RIRS 1200-5500 H EKO 3.0 v2019.06

20 Motor2

04h_Read_Input

16

1

Motor2 fan speed value

0-3

Temperature sensor value 

real

 format (-3.3E38 - 3.3E38) example: 0h->0C, 7FFFh->3276.7C, 8000h->3276.8, FFFFh->-0.1C

21 Tlimit

04h_Read_Input

0

1

Supply air temperature value

Hex: E0

22 Texhaust

04h_Read_Input

1

1

DTJ(100) temperature sensor value

Hex: E0

23 Textract

04h_Read_Input

2

1

Exhaust air temperature sensor value

Hex: E0

24 ToutDoor

04h_Read_Input

3

1

Ouside air temperature sensor value

Hex: FFEC

25 Twater

04h_Read_Input

12

1

Return water temperature sensor value

Hex: FFEC

19.4.  ELECTRICAL CONNECTION OF THE HVAC UNIT

Electrical connection can only be implemented by the qualified electrician in accordance with the applicable international and national electrical 

safety requirements and requirements for installation of electrical devices.

Use only power source which meets the requirements specified on the device label.

Power supply cable should be selected based on the electrical specification of the device. If the device power supply line is far from the unit, the 

distance and voltage drop should be considered.

Device must be earthed.

Install the control panel at the designated place.

Install the supplied connection cable(FLEX controller) between the control panel and the HVAC unit. It is recommended to install the control panel 

separately from the power cables.

Note:

 If cable is used together with other power cables, shielded control panel cable with earthed shield should be used.

Connect the plug (RJ10 type) to the RS485-1 socket of the unit. Connect the other end to the control panel.

RS458_1 RS458_2

NOTE:

 The remote control panel can be connected and (or) disconnected only after disconnecting the power supply for the HVAC unit.

Switch on the mains voltage, switch on the blade switch Q, see 

Fig. 5

 (actual appearance of the blade switch can be different from the given photo 

based on the model of the product).

OFF

ON

Select the desired fan rotation speed and the supply air temperature using the remote controller.

19.5.  SYSTEM ADJUSTMENT GUIDELINES

X16

B

OOS

T

S

TA

RT

-NC

ST

O

P-

N

O

Jumper

CO2; Extract air pressure

Air quality transmitter

Supply air pressure

Transmitter 2

26 - 24V DC,

27 - intput, 0-10V DC,

28 - GND,

X16.10

28

27

P

26

27 28

26

24 25

23

CE7/7

27 28

26

24 25

23

X16.7

PE N L1

L1

N

PE

L1

N

PE

L1

N

PE

1f, 230V AC

   Power 

supply cable

valve actuator

Water cooler

1

3

2

X16.1

Y1 Y2 G

M5

24VAC, 3-position

Y1 - OPEN (24VAC)

Y2 - CLOSE (24VAC)

G - System potential 24VAC

1 2 3 4 5 6 7 8 9 10

10

9

8

7

6

5

4

3

2

1

Boost

Start/Stop

AHU status

AHU work

AHU stop

24V

D

C

24V

D

C

3

1

P

DX Cooling

X16.4

X16.4

X16.2

13 14

8

7

X16.3

AH

st

op

1.

2W

 m

ax

4 5 6

10

9

X16.4

1.

2W

 m

ax

AHU

 wo

rk

11 12

25

24

23 - 24V DC,

24 - intput, 0-10V DC,

25 - GND,

Transmitter 1

P

23

18 19 20 21 22

22

21

20

19

18

17

16

15

14

13

12

11

NTC

Supply air

TJ

temp.sensor

21 22

X16.6

11 12 13 14 15 16 17

N

L

19

X16.5

M2

M3

17 18

L

N

N L L

16

20

15

230V AC

230V AC

ON/OFF

ON/OFF

L c

ont

rol

N

L c

ont

rol

L

Supply air

Extract air

damper actuator

damper actuator

Fire alarm

input

Air quality transmitter

X16

X16

Air quality transmitter

Fire alarm

input

damper actuator damper actuator

Extract air

Supply air

L

L c

ont

rol

N

L c

ont

rol

ON/OFF

ON/OFF

230V AC

230V AC

15

20

16

L

L

N

N

L

18

17

M3

M2

X16.5

19

L

N

17

16

15

14

13

12

11

X16.6

22

21

temp.sensor

TJ

Supply air

NTC

11 12 13 14 15 16 17 18 19 20 21 22

22

21

20

19

18

23

P

Transmitter 1

23 - 24V DC,

24 - intput, 0-10V DC,

25 - GND,

24 25

12

11

AHU

 wo

rk

1.

