENT 0 10 VDC MODBUS 4 Maintien de la pression r gl e l aide du bo tier ou de l ordinateur au m...

Page 73: ...s une alimentation s par e Ils ne sont pas fournis avec le bo tier Menu service Pour acc der au menu service il est n cessaire de 1 Mettre le bo tier au r gime Arr t si le bo tier est allum appuyer 3...

Page 74: ...0 F 27 Temperature address 00 00 FF FF 00 00 F 28 Alarm 1 address 00 00 FF FF 00 00 F 29 Alarm 2 address 00 00 FF FF 00 00 F 30 Alarm 3 address 00 00 FF FF 00 00 F 31 Alarm 4 address 00 00 FF FF 00 00...

Page 75: ...s touches B2 et B3 s lectionner les bytes HIGH ou LOW dont l affichage est respectivement H 00 et L 00 Libell Valeurs ventuelles Type Adresse HEX Adresse DEC Commande des ventilateurs 0 0 100 1 Vitess...

Page 76: ...x18 24 SET Pressure address 00 00 FF FF Holding register 0x19 25 SET CO2 address 00 00 FF FF Holding register 0x1A 26 Temperature address 00 00 FF FF Holding register 0x1B 27 Alarm 1 address 00 00 FF...

Page 77: ...i Holding register 0x36 49 Current fan speed 0 100 Input register 0x01 1 Current fixed fan speed 0 4 Input register 0x02 2 Temperature Setpoint 150 350 C 10 Input register 0x03 3 Current Temperature 5...

Page 78: ...e l changeur de chaleur activ e A 02 D clenchement de la protection ext rieure par exemple entr e anti incendie filtres en crass s relai de pression activ ventilateurs A 03 Temp rature critique de l e...

Page 79: ...79 S touch Gr imo vieta gr to diametras 5mm 5 Drilling place drill diameter 5mm Bohrung Platz bohrer 5 mm Endroit pour percer diam tre de 5 mm...

Reviews: