PG-B2 (For Flux Vector Control Mode Only)
•
Shielded twisted-pair wires must be used for signal lines.
•
Do not use the PG’s power supply for anything other than the PG. Using it for another
purpose can cause malfunctions due to noise.
•
The length of the PG’s wiring must not be more than 100 meters (328 feet).
•
The direction of rotation of the Inverter can be set in user constant F1-05. The factory preset
if for forward rotation, A-Phase advancement.
Figure 3.26
PG-B2 Wiring
I/O Circuit Configuration
•
When connecting to a voltage-output-type PG, select a PG that has an
output impedance with a current of at least 12 mA to the input circuit
photocoupler (diode).
Figure 3.27
I/O Circuit Configuration of the PG-B2