2W

 m

ax

X16.4

9 10

6

5

4

1.

2W

 m

ax

AH

U s

to

p

X16.3

7 8

14

13

X16.2

X16.4

X16.4

DX Cooling

P

1
3

24V

D

C

24V

D

C

AHU stop

AHU work

AHU status

Start/Stop

Boost

1 2 3 4 5 6 7 8 9 10

10

9

8

7

6

5

4

3

2

1

Y1 - OPEN (24VAC)

Y2 - CLOSE (24VAC)

G - System potential 24VAC

24VAC, 3-position

M5

G

Y2

Y1

X16.1

2 3

1

Water cooler
valve actuator

supply cable

   Power 

1f, 230V AC

PE N L1

PE N L1

PE N L1

L1

N

PE

X16.7

23

25

24

26

28

27

CE7/7

23

25

24

26

28

27

26

P

27 28

X16.10

26 - 24V DC,

27 - intput, 0-10V DC,

28 - GND,

Transmitter 2

Supply air pressure

Air quality transmitter

CO2; Extract air pressure

Jumper

ST

O

P-

N

O

S

TA

RT

-NC

B

OOS

T

X16

X16

Air quality transmitter

Fire alarm

input

damper actuator damper actuator

Extract air

Supply air

L

L c

ont

rol

N

L c

ont

rol

ON/OFF

ON/OFF

230V AC

230V AC

15

20

16

L

L

N

N

L

18

17

M3

M2

X16.5

19

L

N

17

16

15

14

13

12

11

X16.6

22

21

temp.sensor

TJ

Supply air

NTC

11 12 13 14 15 16 17 18 19 20 21 22

22

21

20

19

18

23

P

Transmitter 1

23 - 24V DC,

24 - intput, 0-10V DC,

25 - GND,

24 25

12

11

AHU

 wo

rk

1.

2W

 m

ax

X16.4

9 10

6

5

4

1.

2W

 m

ax

AH

U s

to

p

X16.3

7 8

14

13

X16.2

X16.4

X16.4

DX Cooling

P

1
3

24V

D

C

24V

D

C

AHU stop

AHU work

AHU status

Start/Stop

Boost

1 2 3 4 5 6 7 8 9 10

10

9

8

7

6

5

4

3

2

1

Y1 - OPEN (24VAC)

Y2 - CLOSE (24VAC)

G - System potential 24VAC

24VAC, 3-position

M5

G

Y2

Y1

X16.1

2 3

1

Water cooler
valve actuator

supply cable

   Power 

1f, 230V AC

PE N L1

PE N L1

PE N L1

L1

N

PE

X16.7

23

25

24

26

28

27

CE7/7

23

25

24

26

28

27

26

P

27 28

X16.10

26 - 24V DC,

27 - intput, 0-10V DC,

28 - GND,

Transmitter 2

Supply air pressure

Air quality transmitter

CO2; Extract air pressure

Jumper

ST

O

P-

N

O

S

TA

RT

-NC

B

OOS

T

X16

1_789.0046A.0.1.2-L-0k

1_789.0046A.0.1.2-L-0k

1_789.0046A.0.1.2-L-0k

FA

NC

Jumper

FA

NC

Jumper

FA

NC

Jumper

Figure 19.5.1. RIRS 1200-1900 HE EKO 3.0 

Summary of Contents for RIRS EKO 3.0 1900 HE

Page 1: ...RIRS 1200 5500 H EKO 3 0 EN MOUNTING AND INSTALLATION INSTRUCTION...

Page 2: ...RS 11 18 2 FAN 11 18 3 HEAT EXCHANGER 12 18 4 ELECTRICAL HEATER 13 19 AUTOMATIC CONTROL 13 19 1 SYSTEM PROTECTION 14 19 2 USING THE UNIT IN BMS NETWORK 14 19 3 MODBUS ADRESSES 15 19 4 ELECTRICAL CONNE...

Page 3: ...quency Max current Max power consumption Protection class Weight xxx xx VAC Hz x xx A x xx kW IP xx xx kg Made in iauliai Lithuania AHU000000 BN xxxxxx 2019 01 01 SERIAL 2514523357 XXX GAMINIO PAVADIN...

Page 4: ...da Antifrost system uses dis balancing of the air flow and it may cause negative pressure in premises Great care should be taken when using at the same time in premises as another heating appliance wh...

Page 5: ...715 3 1 0 715 3 1 1 3 6 4 1 3 6 4 speed min 1 2800 2800 2390 2390 supply power current kW A 0 715 3 1 0 715 3 1 1 31 6 4 1 3 6 4 speed min 1 2800 2800 2390 2390 control input VDC 0 10 0 10 0 10 0 10...

