Mini Air Cooled Chiller
5
Water Discharge
Valve
Electric Heater
Filter
Soft Connect Pipe
Flow Switch
Check Valve
Auto Water Supply
Valve
Auto Discharge
Valve
Thermometer
Pressure Gauge
Safety Valve
valve
Mini Chiller
Expansion Water
Tank
Code
Description
This diagram is for close type water system.
One Way
Different Way
Water System Installation
For pipe connection, please refer to diagram No. 3. Some of the accessories are provided by
TICA.
3.
Important Points:
The water flow switch must be installed on the horizontal straight pipes and keep the
distance of 5 times of pipe diameter from the elbow or valve etc. The flow switch must
be installed.
The close type expansion tank is used to protect the water pipe from breaking caused over
high pressure.
The auto water supply valve and water discharge valve. When water pressure drops, the
water supply valve will open automatically. When the water pressure is over 5bar, the
water discharge valve will open to discharge the water. The water supply pressure can
be determined by the actual situation at site.
To avoid frequent stop the unit, the water tank needs to be installed.
Install an air discharge valve at the top of the whole water system and some higher
places.
Well insulate the water pipes.
Install the pressure gauge and thermometer at the water inlet/outlet.
Di st ance t o
Wal l
>
500mm
>
800mm
Di st ance t o
Wal l
>
500mm
>
1500mm
>
500mm
400mm