3) Transportation
To move or lift the unit, attach ropes to the hoisting hangers (4 pieces)
available on the edge of the unit. Apply protector or support to avoid the
ropes direct contact with coil and panel as shown in the diagram.
4) Water Piping
a) Air vent must be installed at the highest position. Open the air vent to
release the air trapped in the water system.
b) It is recommended to install water tank to lower the frequency of
compressor loading and unloading during low load condition. Ensure the
water volume in the system does not less than 10L/kw (water
volume/load).