Page 6: ...r 6 Control board 7 Extract air filters panel pocket 8 Supply air filter panel pocket 9 Rotor engine 7 OPERATING CONDITIONS 5 C o 40 C o 40 C o 40 C o 15 C o 40 C o 3 C o 40 C o 5 C o 40 C o 23 C o 40...

Page 7: ...he unit first unpack the accessories Remove the film from the unit Remove the bracing packaging tape which keeps the protective profiles Remove the protective profiles After unpacking the unit examine...

Page 8: ...CE REQUIREMENTS L 1 5xL L 1 5xL H Min distance to open the door 1 5xL Min distance to open control box door H 400 mm 13 MOUNTING The protective film is intended to protect the unit during transportati...

Page 9: ...CTION OF THE AIR DUCT Figure 14 1 Circular air duct conection Figure 14 2 Rectangular air duct conection 15 CONNECTION DIAGRAM PS PS PS PS PS 2 2 2 2 2 Figure 15 1 RIRS 1200 1900 HE EKO 3 0 Placement...

Page 10: ...ostat KV2 Water pre heater TV2 Water preheater temperature sensor KV3 Water cooler TV3 Water cooler temperature sensor DX DX cooler U3 PV pressure transmitter M1 By pass damper U4 IV pressure transmit...

Page 11: ...power connection diagrams all electrical equipment protection elements are properly connected if they are additionally used cables and wires correspond to all applicable safety and functional requirem...

Page 12: ...cause disbalance of impeller or damage it Hold the fan by the casing Figure 18 1 RIRS 1200 1900 H EKO 3 0 Figure 18 2 RIRS 2500 5500 H EKO 3 0 18 3 HEAT EXCHANGER Be sure the unit is disconnected from...

Page 13: ...by the ESKM controller using the PWM signal If the water supply air heater is used then the actuator is controlled using RG1 controller with analogous 0 10V DC signal BOOST feature Fans are started a...

Page 14: ...pes of the capillary thermal protections are used for the overheat protection of the electrical heater manual and automatic Automatic thermal protection is activated when air temperature exceeds 50 C...

Page 15: ...Supply air temperature sensor alarm 1 a c t i v e o passive 9 RH 01h_Read_Coils 9 1 TJ 100 humidity sensor alarm controller works in deter mining the moisture content of 70 1 a c t i v e o passive 10...

Page 16: ...should be used Connect the plug RJ10 type to the RS485 1 socket of the unit Connect the other end to the control panel RS458_1 RS458_2 NOTE The remote control panel can be connected and or disconnecte...

Page 17: ...24VAC G System potential 24VAC 24VAC 3 position M5 G Y2 Y1 Water cooler valve actuator Jumper STOP NO START NC BOOST CE7 7 X16 7 PE N L1 L1 N PE L1 N PE L1 N PE 1f 230V AC Power supply cable X16 36 36...

Page 18: ...a LED2 Air damper close LED9 Medium fans speed LED2 LED3 Air damper open LED10 Minimal fans speed LED4 Water valve open LED11 Supply air fan speed reducing LED5 Water valve close LED12 Preheater LED6...

Page 19: ...19 06 20 1 LABELING CHARACTERISTICS OF THE CONTROLLER AND THE SYSTEM COMPONENTS Contact No Labeling Description I O type Max load Min load A mA X10 L 230V 50Hz power supply I X8 N 230V 50Hz power supp...

Page 20: ...AO X33 5 VAL Cooling valve common Pulse 24v 50hz AO M1 By pass actuator X33 6 DMP Bypass damper opening PWM 24v 50hz AO 100mA X33 7 DMP By Pass damper closing PWM 24v 50hz AO 100mA X33 8 DMP By Pass d...

Page 21: ...1 2 COM PV Supply air fan X37 1 V1 Supply air fan 0 10V AO X37 2 COM COM IV Extract room s air fan X37 3 V2 Extract air fan 0 10V AO X37 4 COM COM 20 2 REGULAR SYSTEM CHECK UP The operation of the swi...

Page 22: ...3 2 CHIL X33 9 COM X33 10 BOOST STOP NO START NC A2 A1 R1 8 7 X16 3 ALARM X33 11 COM ANTI F Fan fall 1 2W max 4 5 6 10 9 X16 4 24 1 2W max Fan run 11 12 COM FAN 25 24 23 24V DC 24 intput 0 10V DC 25 G...

