44
Smarty 2X/3X V
www.salda.lt
C
Connector
Contactor No.
Contactor name
Functional block name
miniEX1
X23
1
DI1
Electric heater manual protection (NC)
2
12VDC
3
DI2
Electric heater automatic protection (NC)
4
12VDC
5
DI3
Filter relay/Fire place I, DI (NC)
6
12VDC
7
DI4
Filter relay/Fire place II, DI (NC)
8
12VDC
Fire protection signal input must be normally closed, until the fire protection system is not connected a jumper is installed in the factory.
Automation controller A zone X4.
In product versions 1.1 pre-heater is integrated inside the product. In product versions 1.2 and 1.3 pre-heater is
integrated on the outdoor air channel. Pre-heater is controlled by 0-10V signal.
Installation diagram.
Installation based on air direction Air Damper M2 -> Pre-Heater PE -> Recuperator.
Wiring diagram.
Automation controller A (X2) and D (X12) zones
1 2 3 4 5 6
DRAWN BY
CHECKED BY
SIGNATURE
DUTIES / NAME
DATE
UAB"SALDA"
Drawing #
Book #
APPROVED BY
1
2
3
4
5
6
7
8
9
10
External preheater
SP36
1
01
2015-11-27
2015-11-27
X2
:5
-
GN
D
X2
:6
-
AO
3(
0-
10
V)
-N1
miniMCB V0.3
X1
2:
1
- P
E
X1
2:
2
- N(
L1
)
X1
2:
3
- D
O2
(L
(L
2)
)
-N1
miniMCB V0.3
External preheater.
Control 0-10V
Power up to 2kW, 1f/230V
PE
N
L1
0-
10
V
GN
D
PE1
EKA NIS ... -1F
Max. 2kW/230V
X1
2:
1
- P
E
X1
2:
2
- N(
L1
)
X1
2:
3
- D
O2
(L
(L
2)
)
-N2
miniMCB V0.3
X2
:5
-
GN
D
X2
:6
-
AO
3(
0-
10
V)
-N2
miniMCB V0.3
External preheater.
Control 0-10V
Power over 2kW, 2f/400V
-K1
A1
A2
230VAC
11
14
-K1
PE
L1
L2
11
-G
ND
12
-0
-1
0V
-PE1
EKS NIS ... -2f
-K1
1
2
3
4
PE
L1
L2
KE
(EKA)
+
TA
PE
Ptouch
Stouch
*
TE**
Tinklas
KE*
(EKA)
TA
*
TE**
PE*
(EKA
NIS/
EKA)
KE*
(EKA)
TA
*
TE**
PE*
(EKA
NIS/
EKA)
AKS***
AKS***
AKS***
AKS***
AKS***
AKS***
*
*
*
MB-
Gateway
Ptouch
Stouch
Tinklas
MB-
Gateway
Ptouch
Stouch
Tinklas
MB-
Gateway