DE |
33
SMARTY XV v2019.06
• Service -> Heaters -> Supply air heater or Fresh air pre-heater
Set whether it is a heater or pre-heater as well as the type of the heater or pre-heater and actions to be performed in case of the activation of a
danger signal.
Settings with the FLEX MCB control panel
1. Go to Menu/Service/Heaters. Enter the password (the initial password – 4444);
2. Select Control Position in the settings “Heater on basic” or “Pre-heater on basic”.
3. Go to Menu/Service/Heaters/Heater Set type “E010” 0-10 control, EONOFF On/Off control, NONE – heater switch-off, and also specify the
system’s response to danger.
4. Go to Menu/Service/Heaters/Preheater. Set type “E010” 0-10 control, EONOFF On/Off control, NONE – heater, pre-heater switch-off. Set the
system’s response to danger.
5. Go to Menu/Service/Digital inputs/Heater protection. Set the manual and automated protection statuses – according to the standards, it should
be NC.
6. Go to Menu/Service/Digital inputs/Preheater protection. Set the manual and automated protection statuses – as a standard, it should be NC.
When using the supply air heater, the supply air sensor (SS) shall be installed downstream the heater (or cooler) as the sen-
sor cable allows or until the first branching, bend of the air transportation system.
EKA
TJ
21.10. CONNECTION OF SUPPLY AND EXTRACT AIR DAMPERS
Product Smarty XV all versions can be equipped with fresh air damper and extract air drives. They are controlled by 3-point.
Installation diagram.
See “Principle mounting diagram”
Wiring diagram.
Automation controller D zone. Upon activation of output X13:3 the dampers shall open, Upon activation of output X13:4 the dampers shall close.