Page 23: ...A1 R1 8 7 X16 3 ALARM X33 11 COM ANTI F Fan fall 1 2W max 4 5 6 10 9 X16 4 24 1 2W max Fan run 11 12 COM FAN 25 24 23 24V DC 24 intput 0 10V DC 25 GND Transmitter 1 24 VDC U P 23 X29 X25 N L 3 1 P DX...

Page 24: ...230V AC 230V AC ON OFF ON OFF L X37 TL LOW X32 1 COM X32 4 HIGH X32 2 TIMER X32 3 COM X33 1 MIDL X33 2 CHIL X33 9 COM X33 10 BOOST STOP NO START NC A2 A1 R1 8 7 X16 3 ALARM X33 11 COM ANTI F Fan fall...

Page 25: ...1 FA 13 14 16 15 X16 6 TL LOW X32 1 COM X32 4 HIGH X32 2 TIMER X32 3 COM X33 1 MIDL X33 2 CHIL X33 9 COM X33 10 BOOST STOP NO START NC A2 A1 R1 8 7 X16 3 ALARM X33 11 COM ANTI F Fan fall 1 2W max 4 5...

Page 26: ...JK 10K TJ tiekiamo oro temperat ros jutiklis TJK 10K TE i metamo oro jutiklis TJK 10K DTJ100 i traukiamo oro temperat ros santykin s oro dr gm s jutiklis keitiklis PV tiekiamo oro ventiliatorius EC IV...

Page 27: ...S 0K Automatic connection s principal scheme 1 01 2019 06 04 2019 06 04 5 5 110 N L KE2 PE PE1 15 15 1 10 2 9 X21 87 127 Q3 B 16 7 W5 White 14 W5 Red 14 W5 Red AT3 12 R2 A1 A2 11 14 R2 17 17 16 16 87...

Page 28: ...28 EN RIRS 1200 5500 H EKO 3 0 v2019 06 21 7 RIRS 3500 HW EKO 3 0...

Page 29: ...s Green alias White balta Yellow Orange geltonas oran inis Blue Black Grey m lynas juodas pilkas Gray pilkas Red raudonas ym jimas Feston PKC Pin MTA2 Jungties lizdas Jungties ki tukas Kabelis su dvie...

Page 30: ...500HW V2 4 RHX 0k principin schema UAB SALDA Lap M stelis Svoris Lapas Raid Data Para as Dok Nr Lapas Pak Pareng Tikrino Tikrino X42 1 2 3 4 5 7 6 8 9 10 11 12 14 13 15 Spalvinis ym jimas Yellow Green...

Page 31: ...1 0 White White White White K Grik as TJ Supply air temperature sensor TV 1 4 T1 Water heater antifreeze thermostat Water heater antifreeze return heat carrier temperature sensor Lap M stelis Svoris L...

Page 32: ...WH BK RD GN BU RG3 TK TK PWM 0 A1 A2 X04 YE WH BK RD 1 2 X22 1 2 1 3x400V B25 X16 10 1 2 F1 6 3A A1 A2 A1 A2 A2 A1 5 6 7 L1 N 9 10 X21 3 C 0 AT3 KE2 50w M3 N 1 L 2 L 3 230V AC N L control X46 N 1 L 2...

Page 33: ...ition Y2 Y1 VAL VAL VAL X33 3 X33 4 X33 5 3 1 2 X16 1 Y1 Control OPEN AC 24 V Y2 Control CLOSE AC 24 V G System potential AC 24 V X35 2 X35 1 X33 13 X33 14 X33 18 X33 12 X33 17 X33 25 X33 26 X34 1 X34...

Page 34: ...www salda lt RIRS EKO 3 0 2500 HE 2500 HW 3500 HE 3500 HW 5500 HE 5500 HW Declared typology bidirectional bidirectional bidirectional bidirectional bidirectional bidirectional Type of drive Variable...

Page 35: ...sk reduction LST EN 60204 1 2006 Safety of machinery Electrical equipment of machines Part 1 General requirements LST EN 60335 1 2012 Household and similar electrical appliances Safety Part 1 General...

Page 36: ...iver the equipment to manufacturer Delivery costs should be covered by customer Manufacturer reserves the right to change this technical passport any time without prior notice if some typographic erro...

Page 37: ...37 RIRS 1200 5500 H EKO 3 0 v2019 06...

Page 38: ...38 RIRS 1200 5500 H EKO 3 0 v2019 06...

Page 39: ...39 RIRS 1200 5500 H EKO 3 0 v2019 06...

Page 40: ...NANCE TABLE Product name LOT number Instalation Interval Datum Fan cleaning Once a year Heat exchanger cleaning Once a year Filter replacement Every 3 4 months Look at the product label At least NOTE...

Reviews: