- The motor is of heavy duty ball bearing construction. The motor is completely sealed and requires no lubrication for the life of the motor.

- Detach fan from the unit.

- Impeller should be specially checked for buil-up material or dirt which may cause an imbalance.  Excessive imbalance can lead to accelerated 

wear on motor bearings and vibration.

- Clean impeller and inside housing with mild detergent, water and damp, soft cloth.

- Do not use high pressure cleaner, abrasives, sharp instruments or caustic solvents that may scratch or damage housing and impeller.

- Do not plunge impeller into any fluid.

- Make sure, that impeller’s balance weights are not moved.

- Make sure the impeller is not hindered.

- Mount the fan back into the unit. Replace fan guards and connect the fan to power supply source.

- If after maintenance or repair the fan does not start either thermal protection contact activates automatically, contact the manufacturer.

- During the maintenance do not hold the fan by the impeller, it might cause disbalance of impeller or damage it. Hold the fan by the casing.

Figure. 18.1. 

RIRS 1200-1900 H EKO 3.0

Figure. 18.2. 

RIRS 2500-5500 H EKO 3.0

18.3.  HEAT EXCHANGER

• Be sure the unit is disconnected from power source before performing any maintenance or repair.

• Proceed to maintenance and repair after any rotation in the fan stopped.

• Clean it once a year.

• The maintenance works for the rotor heat exchanger shall be carried out once a year.

• Ensure that the gaps of the heat exchanger are not contaminated, the seal brushes are not worn, the belt drive is not worn and the clamp as-

semblies are tight.

• The rotor heat exchanger can be easily removed from the unit by disconnecting the power supply cable of the heat exchanger motor (Pic. 1-2).

• The heat exchanger is cleaned using the solution of warm water and non-corrosive toward aluminum alkaline agent or the air stream. It is not 

recommended to apply direct stream of liquid as it can harm the heat exchanger.

• It is 

NECESSARY

 to protect the motor of the heat exchanger from the moisture and liquid while cleaning the heat exchanger.

• CAUTION!

 It is forbidden to use the heat exchanger if the fi lters are removed!

Figure. 18.1. 

RIRS 1200-1900 H EKO 3.0

Figure. 18.2. 

RIRS 2500-5500 H EKO 3.0

Summary of Contents for RIRS EKO 3.0 1900 HE

Page 1: ...RIRS 1200 5500 H EKO 3 0 EN MOUNTING AND INSTALLATION INSTRUCTION...

Page 2: ...RS 11 18 2 FAN 11 18 3 HEAT EXCHANGER 12 18 4 ELECTRICAL HEATER 13 19 AUTOMATIC CONTROL 13 19 1 SYSTEM PROTECTION 14 19 2 USING THE UNIT IN BMS NETWORK 14 19 3 MODBUS ADRESSES 15 19 4 ELECTRICAL CONNE...

Page 3: ...quency Max current Max power consumption Protection class Weight xxx xx VAC Hz x xx A x xx kW IP xx xx kg Made in iauliai Lithuania AHU000000 BN xxxxxx 2019 01 01 SERIAL 2514523357 XXX GAMINIO PAVADIN...

Page 4: ...da Antifrost system uses dis balancing of the air flow and it may cause negative pressure in premises Great care should be taken when using at the same time in premises as another heating appliance wh...

Page 5: ...715 3 1 0 715 3 1 1 3 6 4 1 3 6 4 speed min 1 2800 2800 2390 2390 supply power current kW A 0 715 3 1 0 715 3 1 1 31 6 4 1 3 6 4 speed min 1 2800 2800 2390 2390 control input VDC 0 10 0 10 0 10 0 10...

Page 6: ...r 6 Control board 7 Extract air filters panel pocket 8 Supply air filter panel pocket 9 Rotor engine 7 OPERATING CONDITIONS 5 C o 40 C o 40 C o 40 C o 15 C o 40 C o 3 C o 40 C o 5 C o 40 C o 23 C o 40...

Page 7: ...he unit first unpack the accessories Remove the film from the unit Remove the bracing packaging tape which keeps the protective profiles Remove the protective profiles After unpacking the unit examine...

Page 8: ...CE REQUIREMENTS L 1 5xL L 1 5xL H Min distance to open the door 1 5xL Min distance to open control box door H 400 mm 13 MOUNTING The protective film is intended to protect the unit during transportati...

