13. Specific installation procedures (if any) - this device must be installed by a licensed electrician:
MANUAL OVERRIDE MODE
• How to activate override mode:
When the sensor is in automatic sensor mode and the light is ON, switch the wall switch twice(OFF-ON-OFF-ON) within 5 seconds, the sensor will turn ON-OFF-ON and
enter the override mode. The red indicator LED will then illuminate continuously, the sensor is now in an 8-hour override mode. After this period times out, the sensor will
return to the automatic operation mode.
• How to return to automatic sensor mode:
Switch off the wall switch, wait 10 seconds and then switch it back on, then the sensor will be back in automatic sensor mode.
IMPORTANT: If the power is off for LESS than 10 seconds, the override mode will remain.
• How to activate the photocell mode:
When the sensor is in automatic sensor mode and the connected load is ON, switch the controlling switch three times (OFF-ON-OFF-ON-OFF-ON) within 5 seconds, the
sensor will then revert to the photocell mode.
• Once the photocell mode activated, the red sensor indicator light will continually flash.
• In photocell mode, when the ambient light is daytime (>150LUX) the connected load turns off after 10 seconds and when the ambient light is night-time (<10LUX), the
connected load will operate continuously.
• How to return to automatic sensor mode:
Switch off the wall switch, wait 10 seconds and then switch it back on, then the sensor will revert to the automatic sensor mode.
IMPORTANT: If the power is off for LESS than 10 seconds, the photocell mode will remain. Need to power off 10 seconds before manually changIng from photocell to
override mode.
MANUAL PHOTOCELL MODE:
1. Pressing ON - turns the device ON. Allow warm up for 10 seconds, then the load and the indicator light will operate together.
2. Pressing OFF - turns the the device OFF.
3. Pressing the SENSOR button will activate the sensor mode, resulting in default settings of 10sec hold time, 100% distance sensitivity, daylight sensor disabled. After 10
seconds hold time, if no movement is detected, the connected load will turn off. Should movement be detected within the 10 seconds, another 10 seconds hold time
will be added from the time of the detection.
SENSITIVITY, HOLD TIME AND DAYLIGHT SENSOR buttons are used to change the default settings.
3.1 Pressing the HOLD (TIME) will achieve 10s, 30s, 1min, 5mins, 8mins and 20mins hold time.
3.2 Pressing the SENSITIVITY (SENS) button achieves LOW ≈ 8M, MEDIUM button ≈ 14m, HIGH button ≈ 18M .
3.3 Pressing the DAYLIGHT (LUX) button achieves < 10LUX(NIGHT), LOW button ≈ 25LUX, MEDIUM button ≈ 250LUX, HIGH button ≈ 500LUX, DAY/24H button =24 hour operation.
IMPORTANT - After changing any parameters, the load will turn on and off once to indicating the change.
4. Pressing the PHOTOCELL button will activate the photocell mode. The load will turn ON - OFF - ON once and then enter PHOTOCELL control mode. Photocell range is
<10 LUX (ON) to >150 LUX (OFF).
IMPORTANT: When changing from ANY mode to another mode on romote control, the load will turn ON and OFF as well as a “red” led light flash in the sensor lens, will
indicate the function has been changed.
REMOTE CONTROL FUNCTIONS:
WIRING DIAGRAM
L
Lamp
Lout
Power cable
Brown
(Sensor wire)
Blue
(Sensor wire)
White
(Sensor wire)
Power cable
Lamp wire
Lamp wire
LOAD
LOOP
• Daylight (LUX) threshold dial: Adjust the working state in different values of ambient light. The sensor can operate in the daytime and at night when it is adjusted to the
“LUX” position (max). It can operate in an ambient light less than 10LUX when it is adjusted to the “LUX” position (min).
• Sensitivity (SENS) dial: It can be adjusted according to application. The detection distance is a maximum of 18m.
• HOLD (TIME) dial: HOLD time is added continually. When it receives a second movement signal within the duration of the first detection, it will restart the time delay
from the second signal.
MANUAL SENSOR MODE:
OPTIONAL ACCESSORY - REMOTE CONTROL
OFF
ON
PHOTOCELL
MODE
SENSITIVITY
L/M/H
SENSOR
MODE
DAYLIGHT
SENSOR
HOLD TIME
3. PRESS once, the sensor mode
will operate in default settings
as detailed below
3.2 SENSITIVITY (SENS) OPTIONS
LOW, MEDIUM, HIGH
3.3 DAYLIGHT (LUX) OPTIONS
NIGHT, LOW, MEDIUM, HIGH,
DAY/24h
1. PRESS once the load will turn ON
2. PRESS once, the load will turn OFF
4. PRESS once to activate the
PHOTOCELL MODE
3.1 HOLD (TIME) OPTIONS
10/30 seconds, 5/10/20/30 minutes
SMS806WF
DIMENSIONS:
115 mm
75 mm
140 mm
IMPORTANT -
selection dials
must face down