Commands by the serial interface
PCD7.D250
Page 6-8
SAIA-Burgess Electronics Ltd.
(D25-06-E.DOC)
26/770 E1
6.3 Display control
Clear display
Clear display sets all the characters on the display to spaces, and moves
the cursor to the home position.
Command
ASCII
Decimal
Hex
Clear display
CTRL+L
12
0C
Save display/Restore display
Ten save/restore areas are provided, numbered 0 to 9. Restoring from a
display area that was not previously saved will produce a blank screen
with cursor on. The content of the stored areas is lost when the ..D250 is
powered off.
Command
ASCII
Decimal
Hex
Save display ‘n’
ESC @ S n
27 64 83 n
1B 40 53 n
Restore display ‘n’
ESC @ R n
27 64 82 n
1B 40 52 n
for „n“ =
0...9
48..57
30...39
Backlight off/on
The backlight is normally always on, and is required to make the text
visible. The backlight can be turned off and on (blinked) to provide a
visual indication of an alarm etc.
Command
ASCII
Decimal
Hex
Backlight off
ESC O
27 79
1B 4F
Backlight on
ESC L
27 76
1B 4C