Page 9: ...CTION OF THE AIR DUCT Figure 14 1 Circular air duct conection Figure 14 2 Rectangular air duct conection 15 CONNECTION DIAGRAM PS PS PS PS PS 2 2 2 2 2 Figure 15 1 RIRS 1200 1900 HE EKO 3 0 Placement...

Page 10: ...ostat KV2 Water pre heater TV2 Water preheater temperature sensor KV3 Water cooler TV3 Water cooler temperature sensor DX DX cooler U3 PV pressure transmitter M1 By pass damper U4 IV pressure transmit...

Page 11: ...power connection diagrams all electrical equipment protection elements are properly connected if they are additionally used cables and wires correspond to all applicable safety and functional requirem...

Page 12: ...cause disbalance of impeller or damage it Hold the fan by the casing Figure 18 1 RIRS 1200 1900 H EKO 3 0 Figure 18 2 RIRS 2500 5500 H EKO 3 0 18 3 HEAT EXCHANGER Be sure the unit is disconnected from...

Page 13: ...by the ESKM controller using the PWM signal If the water supply air heater is used then the actuator is controlled using RG1 controller with analogous 0 10V DC signal BOOST feature Fans are started a...

Page 14: ...pes of the capillary thermal protections are used for the overheat protection of the electrical heater manual and automatic Automatic thermal protection is activated when air temperature exceeds 50 C...

Page 15: ...Supply air temperature sensor alarm 1 a c t i v e o passive 9 RH 01h_Read_Coils 9 1 TJ 100 humidity sensor alarm controller works in deter mining the moisture content of 70 1 a c t i v e o passive 10...

Page 16: ...should be used Connect the plug RJ10 type to the RS485 1 socket of the unit Connect the other end to the control panel RS458_1 RS458_2 NOTE The remote control panel can be connected and or disconnecte...

Page 17: ...24VAC G System potential 24VAC 24VAC 3 position M5 G Y2 Y1 Water cooler valve actuator Jumper STOP NO START NC BOOST CE7 7 X16 7 PE N L1 L1 N PE L1 N PE L1 N PE 1f 230V AC Power supply cable X16 36 36...

Page 18: ...a LED2 Air damper close LED9 Medium fans speed LED2 LED3 Air damper open LED10 Minimal fans speed LED4 Water valve open LED11 Supply air fan speed reducing LED5 Water valve close LED12 Preheater LED6...

Page 19: ...19 06 20 1 LABELING CHARACTERISTICS OF THE CONTROLLER AND THE SYSTEM COMPONENTS Contact No Labeling Description I O type Max load Min load A mA X10 L 230V 50Hz power supply I X8 N 230V 50Hz power supp...

Page 20: ...AO X33 5 VAL Cooling valve common Pulse 24v 50hz AO M1 By pass actuator X33 6 DMP Bypass damper opening PWM 24v 50hz AO 100mA X33 7 DMP By Pass damper closing PWM 24v 50hz AO 100mA X33 8 DMP By Pass d...

Page 21: ...1 2 COM PV Supply air fan X37 1 V1 Supply air fan 0 10V AO X37 2 COM COM IV Extract room s air fan X37 3 V2 Extract air fan 0 10V AO X37 4 COM COM 20 2 REGULAR SYSTEM CHECK UP The operation of the swi...

Page 22: ...3 2 CHIL X33 9 COM X33 10 BOOST STOP NO START NC A2 A1 R1 8 7 X16 3 ALARM X33 11 COM ANTI F Fan fall 1 2W max 4 5 6 10 9 X16 4 24 1 2W max Fan run 11 12 COM FAN 25 24 23 24V DC 24 intput 0 10V DC 25 G...

Page 23: ...A1 R1 8 7 X16 3 ALARM X33 11 COM ANTI F Fan fall 1 2W max 4 5 6 10 9 X16 4 24 1 2W max Fan run 11 12 COM FAN 25 24 23 24V DC 24 intput 0 10V DC 25 GND Transmitter 1 24 VDC U P 23 X29 X25 N L 3 1 P DX...

