Power terminals M6

Heat sink

Grounding point M3

Handle

Handle

Unit 1

Unit 1

bus

bus

bus

bus

Unit 2

Unit 2

Unit 3

Unit 3

Unit 

n

Unit 

n

Emergency vent ports

+

+

+

+

+

+

+

+

+

+

-

-

-

-

-

-

-

-

-

-

5. Transportation   

Use the original packaging or 
equivalent. Follow the necessary 
transportation rules for Li-ion 
batteries by consulting with your 
company’s standard practice and 
your local transportation regulations. 
Secure the Evolion

®

 to prevent violent 

shock and other items from falling 
onto it. The Evolion

®

 must be OFF 

during transportation.

6. Installation   

See Figure 4 for Evolion

®

 features.

Pin 1

RS485+

Pin 2

RS485-

Pin 3

Ground (isolated from power terminals)

Pin 4

Wake up (ground referenced)

Pin 5

Reserved

Pin 6

Reserved

Pin 7

Dry contact alarm output

Pin 8

Dry contact alarm output

IMPORTANT:

 A reverse connection 

on the power terminals may cause 
an internal fuse fault. See Section 
10 if replacing the fuse is necessary.

Connect communication

See Table 4 for RJ45 jack pin 
assignments.

Table 4 - RJ45 pin assignments 

Both RJ45 jacks are interchangeable 
and can be used to plug either the 
communication cable (772518) or 
the RJ45 resistor cap (773455).
To access the dry contact alarm 
signal, use pins 7 and 8. Both minor 
or major alarm signals are reported 
and the default state of the pin is as 
follows:
CLOSED = ALARM/power down
OPEN    = NO ALARM
Use the communication cable 
provided. See Figures 7 and 8.

Make sure to conduct an Evolion

®

 

Installation and Commissioning 
(I&C) prior to startup. Setting a 
unique node ID (default = 1) for 
each parallel connected Evolion

®

 is 

necessary in order to communicate 
using the Saft Evolion

®

 Toolbox 

software during operation.

IMPORTANT:

 Never connect the 

power terminals in series with other 
Evolion

®

 units. The Evolion

®

 may be 

damaged and rendered inoperable.

IMPORTANT:

 Parallel connecting can 

be done as long as the total system 
discharge current never exceeds 
130 A (5 kW at 42 V) continuous.  
In this case paralleling any number of 
units is allowed.

Make sure to never parallel connect 
Evolions that have more than 2 V 
difference between the modules. 
Equalizing the voltage by charging or 
discharging modules separately may 
be necessary. To check the open 
circuit voltage when disconnected, 
press the ON/OFF button for at 
least 2 seconds and measure the 
voltage at the terminals. Make sure 
to turn the unit OFF by pressing 
the ON/OFF button for at least 4 
seconds.

The Evolion

®

 limits its own current 

with a built in charge regulated 
circuit. However, starting up 
the Evolion

®

 to avoid the charge 

regulated mode is important to avoid 
a possible internal fuse fault.
Make sure to switch off the battery 
breaker(s) before connecting Evolion

®

 

power terminals to the power bus.
The Evolion

®

 power terminals can be 

connected to systems with a positive 
ground, a negative ground or a 
floating ground system.
In order to prevent reverse connections, 
make sure to measure and note the 
polarity of the power bus cables.

Never block the heat sink.

Do not obstruct the emergency 
vent ports.

Install in environment with IP55 
(NEMA3 outdoor) or higher 
protection index.

95% maximum humidity  
(non-condensing)

Overall installation steps  
(details follow):
1. Connect power
2. Connect communication (optional)
3. Startup

Required tools

• 10 mm socket (for terminal)
• Multimeter (60 Vdc, ohms)
• Flat screwdriver (for cover removal)
• 7 mm socket (for fuse)
• Torque wrench (insulated)

Connect power

Always connect the Evolion

®

 using 

the provided cables in order to 
balance the resistance in each 
branch. See Figures 5 and 6 for power 
connections schematics and options.

Figure 4 - Evolion

®

 features (oriented 

upright with front and back view) 

Figure 6 - Parallel connecting Evolions

OPTION 1 - For any 

number of 

parallel 

chained

 Evolions, 

take off the power 

bus connection 

at the end of the 

parallel connected 

system. This is the 

best way to balance 

the resistance of 

each.

NOTE: Can only be 

used when the total 

continuous bus 

current is less than 

or equal to 63 A.

OPTION 2 - For any 

number of 

direct 

connected 

Evolions, 

using the same 

length of cable 

for each will make 

sure to balance the 

resistance.

Figure 5 - Connecting to terminals

•  Only use the terminal bolts, washers, 

terminal protectors and cable lugs 

provided.

•  Terminal bolt torque = 6 N.m (53 in.lbs)