9
(This charging here refers to the mains charging instead of
solar charging.For solar charger,it will be automatically
charged as long as there is solar power).
9
Charger current of
2
nd
Charge period
10.0
Set between 1-40A. For example
:
10.0 means the charge
current of 2
nd
charging period is 10A. (This charging here
refers to the mains charging instead of solar charging.For
solar charger,it will be automatically charged as long as
there is solar power).
10
1
st
Start discharging
Time
00
:
00
Setting between 0-23 hour and 0-59 minute. For example,
set as 08:00, it means the system will discharge battery
power to the grid (feed to grid) from 08:00 in 1
st
discharging period.
11
1
st
discharge period
00
:
00
Set between 0-11 hour and 0-59 minute. For example, the
setting is 03:20, it means the 1
st
discharging period is 3
hour and 20 minutes (if the timing mode is started, but
don’t want it discharge,change the discharge period to
00:00 directly, then 1
st
discharge period will not work)
12
Mini. SOC of 1
st
discharge period
50%
Set between 20%-100%;for example,set as 50% it means
the system will stop discharge battery power to the grid
(feed to grid) once the battery SOC reaches to 50% in the
1
st
discharge period. The SOC will be compared with the
discharge time, whichever arrives first and it stops first. For
example:
SOC is set as 50%, while the discharging(feeding to grid)
time is set as 10 minutes. When battery SOC discharges to
60%, but the discharge time already reach to 10 minutes,it
will stop discharging(feeding to grid) also.
Another example:
SOC is set as 50% and the discharging time is set as 10
hours. If the battery is discharged to 50% less than 10
hours,the system will also stop discharging to grid before
reach the set time.
(This discharging/feeding to grid has nothing to do with
solar power.For solar charger,it will be automatically
charged as long as there is solar power).
13
Discharge current of
1
st
discharge period
20.0
Set between 1-20A. For example
:
20.0 means the charge
current of 1
st
discharging period to grid is 20A. (This
discharging here refers to battery power feeds to grid.For
example,if it set as 20A, the battery power feeds to grid is:
26V*20A=520).
14
2
nd
Start discharging
Time
00
:
00
:
Setting between 0-23 hour and 0-59 minute. For example,
set as 12:00, it means the system will discharge battery
power to the grid (feed to grid) from 12:00 in 2
nd
discharging period.
15
2
nd
discharge period
00
:
00
:
Set between 0-11 hour and 0-59 minute. For example, the
setting is 04:00, it means the 2
nd
discharging period is 4
hour(if the timing mode is started, but don’t want it