Page 24: ...230V AC 230V AC ON OFF ON OFF L X37 TL LOW X32 1 COM X32 4 HIGH X32 2 TIMER X32 3 COM X33 1 MIDL X33 2 CHIL X33 9 COM X33 10 BOOST STOP NO START NC A2 A1 R1 8 7 X16 3 ALARM X33 11 COM ANTI F Fan fall...

Page 25: ...1 FA 13 14 16 15 X16 6 TL LOW X32 1 COM X32 4 HIGH X32 2 TIMER X32 3 COM X33 1 MIDL X33 2 CHIL X33 9 COM X33 10 BOOST STOP NO START NC A2 A1 R1 8 7 X16 3 ALARM X33 11 COM ANTI F Fan fall 1 2W max 4 5...

Page 26: ...JK 10K TJ tiekiamo oro temperat ros jutiklis TJK 10K TE i metamo oro jutiklis TJK 10K DTJ100 i traukiamo oro temperat ros santykin s oro dr gm s jutiklis keitiklis PV tiekiamo oro ventiliatorius EC IV...

Page 27: ...S 0K Automatic connection s principal scheme 1 01 2019 06 04 2019 06 04 5 5 110 N L KE2 PE PE1 15 15 1 10 2 9 X21 87 127 Q3 B 16 7 W5 White 14 W5 Red 14 W5 Red AT3 12 R2 A1 A2 11 14 R2 17 17 16 16 87...

Page 28: ...28 EN RIRS 1200 5500 H EKO 3 0 v2019 06 21 7 RIRS 3500 HW EKO 3 0...

Page 29: ...s Green alias White balta Yellow Orange geltonas oran inis Blue Black Grey m lynas juodas pilkas Gray pilkas Red raudonas ym jimas Feston PKC Pin MTA2 Jungties lizdas Jungties ki tukas Kabelis su dvie...

Page 30: ...500HW V2 4 RHX 0k principin schema UAB SALDA Lap M stelis Svoris Lapas Raid Data Para as Dok Nr Lapas Pak Pareng Tikrino Tikrino X42 1 2 3 4 5 7 6 8 9 10 11 12 14 13 15 Spalvinis ym jimas Yellow Green...

Page 31: ...1 0 White White White White K Grik as TJ Supply air temperature sensor TV 1 4 T1 Water heater antifreeze thermostat Water heater antifreeze return heat carrier temperature sensor Lap M stelis Svoris L...

Page 32: ...WH BK RD GN BU RG3 TK TK PWM 0 A1 A2 X04 YE WH BK RD 1 2 X22 1 2 1 3x400V B25 X16 10 1 2 F1 6 3A A1 A2 A1 A2 A2 A1 5 6 7 L1 N 9 10 X21 3 C 0 AT3 KE2 50w M3 N 1 L 2 L 3 230V AC N L control X46 N 1 L 2...

Page 33: ...ition Y2 Y1 VAL VAL VAL X33 3 X33 4 X33 5 3 1 2 X16 1 Y1 Control OPEN AC 24 V Y2 Control CLOSE AC 24 V G System potential AC 24 V X35 2 X35 1 X33 13 X33 14 X33 18 X33 12 X33 17 X33 25 X33 26 X34 1 X34...

Page 34: ...www salda lt RIRS EKO 3 0 2500 HE 2500 HW 3500 HE 3500 HW 5500 HE 5500 HW Declared typology bidirectional bidirectional bidirectional bidirectional bidirectional bidirectional Type of drive Variable...

Page 35: ...sk reduction LST EN 60204 1 2006 Safety of machinery Electrical equipment of machines Part 1 General requirements LST EN 60335 1 2012 Household and similar electrical appliances Safety Part 1 General...

Page 36: ...iver the equipment to manufacturer Delivery costs should be covered by customer Manufacturer reserves the right to change this technical passport any time without prior notice if some typographic erro...

Page 37: ...37 RIRS 1200 5500 H EKO 3 0 v2019 06...

Page 38: ...38 RIRS 1200 5500 H EKO 3 0 v2019 06...

Page 39: ...39 RIRS 1200 5500 H EKO 3 0 v2019 06...

Page 40: ...NANCE TABLE Product name LOT number Instalation Interval Datum Fan cleaning Once a year Heat exchanger cleaning Once a year Filter replacement Every 3 4 months Look at the product label At least NOTE...

Reviews: