8
Smarty 4X V
www.salda.lt
• Proceed to maintenance and repair after any rotation in the fan stopped.
• Clean the heat exchanger once a year.
• Firstly take out heat exchanger cassette carefully. Submerge it into a bath and wash with warm soapy water (do not use soda). Then rinse it with
weak hot water stream (too strong stream can fold the plates). Place back the heat exchanger only when it is completely dry.
Bypass damper and pre-heater are mounted on one block. The pre-heater shall be disconnected by removing X29 connector. The bypass damper
shall be disconnected by removing X25 .
X29
X25