Saia-Burgess Controls AG
Manual PCD7.D412DTPF & PCD7.D4xxxT5F │ Document 27-620 – Release ENG07 │ 2019-06-20
1-6
Quickstart
1
Setting up communications for displaying a website
1.7
Setting up communications for displaying a website
1.7.1
HTTP Direct over ethernet RJ-45 connector
The quickest communications port is the ethernet port via RJ-45, with the HTTP
Direct protocol selected. The speed is either 10 MBit/s or 100 MBit/s after an auto-
negotiation protocol with the connected device.
Internal connection for programmed pWeb panels
The programmed panels are connected internally directly to the programmable
logic controller, via an ethernet connection. It therefore suffices, in this case, to
simply set the local host IP address 127.0.0.1 and HTTP Direct connection in the
Setup menu under Web connection. The programmable pWeb panels are obvious
-
ly also capable of displaying websites from controllers located within the network.
The procedure for this is the same as with the standard 12” SVGA panel.
Connecting to external devices
If an ethernet connection to an Automation Server exists, the HTTP connection
can be established between our PCD7.D4xx and any SBC controller. In the case
of the programmable panels, the panel is generally connected to the internal con
-
troller.
Ethernet http direct
Quick test of the SVGA panel
■ First the Saia PCD must have a web program loaded which was created with
the Web Editor (see 26-838_Manual_Web-Editor). You can ask the SBC Sup
-
port Team for some examples. They will also soon be available on our website.
■
Using a
CAT5 cable
, you can connect our PCD7.D4xx terminal to the SBC
device. The current controllers support auto-crossing; a crossover cable is thus
no longer required.
■ Using PG5, define the
HW settings of the Saia PCD
device: S-bus support
must be selected together with the TCP/IP channel where a valid IP address is
entered.