WSSFCEX-GHC is a Sigfox-Ready sensor with Ex d explosion-proof approve and comes with a built-in high-performance

NDIR technology sensor to detect the Hydrocarbon Gas concentration in the air. Ultra-low-power design and smart

firmware allow the complete Wireless and Sensor package to run on a single battery type C for 3-5 years or more with

15 minutes update.

It is battery-operated and able to connect to any Sigfox network in the World. It supports all frequency zones such as

RC1, RC2, RC3c, RC4, RC5, RC6, and RC7.

Please refer to

 this link 

for the flammable gas sensor's principal operation

.

Please refer to 

this link

 for typical applications.

The device will send uplink messages in the following cases:

Case 1: After power-up in the 60s, the device will send the first message called START_UP. The payload will tell

the user the HW version, FW version, and current configuration of the device;

Case 2: Then, in every interval time (pre-configured), for example, 10 minutes, it will send the message called

CYCLIC_DATA. The payload will tell the user the following data like measured values, battery level, and alarm

status...

Case 3: If the Alarm function was enabled (in the configuration of the sensor), if the measured value passed the

threshold, it will send the uplink message immediately. This message is called ALARM. The payload also tells the

user the data like measured values, battery level, and alarm status...

Case 4: The HEART_BEAT uplink message will be sent once a day (the default setting can be changed in

configuration) to allow the Sigfox back-end system can send the downlink message for changing the

configuration of the sensor. Please refer to the downlink section for more details. The uplink payload will tell the

user the HW version, FW version, and current configuration of the device;

Case 5: During the commissioning, testing, or calibration sensor, the user can force the device to send the uplink

message to get the data immediately. This message is called FORCE_DATA. The payload will provide data like

raw measured value, scaled measured value, battery level, and alarm status... It can be forced by applying the

magnet key on the reed switch in 1s;

Case 6: If users want to change the configuration immediately, they don't need to wait up to 1 day for the

HEART_BEAT message, instead they can force the device to send a special uplink message so that the device can

get the new downlink message. This uplink message is named PARAMETERS_UPDATE. It can be forced by

applying the magnet key in more than 5s.

The sensor was pre-configured at the factory with default values for configuration parameters that meet most use

cases. However, depending on the specific use case, the customer can adjust those parameters. Please refer to

section 3.2

 for more details.

The sensor is powered by 1 x Type C battery 3.6V LiSOCl2 for many years of operation. We do recommend using Saft

LS26500 battery which is suitable for Exd-approved instruments. This battery has a capacity of up to 7700mAh with a
working temperature range from -40 to +85 oC. The instruction for installing the batteries is in 

this link

.

Finish this part so you can understand and put the sensor in operation with the default configuration from the

factory.

1.1 What is the Sigfox-Ready GHC Flammable Gas Sensor and its
principle of operation?

1.1.1 What are the typical applications of this sensor?

1.1.2 When does the device send uplink messages?

To change the cycle of data sending, you can change the value of the parameter: CYCLIC_DATA_PERIOD (default

is 600 seconds).

The alarm thresholds can be changed via downlink or offline tools.

1.1.3 The important configuration parameters

1.1.4 What kind of battery is used for this sensor?

Note: The battery can be inserted into the device in the Safe Zone only!!!

Summary of Contents for WSSFCEX-GHC

Page 1: ...gfox Product Type 1 part Mounting Type Wall mount Powered by 1 x C battery LiSOCl2 recommend SAFT LS26500 Information Changes in this version v s the previous version Item Changes Changed by Changed D...

Page 2: ...the device Case 5 During the commissioning testing or calibration sensor the user can force the device to send the uplink message to get the data immediately This message is called FORCE_DATA The pay...

Page 3: ...late Device PAC Get Devive PAC on the device nameplate 1 2 What s in the package The package includes the following items 01 x Main device 01 x Magnet key 01 x Antenna Type N connector 1 3 Quick Test...

Page 4: ...batteries into the device in Safe Zone Step 2 Add the device to Sigfox Backend Step 3 Install the batteries to the device After installing the battery in 60 seconds the first data packet will be sent...

Page 5: ...iptions Consumable parts replacement Yes The battery is the only part need to check the lifetime to replace Check the battery status on the back end system Cleaning device No Please refer to this link...

Page 6: ...e estimation please refer to this link measure_period Default 300s This is the time period for the wireless transmitter to wake up and take the measurement from the transducer The default value is 360...

Page 7: ..._VERSION string Read 6 6 3 2 HW_VERSION string Read 8 8 3 2 DEVICE_ID hex Read Product ID 10 A 3 4 DEVICE_PAC hex Read Product PAC 14 E 3 1 SENSOR_TYPE 1 255 uint16 Read Sensor or Input Type Read Writ...

Page 8: ...se time in second 307 133 3 16 2 C_H_FACTOR 4 4 float Read Write For methane C h 4 4 vol for propane C h 1 7 vol Please refer to this link Please refer to the detailed specifications inthis link For w...