80
VG5 Installation & Quick-Start Manual
Gr
oup b Ap
pl
ic
ati
on
PID
Cont
ro
l
B5-12
<1110>
PID Feedback Ref-
erence Missing
Detection Selection
(Fb Los Det Sel)
0~2
1
0
0: PID feedback missing
detection disabled. (Dis-
abled)
1: PID feedback missing
detection enabled. (Alarm)
Operation continues after
detection, “Fbl” alarm is dis-
played.
2: PID feedback missing
detection enabled. (Fault)
Inverter output is shut off
after detection, “Fbl” is dis-
played.
x
A
A
A
A
B5-13
<1110>
PID Feedback Ref-
erence Missing
Detection Level
(Fb los Det Lvl)
0~100
1%
0
—
x
A
A
A
A
B5-14
<1110>
PID Feedback Ref-
erence Missing
Detection Time
(Fb los Det Time)
0.0~
25.5
0.1s
1.0
—
x
A
A
A
A
Fu
nc
tion
b6 Ref
erenc
e H
ol
d
B6-01
Dwell Frequency at
Start
(Dwell Ref @Start)
0.0~
400.0
0.1Hz
0.0
—
x A A A A
B6-02
Dwell Time at Start
(Dwell Time @
Start)
0.0~
10.0
0.1s
0.0
—
x A A A A
B6-03
Dwell Frequency at
Stop
(Dwell Ref @ Stop)
0.0~
400.0
0.1Hz
0.0
—
x A A A A
B6-04
Dwell Time at Stop
(Dwell Time @
Stop)
0.0~
10.0
0.1s
0.0
—
x A A A A
Func
tion b7 D
roop
Contr
ol
D
roop
Contr
ol
B7-01
Droop Control Gain
(Droop Quantity)
0.0~
100.0
0.1% 0.0
—
o
- - - A
B7-02
Droop Control
Delay Time
(Droop Delay Time)
0.03~
2.00
0.01s 0.05
—
o
-
-
-
A
Function
Parameter
No.
Name
(Digital Operator
Display)
Setting
Range
Setting
Unit
Factory
Setting
Remarks
(Digital Operator Display)
Change
during
Operation
o: Enabled
x: Disabled
Parameter Access Level
User
Setting
V/f
V/f
w/
PG
Open
Loop
Vector
Flux
Vector
Appendix
VG5 Parameters
Summary of Contents for CIMR-VG5U
Page 2: ...2 VG5 Installation Quick Start Manual This page intentionally left blank...
Page 36: ...36 VG5 Installation Quick Start Manual This page intentionally left blank...
Page 60: ...60 VSG5 Installation Quick Start Manual This page intentionally left blank...
Page 113: ...VG5 Installation Quick Start Manual 113 This page intentionally left blank Appendix Notes...