![Salda RIRS EKO 3.0 400 VEL Mounting And Installation Instruction Download Page 13](http://html1.mh-extra.com/html/salda/rirs-eko-3-0-400-vel/rirs-eko-3-0-400-vel_mounting-and-installation-instruction_3641554013.webp)
EN |
13
RIRS 400-700 V EKO 3.0 v2020.1
6. MAINTENANCE
6.1. SAFETY
INSTRUCTION
Unplug the unit from the mains before opening the door (disconnect the power plug from the outlet or in case a two-pole
automatic circuit breaker installed, disconnect it as well. Make sure that it cannot be turned on by third parties) and wait until
the fans completely stop (for about 2 min.).
6.2. GENERAL RECOMMENDATIONS FOR VENTILATION SYSTEM MAINTENANCE
,QRUGHUWRHQVXUHSURSHUIXQFWLRQLQJRIWKHV\VWHPPDLQWHQDQFHUHTXLUHPHQWVDQGLWVSHULRGVVKRXOGEHREVHUYHG2WKHUZLVHWKHZDUUDQW\VKDOO
EHYRLG6RPHUHFRPPHQGDWLRQVDUHSURYLGHGLQWKHWDEOHEHORZEXWWKH\DUHMXVWDGYLVRU\DVWKHQHHGIRUV\VWHPPDLQWHQDQFHGHSHQGVRQWKH
ORFDWLRQRIWKHXQLWLQVWDOODWLRQWKHSROOXWLRQRIDWPRVSKHUHSRSXODWLRQZRUNLQJKRXUVHWF
COMPONENT
DURING START-UP
AT LEAST EVERY 6 MONTHS
Filters
&KHFNWKHFOHDQOLQHVVRIWKH¿OWHUV
5HSODFH¿OWHUVHYHU\WRPRQWKVRUDFFRUGLQJWRWKH
control device indications.
Fans
Check the connections and the direction of rotation
Check cleanliness. Clean, if necessary
Make sure that the impellers are not unbalanced.
0DNHVXUHWKDWWKHLPSHOOHUVGRQRWFDXVHQRLVHZKHQ
rotated by hand.
0DNHVXUHWKDWWKHIDVWHQLQJVFUHZVDUHQRWORRVHDQG
free of mechanical damage.
Check electrical connections and make sure that these
are secured properly and are free of signs of corrosion.
Rotor heat exchanger
Check the cleanliness of the heat exchanger
Check cleanliness and clean, if necessary
Check the tension of a belt
Control panel
Check the connections
Check the connections
Electric heater
Check the connections
&OHDQRႇGXVWDQGFKHFNWKHHOHFWULFDOFRPSRQHQWVDQG
connections of the heater
Temperature sensor
Check electrical connections
Check the operation
Air supply and extract system
Check the connections
Clean
Air duct system
Check the tightness
Clean
'DPSHUVGLႇXVHUVJULG
Check the tightness of connections
Clean
6ZLWFKLQJXQLWFRQWDFWRU
Every 3 to 4 months, visually assess the functioning of
WKHVZLWFKLQJXQLWFRQWDFWRULHPDNHVXUHWKDWLWVFDV
-
ing has no signs of melting or is not thermally damaged
LQDQ\ZD\DQGGRHVQRWSURGXFHDQ\XQXVXDOVRXQGV
All the contactors in the product or in its accessories
must be checked.
6.3. COVER
OPENING
%HIRUHRSHQLQJWKHFRYHUV¿UVWXQSOXJWKHXQLWIURPWKHPDLQVWKHQZDLWIRUPLQXWHVXQWLOWKHIDQVFRPSOHWHO\VWRS