Sakura FVCA Series Installation, Operation And Maintenance Manual Download Page 14

Mini Air Cooled Chiller 

13 

 

4.

 

  

 

Test Run and Operation 

1. Voltage Range 

The power supply must comply with requirements.  The fluctuation of voltage must be

 

kept in the stated range.

 

The voltage among each phase must be within 

±

10% of the stated voltage.    Improper 

voltage may cause control problem and shorten the electric components and compressor’s 

life span. 

        If  the  voltage  between  three  phase  are  not  well  balanced,  it  will  cause  motor  overheat.   

The max voltage difference is 2% among each phase.     

Voltage imbalance%=100*|Va-Vd|/Va 

Average Voltage

Va=

V1+V2+V3

/3          Voltage of Each Wire

V1

V2

V3 

Max Va Voltage among wires

Vd 

2.

 

  

 

Water Flow Rate 

Low  flow  rate  will  result  in  abnormal  unit  pressure  and  unit  stoppage.    It  will  also 

produce  low  water  leaving  temp,  which  may  freeze  the  heat  exchanger.    The  high  pressure 

caused by large water flow rate will damage the water pump and the whole water system. 

Recommended Water Flow Rate

:(

m

3

/h

 

Unit 

Pipe Size 

Min 

  

  

  

  

Flow Rate 

Standard 

Flow Rate 

Max 

   

   

   

   

Flow Rate 

FHCA40 

1" 

1.056 

1.6 

2.4 

FHCA50 

1" 

1.188 

1.8 

2.7 

FHCA60 

1" 

1.452 

2.2 

3.3 

FVCA50 

1 1/4" 

1.155 

1.75 

2.625 

FVCA60 

1 1/4" 

1.551 

2.35 

3.525 

FVCA80 

1 1/4" 

2.178 

3.3 

4.95 

FVCA100 

1 1/4" 

3.036 

4.6 

6.9 

FVCA120 

1 1/4" 

3.564 

5.4 

8.1 

FVCA150 

1 1/4" 

4.62 

10.5 

FVCA200 

1 1/2" 

5.76 

8.7 

13.05 

Check following items before starting the unit 

※ 

Check all the wire connections and make sure all the wires are properly connected. 

※ 

Check if the phases are correct and if the voltage is in the normal range.   

※ 

Fill  in  the  water  and  open  the  air  discharge  valve  to  make  sure  the  system  is  filled 

with water. 

※ 

Put power on and check if the flow switch is closed.    Start the water pump and make 

the  water  circulate  to  check  if  there  is  a  leakage and  if  the  water  flow  rate  is  in  the 

normal range. 

※ 

Water flow switch

Operate the water pump and adjust the water flow rate to the half 

of the max flow rate and put the water flow switch off. 

 

Summary of Contents for FVCA Series

Page 1: ...Air Cooled Mini Chiller Installation Operation and Maintenance Manual Models FVCA 40 200 B R 50 80 C R Ref S 080 05 12 Sakura Air Conditioner User friendly Earth friendly...

Page 2: ...ed Mini Chiller Installation Operation and Maintenance Manual Note Please read this Manual carefully before install and operate the unit and keep it probably for reference in the future Air Cooled Min...

Page 3: ...Mini Air Cooled Chiller 2 Contents 1 Notes on Safety 3 2 Installation 4 3 Electric 6 4 Test Run 12 5 Control 14 6 Service and Maintenance 16...

Page 4: ...ers or dealers Don t install the unit by yourself which may cause water leakage electric shock or fire Caution Please install the electric cutoff The main control must use same power supply with the u...

Page 5: ...nstallation The base of the unit can be made of concrete The unit also can be set on the supporter which can be installed on the wall or pillar An isolator pad should be used between the unit and base...

Page 6: ...or valve etc The flow switch must be installed The close type expansion tank is used to protect the water pipe from breaking caused over high pressure The auto water supply valve and water discharge v...

Page 7: ...alve is recommended Auto Water Supply Valve Auto water supply valve can be either vertically or horizontally installed at the water return circuit but not upside down The water supply volume should be...

Page 8: ...llowing chart is the minimal requirement Model Power Min Wire Current Mini Power Supply FHCA40C R 220 50 1 25 6 FHCA40B R 380 50 3 12 5 2 5 FHCA50B R 380 50 3 13 5 4 FHCA60B R 380 50 3 14 4 FVCA50C R...

Page 9: ...Sensor Outer Coil 1 Sensor Water Leaving Temp Sensor 50 Ambient Temp Sensor Return Water Temp Sensor 2 12 MMP 2 13 8 P 9 S R T 50 White White Low Pressure Switch Power Supply Protection KM1 2 FR1 2 F...

Page 10: ...oi l 2 Sensor O ut er Coi l 1 Sensor MMP Am bi ent Tem p Sensor Pl ease i nst al l t he f l ow sw i t ch ot her w i se t he syst em w i l l al ar m W i r e cont r ol Fl ow Sw i t ch Pow er Suppl y Pr...

Page 11: ...W W at er Leavi ng Tem p Sensor O ut er Coi l 1 Sensor Am bi ent Tem p Sensor Ret ur n W at er Tem p Sensor P P Low Pr essur e Sw i t ch Pow er Suppl y Pr ot ect i on KM 1 2 FR1 2 FL M M P LP RVR Fl o...

Page 12: ...er Leavi ng Tem p Sensor O ut er Coi l 1 Sensor Am bi ent Tem p Sensor Ret ur n W at er Tem p Sensor P P P Low Pr essur e Sw i t ch Pow er Suppl y Pr ot ect i on KM 1 2 FR1 2 FL M M P LP RVR Fl ow Sw...

Page 13: ...l 2 Sensor O ut er Coi l 1 Sensor Ret ur n W at er Tem p Sensor W at er Leavi ng Tem p Sensor Am bi ent Tem p Sensor LP Low Pr essur e Sw i t ch W i r e cont r ol M M P AC Cont act or Fl ow Sw i t ch...

Page 14: ...mage the water pump and the whole water system Recommended Water Flow Rate m3 h Unit Pipe Size Min Flow Rate Standard Flow Rate Max Flow Rate FHCA40 1 1 056 1 6 2 4 FHCA50 1 1 188 1 8 2 7 FHCA60 1 1 4...

Page 15: ...2 Put the power on and check water flow rate and if any leakage 3 Put the power on for 24 hours to warm up the compressor before starting the unit 4 System Protection Anti freezing during Winter For...

Page 16: ...he same set information after the electricity is cut off Colorful LCD Display Trouble Codes Display Time clock still works if no electricity 1 Mode Switching the mode by pressing the mode key 2 Temper...

Page 17: ...The system can keep some important data such as the set temp password etc 10 Trouble Codes Code Item Condition 2 Low Temp Compressor Stop Water Pump still works 3 High Temp Compressor Stop Water Pump...

Page 18: ...ription Remark C1 Coil Temp Display Use set key to select the corresponding system coil temp C2 Water Leaving Temp C3 Outdoor Temp 12 Pre heating on compressor oil If to pre heat the compressor oil th...

Page 19: ...ng term stoppage Before starting the unit next time fill in the water and check the unit again Warming up the unit for 6 hours and make sure the unit is in good condition then start the unit Note Sepa...