Disconnect the product from the power mains prior to all operations 
specific to connection, setup, maintenance and repair.
Fan maintenance and installation shall only be performed by professional 
electricians qualified for unassisted operations with electrical installations 
up to 1000 V after careful study of the present manual. 

All the fans are not designed for out-of-the-box operation and require 
connection to the air ducts.

The ducts are connected to the fan on both sides.
If the fan is mounted outdoors it should be protected against the elements 
and moisture (e.g. by means of a top hood above the fan).
Prior to connecting the fan to the power mains check for visible damage 
of the casing and any foreign objects in the fan casing which may damage 
the impeller blades.

The fan may only be used as intended. No modifications or alterations 
are allowed. The fan is not intended for operation in areas with an explosive 
and/or chemically aggressive environment. 

Take all the reasonable steps to prevent back draft of gas from any units 
which utilize gas or direct flame. 

The fan is rated for connection to single-phase ac 230 V / 50 Hz and 
three-phase 380/50 Hz power mains. 

Prior to the fan installation check the integrity of the power supply wires 
and for any obstructions to the impeller wheel.

It is recommended that flexible inserts are mounted on both sides of the fan 
upstream and downstream.

Mount the fan in such a way that the arrow on the fan casing matches the 
air flow direction in the system.

The fan requires reliable grounding. 

SAFETY REQUIREMENTS

INSTALLATION AND OPERATION INSTRUCTIONS

KSK

KSK

Summary of Contents for VRPK 150 4D

Page 1: ...VRPK SERIES USER S MANUAL KITCHEN FAN IN SOUND INSULATED CASING ...

Page 2: ...stallation and Operation Instructions 7 Fan Structure 8 Fan Installation 9 Connection to power mains 10 Troubleshooting and fault handling 11 Storage Regulations 12 Manufacturer s Warranty 13 Acceptance Certificate 14 Warranty Card 2 đ 3 đ 3 đ 3 đ 3 đ 5 đ 5 đ 6 đ 6 đ 8 đ 10 đ 10 đ 11 đ 12 đ 12 CONTENTS ...

Page 3: ...ts access and water ingress protection standard The motor insulation is F rated The delivery set includes Fan 1 piece User s manual Packing The fan designations their parameters and connecting dimensions are given in Tables 1 and 2 as well as on Fig 1 Outlet Duct Diameter 150 160 200 250 mm Fan Name VRPK centrifugal fan in noise reduction casing Designation Example VRPK 160 4Ĺ centrifugal fan in a...

Page 4: ...0 50 380 50 230 50 380 50 230 50 380 50 1 7 0 6 1 7 0 6 3 0 2 0 11 0 3 4 180 180 180 180 550 750 1500 1500 1450 1455 1450 1455 1475 1465 1500 1470 100 100 100 100 100 100 100 100 VRPK 160 4E VRPK 160 4D VRPK 150 4E VRPK 150 4D VRPK 200 4E VRPK 200 4D VRPK 250 4E VRPK 250 4D 160 150 200 250 410 410 330 330 485 365 575 435 540 540 600 665 365 365 425 505 525 525 500 500 625 600 700 675 470 470 475 4...

Page 5: ...y foreign objects in the fan casing which may damage the impeller blades The fan may only be used as intended No modifications or alterations are allowed The fan is not intended for operation in areas with an explosive and or chemically aggressive environment Take all the reasonable steps to prevent back draft of gas from any units which utilize gas or direct flame The fan is rated for connection to...

Page 6: ...ntenance free The power is adjusted by means of transformer control units The fan is connected to the power mains via the terminal box mounted on the electrical motor Provide an additional electric cable length to ensure unobstructed opening of the swing out motor impelle r unit Check the unpacked fan casing no dents or deformations are allowed and make sure that the impeller has smooth rotation a...

Page 7: ...7 1 2 3 4 5 6 Fig 3 ...

Page 8: ...an The recommended automatic breaker nominal current and conductor sections are given in Table 3 2 The power conductor section is 1 5 mm However the conductor section selection shall account for the maximum permissible wire heating which depends on the wire type its insulation length and installation method i e overhead duct layout or inside the walls The trip current shall be consistent with the ...

Page 9: ...mmended cable n x S where n is the number of wires 2 and S is the section in mm Fan Type 2 1 2 1 8 3 15 12 5 4 2 õ 1 5 3 õ 1 5 2 õ 1 5 3 õ 1 5 2 õ 1 5 3 õ 1 5 2 õ 1 5 3 õ 1 5 Connection Diagram for fans VRPK 150 4E VRPK 160 4E VRPK 200 4E VRPK 250 4E with Single Phase Motor to AC Mains Wiring Diagram for fans VRPK 150 4D VRPK 160 4D VRPK 200 4D VRPK 250 4D with Three Phase Motor to AC Mains W1 V1 ...

Page 10: ... Noisy operation Check the power switch Check electrical connections against the wiring diagram Clean the impeller The fan should be stored in the original packing in a ventilated area at temperatures from 5 C to 40 C and relative air humidity not more than 80 at Ň 20 C STORAGE REGULATIONS TROUBLESHOOTING Fig 6 ...

Page 11: ...s are offered at Seller The accessories operated together with the unit both included and not included into the delivery list as well as other equipment operating jointly with the unit shall not be covered by the warranty No warranty for compatibility of the fans with other producers goods Only manufacturing defects are covered by the warranty terms All the defects and faults resulting from mechani...

Page 12: ...ognized as serviceable Model VRPK ______________ tick the proper model ACCEPTANCE CERTIFICATE WARRANTY CARD Date of production Stamp of the acceptance inspector Sold by name of the vendor stamp of the shop Date of sale ...